15. Annex 2: Module alarms - T2S ETH
Module not Recoverable Alarms
Text ID
Name
Level
Def. Map
Check and Action
1
Fan Failure
Minor
Fan replacement
2
Permanent Fault (2)
Minor
3
Permanent Fault (3)
Minor
4
Permanent Fault (4)
Minor
5
Permanent Fault (5)
Minor
6
Permanent Fault (6)
Minor
7
Too Many Starts
Minor
10 starts in 10 min (one a min)-Unplug and replug
inverter and check status
8
Permanent Fault (8)
Minor
9
Permanent Fault (9)
Minor
10
Permanent Fault (10)
Minor
11
Permanent Fault (11)
Minor
12
Permanent Fault (12)
Minor
13
Output Polarity
Minor
14
Overload Too Long
Minor
Check load condition
15
Output Fuse
Minor
16
Permanent Fault (16)
Minor
18
Permanent Fault (18)
Minor
19
Permanent Fault (19)
Minor
28
Permanent Fault (28)
Minor
29
Permanent Fault (29)
Minor
30
Permanent Fault (30)
Minor
31
Permanent Fault (31)
Minor
32
Permanent Fault (32)
Minor
Module Recoverable Alarms
Text ID
Name
Level
Def. Map
Check and Action
33
Output
Synchronization
Minor
Check frequency TSI and Mains
34
Temperature Too High
Minor
Check temperature inside inverter
35
Com. Bus Failure
Minor
T2S bus failure or no T2S seen. TSI blinks red -
hardware problem
36
Com. Bus Conflict
Minor
When two TSI have the same ADX - will self repair
37
No Power Source
Minor
No input AC and inout DC availlable
38
Com. Bus Failure
Minor
TSI has not started must have a T2S - orange LED