TOF/Start
English
8
© CEDES | V 1.1
12. Blanking
Both TOF/Start versions feature a blanking function. The
TOF/Start triggers the output when objects are dynamic
(moving) within the detection field. Static objects within the
detection field will be ignored and blanked out (after 30
seconds). This covers with objects that are already present
at power up (i.e. bollards).
Start-up:
Figure 14:
Active blanking - start-up sequence with i.e. bollards.
Figure 15:
After start-up the bollards are blanked out
from the detection field.
Active blanking:
Figure 16:
The detection field is free.
Figure 17:
A static object is placed in the detection field
(i.e a trash bag). The object will be detected.
Figure 18:
After 30 s the static object will be blanked out and
the TOF/Start continues its operation with the new
geometry of the detection field.
13. Trouble shooting
If the problem persists, please contact your local CEDES
representative (www.cedes.com).
LED dimmed
LED bright
LED dimmed
LED dimmed
Status
Action
LED off
Check supply power
Check electrical
connections
Object in the
safeguarded area and
LED dimmed red
Check distance setting
No object in the
safeguarded area and
LED bright red
Check electrical
connections
Check distance setting