Energy Saver Button  To activate and deactivate the “Energy Saver” mode, press 

the “Energy Saver” button 
The “Energy Saver” indicator light (Row 3) will turn on when 
the cooling unit is in “Energy Saver” mode 
In the “Energy Saver” mode, the Minimum Set Point will 
increase 4°F 
 

Quick Chill Button 

To activate the “Quick Chill” mode, press the “Up” / “Quick 

Chill” button for three seconds 
To deactivate “Quick Chill”, press “Quick Chill” button for 
three seconds again 
The “Quick Chill” indicator (Row 3) light will turn on when the 

cooling unit is in “Quick Chill” mode,  
In the “Quick Chill” mode, the cooling unit will run 
continuously for 6 hours (or until the intake temperature 
registers 50°F).  This mode is useful after loading “warm” 

bottles in a cellar 
 

Up and Down 
Buttons 

To view the “High Temp” recorded by the cooling unit, press 
the “Up” button once.    
To view the “Low Temp” recorded by the cooling unit, press 
the “Down” button once  
To reset the “High Temp” or “Low Temp”, press the “Set” 
button for three seconds while “Hi” or “Lo” is displayed.  

“RST” will blink three times to indicate confirmation. 
 

Auto Defrost Mode 

The cooling unit periodically checks the temperature of the 
evaporator coils as measured by Probe 2 (P2) and initiates an 
auto-defrost cycle if the coils drop below 38

°

F.  When the 

cooling unit is in auto-defrost mode, the “Auto-Defrost” 

Indicator light (Row 2) will turn on 
 

Содержание 1800QT

Страница 1: ......

Страница 2: ...com customer service If you still have questions please don t hesitate to contact your dealer or CellarPro directly We can be reached during normal business hours at 1 877 726 8496 You also may contac...

Страница 3: ...o f C o n t e n t s I Important Notes 3 II Overview 4 III Replacement Instructions 8 IV Operating Instructions 14 V Normal Operation 20 VI Troubleshooting 22 VII Limited Warranty 23 VIII Contact Info...

Страница 4: ...mp circuit Before installing the cooling unit make sure that the exhaust panel is installed in the correct position it MUST cover either the TOP or the REAR exhaust vent o TOP VENT CONFIGURATION If th...

Страница 5: ...the temperatures of the ambient environment the insulation of the cellar and the thermal mass inside the cellar will affect the speed with which the temperature inside the cellar rises during the coo...

Страница 6: ...should be plugged into an outlet connected to a 15 amp circuit The cooling unit uses approximately 3 amps during its on cycle The cooling unit also offers a grounded 115V AC outlet which is rated for...

Страница 7: ...llow guidelines for recommended clearance so that the hot air exhaust is properly dissipated otherwise the hot air will become trapped and the cooling unit will circulate its hot air exhaust thereby c...

Страница 8: ...ate clearance and airflow and proper ambient temperatures in and around the cellar Model Dimensions inches W x D x H Operating Amps Cellar Capacity cubic feet 1800QT 18 x 16 5 x 10 5 3 200 1800XT 18 x...

Страница 9: ...WINE CABINET 4 Open cabinet door and remove all bottles from the top of the rack 5 Place a heavy towel or blanket on top of the wine rack for protection 6 IF YOU HAVE A LE CACHE MODEL 2400 WITH A CENT...

Страница 10: ...tle racks TO INSTALL NEW COOLING UNIT 1 Wait 24 hours before plugging in and operating your CellarPro cooling unit 2 Carefully remove the new cooling unit from the packaging You may reuse this packagi...

Страница 11: ...val instructions described above in reverse 11 After installing the cooling unit It is not necessary to replace the grill 12 A complete and proper seal must be made between the cellar and the cooling...

Страница 12: ...H A CENTER POST Remove the center post by unscrewing the screws two at the top and two at the bottom that attach the post to the wine cabinet 7 Unplug the light from the cooling unit inside the cellar...

Страница 13: ...t make sure it works by plugging it in and letting it run on a hard flat surface Check that cold air is being produced by the unit 5 NEVER turn the cooling unit on its side or upside down 6 The coolin...

Страница 14: ...ir does not enter the cellar Use the butyl tape to seal the perimeter where the cooling unit touches the wine cabinet at the rear of the cellar by rolling the tape with your fingers into a thin pencil...

Страница 15: ...ing unit have been preset and optimized by the factory and it is not necessary to change these settings initially If you find that you want to change one or more of the settings we strongly recommend...

Страница 16: ...ial of 4 F This means that the cooling unit will turn on when the air temperature as measured by Probe 1 P1 rises above 59 F 55 F 4 F and turn off when the air temperature measured by P1 falls below 5...

Страница 17: ...cooling unit will run continuously for 6 hours or until the intake temperature registers 50 F This mode is useful after loading warm bottles in a cellar Up and Down Buttons To view the High Temp reco...

Страница 18: ...F for more than 1 hour Check seals Check if door was left open Lower the ambient temperatures HA2 The condenser temperature is too high above 125 F for 2 hours Clean the condenser coils see Maintenan...

Страница 19: ...ces as follows Scenario What it means What happens P2 70 F for more than 1 hour The evaporator probe is measuring temperatures that are too warm The evaporator fan will turn off until the evaporator t...

Страница 20: ...0 5 F This setting increases or decreases the humidity inside the cellar The factory preset for this setting is 0 The recommended range for this setting is 0 6 If the humidity inside the cellar is to...

Страница 21: ...the time Temperature Control Temperature inside the cellar can be increased or decreased by changing the Minimum Set Point as described in the Basic Operation section above If the cooling unit runs t...

Страница 22: ...denser coils become clogged the cooling unit will not have proper airflow and its performance and longevity will be compromised To clean the coils simply vacuum or brush the coils until all dust and l...

Страница 23: ...coils can all cause the cooling unit to run continuously To reduce cycle times 1 Clean the condenser coils 2 Check the ambient temperature in the space outside the condenser coils while the cooling un...

Страница 24: ...ects in material or workmanship and are not covered by the warranty The limited warranty does not cover any parts or labor to correct any defect caused by negligence commercial use accident or imprope...

Страница 25: ...24 C o n t a c t I n f o r m a t i o n CellarPro Cooling Systems 531 Mercantile Drive Cotati CA 94931 877 726 8496 Email us info cellarpro com Website www cellarpro com...

Отзывы: