Centurion 04791-0 Скачать руководство пользователя страница 9

Generac

®

Power Systems, Inc.

7

Section 2 – Operation

CENTURION 3500 Home Standby Generator

1.6.4 ENGINE

Type of Engine ............................GN-220, Single-cylinder
Cooling Method..................................................Air-cooled
Rated Horsepower ..................................7.8 @ 4,200 rpm
Displacement............................................................220cc
Cylinder Block ....................Aluminum w/Cast Iron Sleeve
Type of Governor ........................Mechanical, Fixed Speed
Air Cleaner ..................Paper Element w/Foam Precleaner
Starter ................................................12-volt DC Electric
Ignition System ................Solid-state w/Flywheel Magneto
Recommended Spark Plug

Champion ..........................................................RC12YC
AC ..........................................................................R45S
Fram Autolite ..............................................................65

Spark Plug Gap ..................................0.03. inch (76 mm)
Recommended Minimum

Battery ......................................235cc Amperes @ 32°F/

195cc Amperes @ 0° F

1.6.5 GENERATOR

Rated Maximum Continuous

AC Output (LP) ................................3,400 Watts (3.4kW)

Rated Voltage ................................................120 Volts AC
Rated Maximum Continuous

AC Current (LP) ........................................28.3 Amperes

Phase ......................................................................Single
Rotor RPM................................................................3,600
Number of Rotor Poles ....................................................2
Engine RPM ..............................................................3,600
Rated AC Frequency ................................................60 Hz
Battery Charge Voltage ....................................14 Volts DC
Battery Charge Current ..........................2 Amperes (max)
Length ..................................................843 mm (33.2 in.)
Width ....................................................504 mm (19.8 in.)
Height ......................................................966 mm (38 in.)
Weight ......................................................90 kg (275 lbs.)

2.1  GENERATOR CONTROL PANEL

The following features are mounted on the generator
control panel (Figure 2.1):

Figure 2.1 — Generator Control Panel

2.1.1 SHUT DOWN INDICATOR

This LED will flash a specific number of times to indi-
cate a specific failure. Shutdowns and their failure
codes follow in Section 2.9, Protection Systems. These
codes can also be referenced on the decal located on
the air filter cover, located below the control panel.

2.1.2 AUTO/OFF/MANUAL SWITCH

2.1.2.1   Auto Position

Selecting this switch position activates fully automat-
ic system operation. It also allows the user the abili-
ty to start and exercise the generator from the remote
Power Transfer Monitor.

2.1.2.2   Off Position

This switch position shuts down the engine. This
position also prevents the engine from starting.

2.1.2.3   Manual Position

Selecting this switch position will crank and start the
engine. Transfer to standby power will not occur
unless there is a utility failure.

With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automatic starting normally occurs when
utility power source voltage drops below a pre-
set level or during the normal exercise cycle. To
prevent possible injury that might be caused by
such sudden starts, always set the switch to
OFF and remove the fuse before working on or
around the generator or transfer switch. Then,
place a “Do Not Operate” tag on the generator
panel and on the transfer switch.

2.1.3 FUSE

The generator panel's 7.5 amp fuse protects the DC
control circuit against overload. The fuse is wired in
series with the battery output lead to the panel. If the
fuse element has melted open, the engine cannot
crank or start. The same fuse also protects the bat-
tery charge circuit against overload. If the fuse ele-
ment has melted open, battery charging will not be
possible. Replace the fuse using only an identical 7.5
amp fuse.

2.1.4 MAIN BREAKERS

The main breakers protect the generator’s AC output
circuit against overload and provide a method of
turning OFF the generator’s 120-volt AC output to the
Power Transfer Monitor’s outlets. The CENTURION
3500 has two (2) 15-amp breakers.

‹

‹

!

‹

‹

15

15

PULL TO DISCONNECT

GENERATOR POWER

CONTROL CENTER

AUTO

DETAILS

OFF

SEE CHART
BELOW FOR

DOWN

INDICATOR

SHUT

MAN.

GREEN BAR INDICATES TRIP

PUSH TO RESET

GENERATOR

POWER

FUSE

7.5A

‹

‹

Содержание 04791-0

Страница 1: ...0 Air cooled Prepackaged Automatic Standby Generator Model 04791 0 3 4kW LP Not intended for use as Primary Power in place of utility or in life support applications This manual should remain with the...

Страница 2: ...personal safety and or property of others This symbol points out potential explosion haz ard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard CONT...

Страница 3: ...ne Oil Level 12 3 2 Changing the Engine Oil and or Oil Filter 12 3 3 Maintaining the Engine Air Cleaner 13 3 4 Clean Air Intake 14 3 5 Checking the Engine Spark Plug 14 3 6 Clean Spark Arrestor 14 3 7...

Страница 4: ...hing muscles e throbbing temples f dizziness g headaches h weakness and i sleepiness IF EXPERIENCING ANY OF THESE SYMPTOMS MOVE INTO FRESH AIR IMMEDI ATELY IF SYMPTOMS PERSIST GET MEDICAL HELP Shut do...

Страница 5: ...ved or disassembled during routine mainte nance If the grounding conductor must be replaced use only a flexible conductor that is of No 12 American Wire Gauge AWG copper wire minimum In case of accide...

Страница 6: ...Brace 19 Exhaust Hood Tailpipe and Spark Arrestor Inside 20 Ground Lug 21 Data Decal Located inside compartment Section 1 General Information CENTURION 3500 Home Standby Generator Please record the fo...

Страница 7: ...utlet is powered by the utility and by the gen erator When utility power is present is acts as anoth er normal household outlet When the generator is supplying power this outlet is then being supplied...

Страница 8: ...air is always available Consider these factors Install the unit where air inlet and outlet openings will not become obstructed by leaves grass snow etc If prevailing winds will cause blowing or drift...

Страница 9: ...allows the user the abili ty to start and exercise the generator from the remote Power Transfer Monitor 2 1 2 2 Off Position This switch position shuts down the engine This position also prevents the...

Страница 10: ...nerator set inside any enclosed area make sure THE EXHAUST SYSTEM IS not LEAKING AND HAS NOT BEEN DAMAGED SYMPTOMS OF CARBON MONOX IDE POISONING ARE a inability to think coher ently b nausea c vomitin...

Страница 11: ...be washed down with an acid neutralizing agent A common practice is to use a solution of one pound 500 grams bicarbon ate of soda to one gallon 4 liters or water The bicarbonate of soda solution is t...

Страница 12: ...n the Power Transfer Monitor should have power Confirm trans fer of power by depressing the test buttons on both GFCI outlets Each one should trip and the indicator will illuminate With the generator...

Страница 13: ...mage by shutting it down if it happens to run faster than the preset limit This protection also prevents the gener ator from supplying an output that could potentially damage appliances connected to t...

Страница 14: ...IN CHECK UP After the break in period the owner should perform the following maintenance items Change the engine crankcase oil and oil filter Check the oil level Inspect the cooling and ventilation op...

Страница 15: ...e new filter Fill the filter until saturated with clean oil 6 Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter Then tight en the filter an additional 3 4 to one...

Страница 16: ...ns Use the following procedure Figure 3 2 1 Follow steps 1 3 in Section 3 3 1 service the foam precleaner if necessary 2 Remove the paper filter 3 Clean the air filter by tapping it gently on a solid...

Страница 17: ...NTENANCE All lead acid batteries will discharge when not in use The generator battery should be inspected as follows 3 8 1 EVERY SIX MONTHS Inspect the battery posts and cables for tightness and corro...

Страница 18: ...cise approximately 1 5 minutes for every second that the starter motor cranks during engine start up The unit will run for a minimum of two minutes and a maximum of 20 minutes based on the crank time...

Страница 19: ...1 Loosen the rocker arm jam nut Use an allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge Figure 3 6 Figure 3 6 Adjusting...

Страница 20: ...18 Generac Power Systems Inc PART II INSTALLATION INSTRUCTIONS ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION DANGER...

Страница 21: ...IST GET MEDICAL HELP Shut down the generator and do not operate it until it has been inspected and repaired The engine exhaust fumes contain carbon monox ide which can be DEADLY This dangerous gas if...

Страница 22: ...ch so as to isolate the gen erator electric system from the electric utility dis tribution system when the generator is operating Failure to isolate the two electric system power sources from each oth...

Страница 23: ...or Adjustable Wrenches Socket Wrenches or Nut Drivers Standard and Phillips Screwdrivers Level Sledge Hammer Channel lock Pliers Spade Shovel and Safety Goggles 1 2 ITEMS THAT MUST BE PURCHASED 2 20 p...

Страница 24: ...to grade A Attach one end of the grounding strap No 12 AWG stranded copper wire to grounding rod and the other end to the grounding lug located at rear of unit Make sure grounding rod and strap are no...

Страница 25: ...R Hold the Power Transfer Monitor in desired location and mark the mounting holes The mounting holes are 1 4 inch in diameter Drill pilot holes Use two fasteners which are appropriate for the area for...

Страница 26: ...t or to the right to desig nate which tank will be the primary or service cylin der tank That tank will supply fuel to the generator first When the lever is moved to a position an indi cator will show...

Страница 27: ...as clogging is a potential cause of regulator malfunction Great care has been taken in the manufacture of the regulator and it has been thoroughly tested and UL listed However even a small piece of d...

Страница 28: ...r leaks 2 Oil Pressure switch is defective 2 3 Oil is contaminated with dirt 3 Change oil and oil filter HIGH TEMPERATURE 1 Engine oil is low 1 Check and fill engine oil 5 Flashes of LED 2 Air flow is...

Страница 29: ...Generac Power Systems Inc 27 Appendix 2 Notes CENTURION 3500 Home Standby Generator...

Страница 30: ...28 Generac Power Systems Inc Appendix 2 Notes CENTURION 3500 Home Standby Generator...

Страница 31: ...Generac Power Systems Inc 29 Appendix 2 Notes CENTURION 3500 Home Standby Generator...

Страница 32: ...ITCH ON OFF 125V 15A SW1 AUTO OFF MANUAL SWITCH ON OFF 125V 15A SM STARTER MOTOR SC STARTER CONTACTOR LOP LOW OIL PRESSURE SWITCH GRD2 CONTROL PANEL GROUND ISOLATED GRD3 POWER STRIP GROUND F1 FUSE 7 5...

Страница 33: ...1A 44 44A 44A 44A 44A 44A 17 0 0 0 UTILITY 11E GENERATOR 11E 11D 11E TB1 TB2 L2 L1 SR SW3 0 0 0 0 CB2 CB3 0 2 22 66 77 11C 4 POWER STRIP WIRING 0 GFCI GFCI 0 22 22 GRD 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SW...

Страница 34: ...3 2 2 66 77 15 0 SW1 9 14 13 12 11 10 6 8 7 5 J1 4 3 1 2 44 11 44 11 11 11 0 0 0 0 14 17 4 6 13 56 2 CB 1 2 15 2 85 86 18A 0 0 0 17 17 17 6 6 4 22 11 LED ALARM INDICATOR LOP LOW OIL PRESSURE SWITCH S...

Страница 35: ...6 77 66 77 66 77 66 77 77 66 17 22 11 11 44 17 13 6 2 11 44 2 18A 18A 56 14 6 4 0 4 0 0 2 6 86 85 0 0 11 4 13 17 44 11 44 22 11 22 11 ENGINE AND ALTERNATOR 11 0 0 0 0 CONN 1 5 11 L1 11F 11A L2 CB 2 0...

Страница 36: ...11 9 8 11 5 20 0 15 14 13 17 3 7 11 11 39 38 19 47 10 47 31 32 33 1 4 34 29 28 21 22 5 24 37 10 23 46 45 44 43 42 41 40 12 49 50 48 12 45 51 42 52 35 53 12 55 56 54 Appendix 4 Exploded Views Parts Li...

Страница 37: ...BACK 24 0C2506A 3 MESH DOOR PANEL 25 0D7176 12 WASHER SELF LOCKING 1 DIA 12GA 26 0D8254 1 SHIELD MUFFLER 27 0E2099 1 PANEL REAR DIVIDER 28 0E5685C 1 FOAM ENGINE COMPARTMENT FRONT 29 0E5685B 2 FOAM FAN...

Страница 38: ...Views Parts Lists CENTURION 3500 Home Standby Generator Generator Drawing No 0E2151 A 1 4 6 5 2 8 10 2 18 36 8 9 1 20 38 20 23 20 21 21 2 18 21 2 18 23 24 25 26 27 28 29 30 31 32 33 34 29 24 35 22 2 1...

Страница 39: ...1 BRACKET ENGINE MOUNTING 18 022145 19 WASHER FLAT 5 16 19 030231 3 SCREW HHC 5 16 18 X 1 1 2 20 0C3168 4 5 16 SPECIAL LOCK WASHER 21 022259 8 NUT HEX 5 16 18 22 0C8565 1 SCREW SHC M8 1 25 X 18MM 23...

Страница 40: ...er Systems Inc 15 14 3 24 28 17 18 19 20 21 6 7 8 9 5 4 11 13 23 22 2 1 16 28 25 10 29 12 6 7 6 8 30 31 Appendix 4 Exploded Views Parts Lists CENTURION 3500 Home Standby Generator Control Panel Drawin...

Страница 41: ...MINAL STRIP 2 POSITION 12 0E5840 2 CIRCUIT BREAKER 15A PUSH PULL MAIN RESET 13 0E2042 1 INDICATOR LIGHT 14 0A9611 1 FUSE AGC 7 5A 15 032300 1 FUSE HOLDER 16 0E4494 1 SWITCH ROC DPDT ON OFF ON 17 0E510...

Страница 42: ...7 8 15 16 17 16 15 10 1 12 13 14 19 20 20 21 22 23 26 27 28 31 30 36 35 9 33 37 45 44 41 42 9 38 39 40 9 34 52 53 54 6 9 Appendix 4 Exploded Views Parts Lists CENTURION 3500 Home Standby Generator Gn...

Страница 43: ...666 1 BREATHER TUBE 20 090051 1 GASKET MANIFOLD HEAD 21 080316 2 SCREW HHFC M6 1 0 X 30MM 22 090948 1 INTAKE MANIFOLD 23 078631 1 GASKET CARBURETOR MANIFOLD 24 0E2094 1 CARBURETOR 25 091846 1 GASKET C...

Страница 44: ...22 24 25 48 30 17 13 28 4 18 40 37 36 46 39 38 21 29 16 35 33 15 32 31 5 41 49 27 1 47 51 12 7 19 1 2 3 9 13 11 10 6 7 50 52 Appendix 4 Exploded Views Parts Lists CENTURION 3500 Home Standby Generator...

Страница 45: ...STEM SEAL 21 0A8822 1 CYLINDER HEAD GASKET 22 078691 1 OIL PRESSURE RELIEF COVER 23 0A5772 1 OIL PRESSURE SPRING 24 0A5776 1 11 32 BALL 25 074908 1 M5 FORM SCREW 26 078606 4 M6 1 0 X 12MM SCREW 27 07...

Страница 46: ...25 26 32 26 11 9 14 REGULATOR 24 23 22 21 20 19 17 16 34 29 37 28 30 33 21 20 27 8 2 31 9 41 42 39 36 15 50 51 45 46 40 47 18 38 10 11 48 49 52 Appendix 4 Exploded Views Parts Lists CENTURION 3500 Ho...

Страница 47: ...RAME ASSEMBLY LP ENCLOSURE 27 0E3163 1 BOX BATTERY REGULATOR 28 0C8285 1 BRACKET BATTERY HOLD DOWN 29 0E2038 1 PANEL TANK ENCLOSURE BACK 30 0E3164 1 COVER BATTERY REG BOX 31 0E1805 1 TRAY TANK ENCLOSU...

Страница 48: ...erac Power Systems Inc 5 6 4 3 2 7 8 1 10 9 11 12 13 14 15 19 21 22 23 24 25 26 16 17 18 20 27 28 Appendix 4 Exploded Views Parts Lists CENTURION 3500 Home Standby Generator Gas Regulator Drawing No 0...

Страница 49: ...STD PIPE 1 8 STEEL SQ HD 13 0D3308 2 WASHER FLAT 3 2MM ID X 10MM OD 14 070728 2 SCREW PFILHM M3 0 5 X 5 15 0C5764A 1 SPRING REGULATOR 16 0C4643A 1 INLET TWIN REG 11 11 DIA 17 0C6066 1 SEAL INLET REGU...

Страница 50: ...eglect improper maintenance or unap proved modifications or the use of counterfeit and or grey market parts not made supplied or approved by Generac You are responsible for presenting your engine to a...

Страница 51: ...ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions related part 4 Repair or replacement of any warranted em...

Страница 52: ...dent misuse abuse negligence or improper installation As with all mechanical devices the Generac engines need periodic part s service and replacement to perform well This warranty will not cover repai...

Отзывы: