background image

______________________________________________________________________________________  

-1- 

 

ES-09 

Field Installation Manual 

 

INDEX 

Important Instructions…………………………………………………………………………….  2 

Product Specifications……………………………………………………………..................  3 

Unpacking & Mounting ………………………………………………………….……………. 

Connection Type 1 ………………………………………………………………….............. 

5  

Connection Diagram ………………………………………………..………………………… 

6                                

Connection Type 2 ……………………………... ……………………………………………. 

Connection Type 3 ……………………………………………………………………………… 

Electrical Data Sheet ………………………………………..…………………………………. 

Recommended Part List…………………………………………………..…………………….  10 

 

 

 
 
 

Содержание ES-09

Страница 1: ..._______________________ 1 ES 09 Field Installation Manual INDEX Important Instructions 2 Product Specifications 3 Unpacking Mounting 4 Connection Type 1 5 Connection Diagram 6 Connection Type 2 7 Connection Type 3 8 Electrical Data Sheet 9 Recommended Part List 10 ...

Страница 2: ...cal Installation and all components of the installation must be CE Certified and as per NEC code WARNING Celec manufacture components parts that can be used in a wide variety of industrial commercial applications The selection and application of Celec products remains the responsibility of the equipment designer or end user Celec accepts no responsibility for how its products may be incorporated i...

Страница 3: ...Single Phase 240V AC Rated Frequency 50Hz Maximum Current 39 Amp Rated kVar 9 27 kVAr Maximum Ambient Temperature Rating 400 C Enclosure Type 1 Connection Terminal Connection Type Size Wire Type Temperature Torque N m Lb in T1 Terminal Block 10mm CU 60 75 C 4 5 T2 Terminal Block Current Sensor 1mm CU 60 75 C 0 5 Bonding Wire Earthing 10mm CU 60 75 C 8 5 ...

Страница 4: ... given for support during transportation 4 Do not use ES 09 in case of any Breakage or loose connections or Oil Spill inside MOUNTING CAUTION Indoor Use Only Type 1 Enclosure 1 Choose the dry and Clean Wall to Install the ES 09 taking care conduit connections from Bottom side Enclosure Size is 400 x 500 x 120 mm and weight 13kg 29 Pounds 2 Premark the Mounting holes on wall or structure 3 Make a D...

Страница 5: ... wire to main breaker panel ground rod Ensure all mechanical connections are secure and making full contact 1 13 Locate existing 2 Pole 63 Amp Circuit Breaker in the Main Breaker Panel a Connect the wire L1 to Phase 1 of 63 Amp circuit breaker b Connect the wire N to Neutral of 63 Amp circuit breaker 1 14 Qualified Representative must inspect size of cable 10mm 1 15 Connect power cables to T1 Term...

Страница 6: ...______________________________________________________________________________________ 6 ...

Страница 7: ...ailable ES 09 unit is designed for use with Customer Main Breaker Panel Single Phase 240V AC up to 400 Amp ES 09 units should be mounted with four appropriate sized fasteners before connect to Main Breaker Panel 1 Remove Main Panel covers exposing internal wiring and breakers 2 Remove existing 2 Pole breaker blanks and install new 2 Pole 63 Amp circuit Breakers 3 For rest of connection follow the ...

Страница 8: ...ircuit Breaker for connection of ES 09 to Customer Main Breaker Panel 1 Install new 63 Amp Blade Fused disconnect or External Circuit Breaker switch to wall or existing backboard Qualified Representative should note if codes allow for direct connection to bus bars in main breaker panel or requires installation of an additional sub panel 2 Wire in rigid conduit between customer main breaker panel e...

Страница 9: ...Protection Capacitor Inbuilt Protection P2 Equipment Protection Internal design has adequate clearance and creepage distance against line transients MOVs not required Circuit breaker Required 63 Amp 2 pole Low Losses 0 5 Watt each step Human Protection All High voltage shielded from contact Operating temperature range 40o C Ambient Dimensions L X H X D 16 X 20 X 5 400 x 500 x 120 mm Metal Enclosur...

Страница 10: ...s required CT Current Sensor Megnelab SCT 0750 050 1 Dowel Plug Size M8 Any 4 Screw 50 mm Size M8 Any 4 1 2 Conduit Connector Any 8 1 2 Tube Conduit Any As required All the Parts used in installation must be CE recognized NOTE Installation of material and workmanship at the customer s Main Breaker Panel shall be the responsibility of the qualified Electrician in accordance with NEC Any and all con...

Отзывы: