Fig. 8. View of ADAConfig software interface
5.3. FACTORY DEFAULT
In case of faulty functioning ADA-4040PC3, can be restored the factory default setting of the converter internal registers.
Set SW1 microswitch mode as in the table below.
SW1-1
SW1-2
OFF
ON
Disconnect
the power and after while
connect
again the power. After that, will be loaded the factory default setting to the converter
internal registers.
After this operation, the converter parameters should be set again for operating in the application.
Set micro switch SW1 to run mode as shown in the table below.
SW1-1
SW1-2
OFF
OFF
In the RUN mode the yellow LED (located near the SW1), will turn off.
5.4. FIRMWARE UPDATE
Set SW1 micro switch to configuration mode as in table below.
SW1-1
SW1-2
ON
OFF
In the configuration mode the yellow LED will blink with frequency 1Hz. Press a button
[Load New Firmware]
to change the software
delivered by manufacturer. The Select File window will open (fig. below) and select the *.bin file then click
[Open]
- software will be
load to
ADAConfig
buffer storage and will be checked. If the
ADAConfig
not detect errors in loaded file, change converter software.
Process of updating is visualized by
ADAConfig
in use Progress Window and after proper changing confirmed by correct message.
9
ADA-4040PC3