MERLIN NX ROOM CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS 

 

29 

EN1Z-1035GE51 R0319 

NI1000TK5000 

 

Temp. 

[°C] 

Resistance 

[Ω] 

Terminal 

voltage [V] 

-30 

871.7 

0.338 

-29 

875.8 

0.340 

-28 

880 

0.341 

-27 

884.1 

0.343 

-26 

888.3 

0.344 

-25 

892.5 

0.346 

-24 

896.7 

0.348 

-23 

900.8 

0.349 

-22 

905.1 

0.351 

-21 

909.3 

0.352 

-20 

913.5 

0.354 

-19 

917.7 

0.355 

-18 

922 

0.357 

-17 

926.2 

0.359 

-16 

930.5 

0.360 

-15 

934.7 

0.362 

-14 

939 

0.363 

-13 

943.3 

0.365 

-12 

947.6 

0.367 

-11 

951.9 

0.368 

-10 

956.2 

0.370 

-9 

960.6 

0.371 

-8 

964.9 

0.373 

-7 

969.3 

0.375 

-6 

973.6 

0.376 

-5 

978 

0.378 

-4 

982.4 

0.380 

-3 

986.7 

0.381 

-2 

991.2 

0.383 

-1 

995.6 

0.384 

1000 

0.386 

1004.4 

0.388 

1008.9 

0.389 

1013.3 

0.391 

1017.8 

0.393 

1022.3 

0.394 

1026.7 

0.396 

1031.2 

0.398 

1035.8 

0.399 

1040.3 

0.401 

10 

1044.8 

0.403 

11 

1049.3 

0.404 

12 

1053.9 

0.406 

13 

1058.4 

0.408 

14 

1063 

0.409 

15 

1067.6 

0.411 

16 

1072.2 

0.413 

17 

1076.8 

0.415 

Temp. 

[°C] 

Resistance

[Ω] 

Terminal 

voltage [V] 

18 

1081.4 

0.416 

19 

1086 

0.418 

20 

1090.7 

0.420 

21 

1095.3 

0.421 

22 

1100 

0.423 

23 

1104.6 

0.425 

24 

1109.3 

0.427 

25 

1114 

0.428 

26 

1118.7 

0.430 

27 

1123.4 

0.432 

28 

1128.1 

0.433 

29 

1132.9 

0.435 

30 

1137.6 

0.437 

31 

1142.4 

0.439 

32 

1147.1 

0.440 

33 

1151.9 

0.442 

34 

1156.7 

0.444 

35 

1161.5 

0.446 

36 

1166.3 

0.447 

37 

1171.2 

0.449 

38 

1176 

0.451 

39 

1180.9 

0.453 

40 

1185.7 

0.455 

41 

1190.6 

0.456 

42 

1195.5 

0.458 

43 

1200.4 

0.460 

44 

1205.3 

0.462 

45 

1210.2 

0.463 

46 

1215.1 

0.465 

47 

1220.1 

0.467 

48 

1225 

0.469 

49 

1230 

0.471 

50 

1235 

0.473 

51 

1240 

0.474 

52 

1245 

0.476 

53 

1250 

0.478 

54 

1255 

0.480 

55 

1260.1 

0.482 

56 

1265.1 

0.484 

57 

1270.2 

0.485 

58 

1275.3 

0.487 

59 

1280.3 

0.489 

60 

1285.4 

0.491 

61 

1290.6 

0.493 

62 

1295.7 

0.495 

63 

1300.8 

0.496 

64 

1306 

0.498 

65 

1311.1 

0.500 

Temp. 

[°C] 

Resistance

[Ω] 

Terminal 

voltage [V] 

66 

1316.3 

0.502 

67 

1321.5 

0.504 

68 

1326.7 

0.506 

69 

1331.9 

0.508 

70 

1337.1 

0.510 

71 

1342.4 

0.512 

72 

1347.6 

0.513 

73 

1352.9 

0.515 

74 

1358.2 

0.517 

75 

1363.5 

0.519 

76 

1368.8 

0.521 

77 

1374.1 

0.523 

78 

1379.4 

0.525 

79 

1384.8 

0.527 

80 

1390.1 

0.529 

81 

1395.5 

0.531 

82 

1400.9 

0.533 

83 

1406.3 

0.535 

84 

1411.7 

0.537 

85 

1417.1 

0.538 

86 

1422.5 

0.540 

87 

1428 

0.542 

88 

1433.4 

0.544 

89 

1438.9 

0.546 

90 

1444.4 

0.548 

91 

1449.9 

0.550 

92 

1455.4 

0.552 

93 

1460.9 

0.554 

94 

1466.5 

0.556 

95 

1472 

0.558 

96 

1477.6 

0.560 

97 

1483.2 

0.562 

98 

1488.8 

0.564 

99 

1494.4 

0.566 

100 

1500 

0.568 

101 

1505.6 

0.570 

102 

1511.3 

0.572 

103 

1517 

0.574 

104 

1522.6 

0.576 

105 

1528.3 

0.578 

106 

1534 

0.580 

107 

1539.7 

0.582 

108 

1545.5 

0.584 

109 

1551.2 

0.586 

110 

1557 

0.589 

111 

1562.8 

0.591 

112 

1568.5 

0.593 

113 

1574.4 

0.595 

Temp. 

[°C] 

Resistance

[Ω] 

Terminal 

voltage [V] 

114 

1580.2 

0.597 

115 

1586 

0.599 

116 

1591.8 

0.601 

117 

1597.7 

0.603 

118 

1603.6 

0.605 

119 

1609.5 

0.607 

120 

1615.4 

0.609 

121 

1621.3 

0.611 

122 

1627.2 

0.613 

123 

1633.2 

0.616 

124 

1639.1 

0.618 

125 

1645.1 

0.620 

126 

1651.1 

0.622 

127 

1657.1 

0.624 

128 

1663.1 

0.626 

129 

1669.1 

0.628 

130 

1675.2 

0.630 

 

Содержание MERLIN NX Series

Страница 1: ...ving connections to from any terminals Table 1 Overview of models OS no CLCM power supply AOs UIs BIs relays A triacs B total no of I Os remarks large housing 198 x 110 x 57 5 mm RL4N 230 VAC 6 10 0 4 4 24 24 hr data retention RL6N 24 VAC 6 10 0 4 4 24 24 hr data retention RL8N 230 VAC 6 6 C 4 D 4 4 24 24 hr data retention supports switch inputs with 24 V pull up for connection of standard light s...

Страница 2: ...O3 WM1 20 C2 23 C2 24 WM2 21 34 UI1 36 UI2 37 UI3 39 UI4 35 GND 38 GND 26 AO1 27 24V 28 GND 29 AO2 30 AO3 31 24V 32 GND 33 AO4 41 C1 40 C1 GND 42 BACnet MS TP SERVICE 22 24V 25 GND 53 5 59 52 24 V MODELS 230 V MODELS Fig 3 RSxN dimensions in mm The unit is suitable for mounting on a standard rail on walls as well as in wiring cabinets or fuse boxes Terminal Protection Covers for IP30 In the case o...

Страница 3: ...nal blocks capable of carrying either low voltage or line voltage are orange colored The delivery includes a plastic bag containing additional removable terminal blocks for BACnet MS TP and Sylk interfaces The controller is powered by 230 VAC and is equipped with differing numbers of triac outputs relay outputs etc capable of being configured in a variety of ways See Table 1 on page 1 Every contro...

Страница 4: ...24V0 Aux power 24 VAC 20 50 60 Hz RS485 Modbus interface corresp GND 26 AO1 Analog Output 1 type 2 type 2 27 24V 24 VAC power for field devices X X 28 GND Ground for AOs X X 29 AO2 Analog Output 2 type 1 type 1 30 AO3 Analog Output 3 type 1 type 1 31 24V 24 VAC power for field devices X X 32 GND Ground for AOs X X 33 AO4 Analog Output 4 type 1 type 1 34 UI1 Universal Input 1 type 1 type 1 35 GND G...

Страница 5: ...counter input max 30 Hz pulse ON min 16 ms pulse OFF min 16 ms closed voltage 1 V open voltage 5 V pull up voltage 10 V X X fast binary counter input max 30 Hz pulse ON min 16 ms pulse OFF min 16 ms closed voltage 1 V open voltage 5 V pull up voltage 24 V X 0 2 10 V X X NTC20kΩ X SetPoint and FanSpdSW from CLCM1T 2T 4T 5T 6T111 X NTC10kΩ X PT1000 Ni1000TK5000 X Table 5 Analog output types and char...

Страница 6: ...Output of Relay 3 type 1 type 1 type 1 26 27 28 29 C2 C2 24V0 24V Not used 30 31 WM1 WM2 Removable interface for Sylk Bus X X X 32 AO1 Analog Output 1 type 3 type 3 type 4 33 GND Ground for AOs X X X 34 AO2 Analog Output 2 type 3 type 3 type 3 35 24V 24 VAC power for field devices X X X 36 AO3 Analog Output 3 type 1 type 5 37 GND Ground for AOs X X 38 AO4 Analog Output 4 type 1 type 5 39 24V 24 VA...

Страница 7: ... A NON RESETTABLE FUSE LINE VOLTAGE N N L L Niagara workbench Fig 8 RS4N example wiring 230 V model 8 7 6 5 4 3 2 1 RJ45 INTERFACE 32 GND 34 UI1 36 UI2 37 UI3 1 TEMP 2 SETP 30 AO3 33 AO4 THERM COOL THERM HEAT CLCM2T WALL MODULE CLCMTR40x TR42x WALL MODULE 5 TN OCCUPANCY CONTACT 31 24V 39 UI4 35 GND 38 GND 40 C1 41 C1 42 GND 7 8 2 3 5 6 4 24V GND 0 10V 24V 24V0 N L ELECTR REHEATER 3 SPEED FAN 10 RO...

Страница 8: ...GND2 485 2 485 2 n a 2 J1 J8 RS232 RS485 1 END BIAS MID EAGLEHAWK NX BACnet MS TP Fig 10 RS5N example wiring 24 V model 8 7 6 5 4 3 2 1 RJ45 INTERFACE 20 WM1 21 WM2 26 AO1 32 GND 34 UI1 36 UI2 37 UI3 1 TEMP 2 SETP 29 AO2 30 AO3 33 AO4 THERM COOL THERM HEAT 5 TN OCCUPANCY CONTACT 28 GND 27 24V 31 24V 39 UI4 35 GND 38 GND 40 C1 41 C1 42 GND 7 8 2 3 5 6 4 24V 0 10V ELECTR REHEATER 3 SPEED FAN 10 RO4 ...

Страница 9: ... OPTIONAL FUSE TO PROTECT CONTROLLER S INTERNAL TRANSFORMER WHICH HAS ONLY A NON RESETTABLE FUSE LINE VOLTAGE N N L L Niagara workbench Fig 12 RL4N 230 V model example wiring 2 TEMP 3 SETP 4 BYP 6 NC 7 NC 5 LED 8 7 6 5 4 3 2 1 RJ45 INTERFACE 30 WM1 31 WM2 32 AO1 33 GND 35 24V 39 24V 43 24V 44 24V 37 GND 41 GND 46 GND 48 UI2 50 UI3 52 GND 54 UI6 56 UI7 58 GND 60 UI10 47 UI1 49 GND 51 UI4 53 UI5 55 ...

Страница 10: ...x TR42x WALL MODULE 22 C F1 230 V LINE VOLTAGE N N L L Niagara workbench CLCM4T 5T 6T111 WALL MODULE Fig 14 RL4N 230 V model example wiring 2 TEMP 3 SETP 4 BYP 6 NC 7 NC 5 LED 87 6 5 43 2 1 RJ45 INTERFACE 30 WM1 31 WM2 32 AO1 33 GND 35 24V 39 24V 43 24V 37 GND 41 GND 46 GND 48 UI2 50 UI3 52 GND 54 UI6 56 UI7 58 GND 60 UI10 47 UI1 49 GND 51 UI4 53 UI5 55 GND 57 UI8 59 UI9 61 GND 34 AO2 36 AO3 38 AO...

Страница 11: ...0 VAC 15 10 50 60 Hz 24 VAC 20 3 24V 3 24V N L 4 24V0 4 24V0 24 VAC MODEL 1 24 VAC MODEL 2 CAUTION ALWAYS CONNECT TERM 4 24VAC0 OF EVERY 24 VAC MODEL TO TERM FAILURE TO COMPLY WILL RESULT IN SHORT CIRCUITING 4 24VAC0 OF EVERY OTHER 24 VAC MODEL Fig 17 Multiple 24 VAC models connected to single power supply Communication Signal Terminals All other i e communication signal terminals except for the S...

Страница 12: ...on Short press UP Opens the slat angle by a configurable slat angle segment Long press UP Drives the blinds to the UP position Movement may be stopped by briefly pressing any blinds pushbutton Short press DOWN Closes the slat angle by a con figurable slat angle segment Long press DOWN Drives the blinds to the DOWN posi tion Movement may be stopped by briefly pressing any blinds pushbutton Example ...

Страница 13: ...s switched OFF once the configurable time is over Staircase lighting with dimming function Light OutManualAddressedCmdBits OutFeedback OutCause EmergencyCmd highest prio MotionBrightnessSensor EmergencyCause Other useful inputs for special cases Parameters LightControlType Hw Terminals Min MaxOutputs DimmingSpeed LockTime Light ON if Occ and Dark Light ON and restart AutoOffTimer if Occ and Dark L...

Страница 14: ...hts Commissioning Parameters Light type e g ON OFF dimming staircase etc Assignment of switching outputs relay or triac It is recommended to use coupling relays if triac outputs are used for lighting Please observe the relays constant current and inrush current limitations Coupling relays may be used if the internal relays cannot support the required current Assignment of analog outputs for light ...

Страница 15: ... non RxxN con troller with a conflicting address is then added D Time to recognize con flicting MAC address of added non RxxN controller while auto MAC still in progress 50 sec Like C but with the addi tional non RxxN controller having a conflicting MAC address added while auto MAC still in progress E Time for auto MAC when additional RxxN controllers are added in stages while auto MAC still in pr...

Страница 16: ...OTE 1 If any of the devices are electrically isolated it is recommended that those devices be connected to signal ground NOTE 2 The 120 Ohm termination resistor must be inserted directly into the terminals of the final BACnet MS TP device NOTE 3 If shielding is used the shielding of each individual bus segment should be separately connected at one end to earth RJ45 Connector for BACnet WiFi Adapte...

Страница 17: ...n 4 of the controller s RJ45 interface The max permissible combined current output of these 24 VAC power output terminals is 300 mA Relay Outputs CAUTION Mixing of different voltages e g 24 V and 230 V within the relay block is not allowed The terminal blocks containing the controller s relay outputs are orange Relay output types See Table 3 NOTE If inductive components are to be connected to the ...

Страница 18: ...ting 24 VAC to any analog output of the RSxN controller small housing will damage the hardware Free I O Option The limitations including model dependent limitations set forth in Table 2 Table 3 Table 4 Table 5 apply Further limitations are explained below Free Universal Inputs Max 5 BACnet Analog Input Objects Under the free I O option a maximum of five of the MERLIN NX controller s unused UIs are...

Страница 19: ... Input output Use as UI1 2 0 10V inputs UI3 NTC20k temperature input UI4 5 binary inputs UI6 counter AO1 0 10V output AO2 0 10V output Triac 1 2 floating actuator outputs Triac 3 4 floating actuator outputs Relay 1 2 3 4 binary outputs In the above example the customer has used the maximum of four analog characteristics No further analog characteristic can be assigned e g relays 1 2 could not be u...

Страница 20: ...n no override is currently in effect OVERRIDE OCCUPANCY If the wall module s LED is ON continuously then the wall module s override button or a BACnet MS TP network command has placed the controller into the occupied or override mode but if the override button is again pushed or if a cancellation net work command is received or if the override time expires the controller will return to its schedul...

Страница 21: ...oller will revert to the unoccupied mode Standby Mode CLCMTR42xx CONFIGURED TO DISPLAY SYMBOLS CLCMTR42xx CONFIGURED TO DISPLAY ENGLISH FAN FAN CANCEL CANCEL OVERRIDE OVERRIDE OVERRIDE CANCEL OVERRIDE OVERRIDE CANCEL OVR DONE DONE OFF AUTO OFF AUTO H C AUTO H C AUTO H C AUTO H C AUTO 2 0 2 0 2 0 2 0 C C C C OVERRIDE Fig 27 Example standby screens If is displayed the controller is in the standby mo...

Страница 22: ...ars first The user can scroll to further screens heating cooling relative humidity and CO2 concentration using the left or right arrow softkey NOTE The user can at any time exit the expanded menu using the upper left softkey below the symbol or the word HOME or by simply waiting approx 60 seconds In the expanded menu the current temperature relative humidity and CO2 concentration can be displayed ...

Страница 23: ...tee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and...

Страница 24: ...r Failure of Sensor Inputs The thresholds at which sensor failures i e sensor breaks SB and short circuits SC are recognized depends upon the given sensor type In the event of a recognized sensor failure the sensor inputs assume the safety values configured in CARE Table 17 lists the measurement ranges and the corresponding thresholds for the recognition of sensor failure for the various different...

Страница 25: ...0 449 2 850 25 10 2 767 26 9 572 2 684 27 9 165 2 603 28 8 777 2 524 29 8 408 2 447 30 8 057 2 372 31 7 722 2 299 32 7 402 2 228 33 7 098 2 159 34 6 808 2 091 35 6 531 2 025 36 6 267 1 962 37 6 015 1 900 38 5 775 1 840 39 5 546 1 781 40 5 327 1 724 41 5 117 1 669 42 4 917 1 616 43 4 726 1 564 44 4 543 1 514 45 4 369 1 465 46 4 202 1 418 47 4 042 1 373 48 3 889 1 329 49 3 743 1 286 50 3 603 1 244 5...

Страница 26: ... 2 34 47 0 7 60 2 27 48 0 7 29 2 20 49 0 7 00 2 14 Temp C Resistance k Terminal voltage V 50 0 6 72 2 07 51 0 6 45 2 01 52 0 6 19 1 94 53 0 5 95 1 88 54 0 5 72 1 82 55 0 5 49 1 77 56 0 5 28 1 71 57 0 5 08 1 66 58 0 4 88 1 61 59 0 4 69 1 56 60 0 4 52 1 51 61 0 4 35 1 46 62 0 4 18 1 41 63 0 4 03 1 37 64 0 3 88 1 32 65 0 3 73 1 28 66 0 3 59 1 24 67 0 3 46 1 20 68 0 3 34 1 16 69 0 3 21 1 13 70 0 3 10 ...

Страница 27: ...0 479 66 0 1255 0 480 67 0 1259 0 481 68 0 1263 0 483 69 0 1267 0 484 Temp C Resistance Terminal voltage V 70 0 1271 0 486 71 0 1275 0 487 72 0 1278 0 488 73 0 1282 0 490 74 0 1286 0 491 75 0 1290 0 493 76 0 1294 0 494 77 0 1297 0 495 78 0 1301 0 497 79 0 1305 0 498 80 0 1309 0 499 81 0 1313 0 501 82 0 1317 0 502 83 0 1320 0 503 84 0 1324 0 505 85 0 1328 0 506 86 0 1332 0 508 87 0 1336 0 509 88 0 ...

Страница 28: ... 287 0 2074 0 769 288 0 2077 0 770 289 0 2081 0 771 290 0 2085 0 773 291 0 2088 0 774 292 0 2092 0 775 293 0 2095 0 776 294 0 2099 0 777 295 0 2102 0 778 296 0 2106 0 780 297 0 2110 0 781 298 0 2113 0 782 299 0 2117 0 784 300 0 2120 0 785 301 0 2124 0 786 302 0 2127 0 787 303 0 2131 0 788 304 0 2134 0 789 305 0 2138 0 791 306 0 2142 0 792 307 0 2145 0 793 308 0 2149 0 794 309 0 2152 0 796 Temp C R...

Страница 29: ...1200 4 0 460 44 1205 3 0 462 45 1210 2 0 463 46 1215 1 0 465 47 1220 1 0 467 48 1225 0 469 49 1230 0 471 50 1235 0 473 51 1240 0 474 52 1245 0 476 53 1250 0 478 54 1255 0 480 55 1260 1 0 482 56 1265 1 0 484 57 1270 2 0 485 58 1275 3 0 487 59 1280 3 0 489 60 1285 4 0 491 61 1290 6 0 493 62 1295 7 0 495 63 1300 8 0 496 64 1306 0 498 65 1311 1 0 500 Temp C Resistance Ω Terminal voltage V 66 1316 3 0 ...

Страница 30: ...y its Authorized Representative CentraLine Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 845 Fax 49 0 7031 637 740 info centraline com www centraline com Subject to change without notice EN1Z 1035GE51 R0319 Trademark Information BACnetTM is a trademark of ASHRAE Inc LON LONWORKS and Neuron are trademarks of Echelon Corporation registered in the United States and o...

Отзывы: