14. Annex 1: Supervisor alarms - T2S ETH
This is the list of alarms issued by supervisor. Other alarms are issued by other modules (see section 15, page 72).
The supervisor is able to generate alarms that are related to the system, to inverter modules, or to itself. Alarms related
to inverters will be seen as system alarms when module alarm is present on all inverters. Each alarm has a priority
level. The level can be (disabled, event, minor, major). If the level can be configured in user interface, then it is marked
as “mappable”.
System Alarms
Text ID
Name
Level
Def. Map
Description
256
MBP Engaged
mappable
major
Digital input 1 is in low state and digital input 1 is
used for MBP signaling.
257
Surge Arrester
mappable
minor
Digital input 2 is in low state and digital input 2 is
used for surge arrester signaling.
258
Redundancy Lost
mappable
minor
Redundancy is configured and redundancy is lost
on any output group.
259
Redu1 Lost
mappable
minor
Redundancy is configured and more than
redundancy is lost on any output group.
260
Main Source Lost
mappable
major
Any of the groups from main source is not conform.
Example: there are 3 AC input groups and AC
source is main source. If one AC input is offline, the
alarm is triggered.
261
Secondary Source
Lost
mappable
minor
Any of the groups from secondary source is not
conform.
262
AC Source Lost
mappable
R3
Any AC input group is not conform.
263
DC Source Lost
mappable
disabled
Any DC input group is not conform.
264
AC Source Not Sync
mappable
minor
Any AC input group is not synchronized with AC
output or has an out of range frequency.
265
DC Source Low
mappable
major
Any DC input group has a voltage lower that defined
threshold.
266
Output Saturated
mappable
disabled
The load on any output group is higher than the
saturation threshold (80% of configured output
power).
267
Output Overloaded
mappable
major
The load on any output group is higher than the
configured output power.
268
Output Failure
mappable
major
Any output group has 0 seen modules, or no
module running (and they are not manually off).
269
System Started
event
System just started.
272
Missing Module
event
No module is detected on system bus.
273
New Module
event
All modules have just been detected on system bus.
274
Manually OFF
mappable
disabled
All modules outputs are manually turned off.
275
Output Fault
event
All modules outputs are turned off because of a
fault.
276
Brownout Derating
event
All modules AC inputs are derated because of a
brown-out.
69
– Monitoring T2S - ETH User Manual – v1.4
Annex 1: Supervisor alarms - T2S ETH