CEM DT-3369T-BT Скачать руководство пользователя страница 4

 

Description 

Meter Description   

1.  NCV Test 

2.  Current clamp 

3.  Non-contact AC voltage indicator light 

4.  Clamp trigger 

5.  Rotary Function switch 

6.  Data Hold and Backlight button 

7.  PEAK and INRUSH button 

8.  REL and HZ% button 

9.  MODE select and Bluetooth    button 

10. Max/Min button 

11. LCD display 

12. V 

 Diode Continuity CAP TEMP Hz% jack 

13. COM input jack 

14. Battery Cover 

 

 

Display icons Description 

HOLD 

          Data Hold 

Minus sign 

  Negative reading display 

0 to 5999   

  Measurement display digits

 

 

REL                  REL/DCA Zero   

MAX/MIN 

  Maximum/Minimum 

                          Auto Power Off 

AUTO 

          Auto Range mode 

DC/AC            Direct Current / Alternating Current 

 

                  Low battery 

mV or V            Milli-volts or Volts (Voltage) 

Ohms                (Resistance) 

                  Amperes (Current) 

                  Farad (Capacitance) 

Hz/% 

          Hertz (Frequency)/Percent(duty ratio) 

o

F and 

o

  Fahrenheit and Celsius units (Temperature) 

n, m, 

μ

, M, k    Unit of measure prefixes: nano, milli, micro, mega, and kilo     

)))                    Continuity test 

Diode test 

              Bluetooth4.0

 

 

 

Содержание DT-3369T-BT

Страница 1: ...DT 3369T BT AC DC TRMS CLAMP METER With Mobile APP ...

Страница 2: ...e the equipment Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instru...

Страница 3: ...ltages are considered a shock hazard Always discharge capacitors and remove power from the device under test before performing Diode Resistance or Continuity tests Voltage checks on electrical outlets can be difficult and misleading because of the uncertainty of connection to the recessed electrical contacts Other means should be used to ensure that the terminals are not live If the equipment is u...

Страница 4: ...4 Battery Cover Display icons Description HOLD Data Hold Minus sign Negative reading display 0 to 5999 Measurement display digits REL REL DCA Zero MAX MIN Maximum Minimum Auto Power Off AUTO Auto Range mode DC AC Direct Current Alternating Current Low battery mV or V Milli volts or Volts Voltage Ohms Resistance A Amperes Current F Farad Capacitance Hz Hertz Frequency Percent duty ratio o F and o C...

Страница 5: ...ts DC Voltage Auto ranging 600 0mV 0 1mV 0 9 of rdg 5digits 6 000V 1mV 1 0 of rdg 3digits 60 00V 10mV 1 0 of rdg 3digits 600 0V 100mV 1 0 of rdg 3digits Maximum Input 750V dc Function Range Resolution Accuracy of reading digits AC True RMS Voltage Auto ranging 6 000V 1mV 1 2 of rdg 5digits 60 00V 10mV 1 2 of rdg 5digits 600 0V 100mV 1 5 of rdg 5digits AC Response 50 Hz to 1kHz Accuracy specified f...

Страница 6: ...on Range Accuracy of reading digits Frequency Auto ranging 10Hz to 20kHz 1 0 5 digits Input Protection 750V AC rms Sensitivity 15V AC rms Function Range Accuracy of reading digits Frequency 40Hz to 1kHz 1 0 5 digits Maximum Input 1000A AC Sensitivity 50A 600A range 500A 1000A range Function Range Resolution Accuracy of reading digits Duty Cycle 20 0 80 0 0 1 1 2 of rdg 10digits Function Range Reso...

Страница 7: ...perature 41o F to 104o F 5o C to 40o C Storage Temperature 4o F to 140o F 20o C to 60o C Operating Humidity Max 80 up to 87o F 31o C decreasing linearly to 50 at 104o F 40o C Storage Humidity 80 Operating Altitude 7000ft 2000meters maximum Battery One 1 9V Battery Auto power OFF After approx 15 minutes Dimensions Weight 239 x 80 x 49mm 305g Safety For indoor use and in accordance with the requirem...

Страница 8: ...sert the black test lead into the negative COM terminal and the red test lead into the positive V CAP TEMP Hz Ω Ω Ω Ω terminal 2 Set the function switch to the V position 3 Connect the test leads in parallel to the circuit under test 4 Read the voltage measurement on the LCD display DC Voltage Measurement 1 Insert the black test lead into the negative COM terminal and the red test lead into the po...

Страница 9: ...r Duty cycle 4 Touch the test probe tips across the part under test 5 Read the value on the display 6 The display will indicate the proper decimal point and value 7 In Voltage and Current mode Press HZ button to select he Frequency Hz or Duty cycle Temperature Measurements 1 Set the function switch to the TEMP position 2 Insert the Temperature Probe into the negative COM and the V CAP TEMP Hz Ω Ω ...

Страница 10: ...V and the other reading displays OL the diode is good If both readings display OL the device is open If both readings are very small or 0 the device is shorted Non Contact AC Voltage Measurements 1 Touch the probe tip to the hot conductor or insert into the hot side of the electrical outlet 2 If AC voltage is present the detector light will illuminate 1 NOTE The conductors in electrical cord sets ...

Страница 11: ... is equipped with backlighting for easier viewing especially in dimly lit areas Press the backlight button to turn the backlight on Press again to turn the backlight off Note that the meter does have an auto power off feature as described below Relative 1 Press the REL button to zero the display REL will appear in the displ ay The displayed reading is now the actual value less the stored zero valu...

Страница 12: ...t leads from the input terminals and turn OFF the meter before opening the case Do not operate the meter with an open case Cleaning and Storage Periodically wipe the case with a damp cloth and mild detergent do not use abrasiv es or solvents If the meter is not to be used for 60 days or more remove the battery and store it separately Battery Replacement 1 Remove the Phillips head screw that secure...