When handling the system/units pay attention to sharp edges.
•
This product is suitable for use in a computer room.
3.3 Installation
•
This product is intended to be installed only in restricted access areas as defined by UL60950 and in accordance
with the National Electric Code, ANSI/NFPA 70, or equivalent agencies.
•
The user must observe the recommended UL listed upstream and downstream circuit breaker requirements as
defined in this manual.
•
Please use extreme caution when accessing circuits that may be at hazardous voltages or energy levels.
•
The modular inverter rack is a dual input power supply. The complete system shall be wired in a way that both
input and output leads can be de-energized when necessary.
•
To comply with local and international safety standards N (input) and PE shall be bonded. The bonded connection
between N (input) and PE must be removed once the AC input is connected. Refer 8.3.5, page 22.
•
AC and DC circuits shall be terminated with no voltage / power applied (de-energized).
•
The safety standard IEC/EN62040-1-1 requires that, in the event of an output short circuit, the inverter must
disconnect in 5 seconds maximum. The parameter can be adjusted on T2S ETH or equivalent device; however,
if the parameter is set at a value > 5 seconds, an external protection must be provided so that the short circuit
protection operates within 5 seconds. Default setting is 60 seconds.
•
The system is designed for installation within an IP20 environment. When installed in a dusty or humid
environment, appropriate measures (air filtering) must be taken. Installation of filters may result in de-rating of
module.
•
All illustrations in the manual are for general reference, refer to the technical drawing which is received along
with the system for exact information.
•
Environment Conditions:
Storage Conditions:
-40 to 70°C
Relative Humidity:
95%, non-condensing
Altitude above sea without de-rating:
Less than 1500 m
Greater than 1500 m – de-rating at 0.8% per 100 m
3.3.1 Handling
•
The cabinet shall not be lifted using lifting eyes.
•
Remove weight from the cabinet by removing the inverter modules. Mark inverter modules clearly with shelf and
position for correct rebuild. This is especially important in dual or three phase configurations.
•
Empty module positions must not be left open. Replace with module or dummy cover.
•
This equipment is shipped with a SHOCKWATCH monitor. SHOCKWATCH monitor should be inspected upon
receipt of shipment. If the SHOCKWATCH shows that the equipment was exposed to excessive force the warranty
will be void.
Warranty and Safety Conditions