Mounting and Operating Instructions
Style 55011 / 55021 (CG-S)
2. Safety Instructions
The device shall only be used
for its intended purpose and
in undamaged and perfect
condition!
Only genuine CEAG spare
parts may be used for re-
placement and repair!
When working on the emer-
gency luminaire first the sys-
tem must be blocked, battery
operation must be interrupted
and mains must be cut off.
Fig. 4 shows the indication
label on the emergency lumi-
naire.
Prior to its initial operation,
the luminaire will have to be
checked in accordance with
the instructions as per section
Installation!
Carry out the marking of the
emergency luminaire: Assign
the circuit and the luminaire
No. and enter them.
Recording in the minutes shall
be performed in compliance
with the national regulations
(is deleted in case of auto-
matic recording).
Any foreign matter shall be
removed from the luminaire
prior to its initial operation!
While undertaking any ser-
vicing on the luminaire, the
national safety rules and regu-
lations for prevention of ac-
cidents shall be observed as
well as the safety instructions
included in these operating
instructions marked with a
3. Conformity with
standards
Luminaire for emergency lighting
acc. to EN 60 598-2-22 for con-
nection to safety luminaire
Fig. 4
systems acc. to DIN VDE 0100-
718, EN 50 172 and E DIN VDE
0108-100. Used ECG is conform
to:
EN 60 929, EN 61 347-2-3 and
EN 61 347-2-4.
Designed, manufactured and
tested according to DIN EN ISO
9001.
4. Technical data
Power input: 220-240 V AC
50/60 Hz
176 - 275 V DC
Standby power loss: < 0.5W
Power factor: 0.6
Inrush current: 3A/ms
Operating frequency: 44 kHz
Rated current (AC): 60 mA
Power con-
sumption (AC): max. 16 VA
Rated current (DC): 30 mA
Lamp:
8 W acc. to
81-IEC-1040-1
Rated luminous flux of
the lamp:
450 lm
Rated luminous flux for emer-
gency operation: 75 % (phi
mains
)
Insulation class:
II
Protection category acc.
to EN 60529: IP 41
At option:
IP 54
Perm. ambient
temperature: - 10 °C ..+ 40°C
Supply
terminals:
3 x 2 x 2.5 mm²
Weight:
0.85 kg (single
side)
1.0 kg (two-sid.)
4.1 Brief description /
Scope of application
Exit or safety luminaire, suitable
for operation on CEAG safety
lighting systems with single
luminaire monitoring (
C
ewa-
G
uard-Technology) and/or with
programmable switching mode
in the outgoing circuit (
S
TAR-
technology).
The Style 55011,-021 (without
CG-S) are not fitted with moni-
toring electronic and so neither
addressable nor switchable.