Installation Instructions
ODH-3000 Over Door Heater
Reference
J008g
SAFETY
The correct procedures for working at height must be adopted when installing this heater.
The heater must be installed by a suitably qualified person in accordance with current regulations.
CONTENTS.
LOCATION
FIXING.
ELECTRICAL CONNECTIONS.
WARNING: THE HEATER MUST BE EARTHED.
Remove from carton and check contents:
- heater unit
- mounting bracket
- 2 no. M6 bolts, 2 no. shakeproof washers, 4 no. plain washers.
Ensure all packing material is removed and inlet/outlet grilles are clear.
.
This heater is designed for high level use above frequently used doorways. It must not be installed less than
1.8metres from floor level and the maximum recommended mounting height is 2.3m. It should not be
positioned immediately below a fixed socket outlet. Optimum performance is achieved when the heater is
positioned as close to the top of the door as possible. For wider doorways multiple units can be installed
giving a continuous curtain of hot air.
The heater can be mounted either a) directly to the wall or b) to the wall or ceiling using the bracket supplied.
a) The unit is mounted directly to the wall via two keyhole slots and fixed via two holes.
1) Securely fix two No.10 screws (not supplied) at 500mm centres 208mm above desired position for
outlet grille.
2) Slide unit over screws and ensure secure fixing.
3) For extra security the front cover can be removed and the two additional mounting holes used
.
(DISCONNECT FROM POWER SUPPLY BEFORE REMOVING COVER)
b) The bracket can be fixed to either the wall or ceiling provided secure fixings can be made
1) Remove plugs from holes in end of unit, loosely fit M6 bolts with 2 plain washers and shakeproof
washer closest to head.
2) Provisionally place in bracket to ascertain optimum location and mark fixing holes.
3) Remove from heater and securely fix bracket
4) Replace heater at appropriate angle and tighten bolts securely.
The Heater should be installed in accordance with the latest edition of the IEE Requirements for Electrical
Installation (BS 7671:2001) by a suitably qualified person.
The unit is NOT suitable for connection via a 13A plug and should be permanently connected to a suitable
230Vac 50Hz. power supply incorporating a means of isolation having a contact separation of at least 3mm
in all poles.
Connect as follows:-
Green-yellow wire to terminal marked E , with earth symbol or coloured green or green-yellow.
Blue wire to terminal marked N. Brown wire to terminal marked L