J.
Load Detection Circuit
The load detecting circuit is showed on Figure S-9. The output current is sensed by
current transformer CT01. It decrease 1000 times of output current for CPU detection. The
current signal decreased from CT01 pass through a full bridge rectifier and across R36 to get
a voltage signal. After the voltage signal divided by R34,R102 to get 0~5 Volts. signal, the
CPU can get output current value of UPS.
1.
At line/booster/buck mode : The current value multiplies output voltage to get output VA
value.
2.
At battery mode : Because the power factor of square wave is approximately equal 1. The
current value multiplies 120V(230V)output voltage to get output Watt value.
ZD03 is added for protection of rectifier. They can clamp voltage spike while there is a
large current occurs.
Figure S-8 Load Detecting Circuit
26
Содержание 400VA
Страница 8: ...Figure S 1 Control Power circuit 6 ...
Страница 9: ...CH1 C15 GND Figure W 1 Cold Start 7 ...
Страница 11: ...Figure S 2 Charger circuit 9 ...
Страница 13: ...Figure S 3 Line and Zero Crossing Detecting circuit 11 ...
Страница 14: ...CH1 Line I P CH2 Q14 collector Figure W 2 Zero Crossing 12 ...
Страница 16: ...Figure S 4 Inverter circuit 14 ...
Страница 17: ...CH1 DS1 CH2 Output Voltage 1 200V Figure W 3 Inverter Circuit 1 15 ...
Страница 18: ...CH1 DS2 CH2 Output Voltage 1 200 Figure W 4 Inverter Circuit 2 16 ...
Страница 20: ...CH1 CLAMP OFF signal CH2 output voltage 1 200V Figure W 5 Clamp circuit 18 ...
Страница 23: ...Figure S 5 CPU circuit 21 ...
Страница 24: ...Figure S 6 Relay Circuit 22 ...
Страница 25: ...CH1 C10 GND CH2 Output Voltage 1 200V Figure W 6 Relay speed up capacitor 23 ...
Страница 27: ...Figure S 7 Panel circuit 25 ...
Страница 33: ...Figure W 7 Battery mode examination flowchart Figure W 8 Line mode examination flowchart 30 ...