8.3.5 AC Input and Output
The pictorial representation of terminal blocks arrangement is as follows.
If AC IN is connected, remove the bonding neutral jumper cable between AC IN Neutral and PE terminal.
8.3.6 DC Input
Model
Individual Feed
Common Feed
Torque
lb.in
Breaker
Cable Min
Breaker
Cable Min
48 VDC
2 X 60 A / 1P
1 X 4 AWG
1 X 125 A/ 1P
2 X 4 AWG
26.1 - 52.0
110 VDC
2 x 30 A / 2P
1 X 8 AWG
1 x 60 / 2P
2 X 8 AWG
Recommended Lugs for DC Input cable:
Company
Part Number
Cable
Lug
Sleeve
Panduit
LCCF4-14B-L
4 AWG
Min 1 inch Length
600 V / 105°C
LCCF8-14B-L
8 AWG
Cembre
CL4-D141
4 AWG
CL8-D141
8 AWG