CT-V900 CONTROLLER 

15

 

red to green), access has been denied (flashing red), or the door is locked (solid red). Typically, the reader buzzer  

 

or an external sounding device will inform the card user that the door has been left open after a valid access or the 

 

door has been forced open. The functions of all these outputs are programmable through the Centaur software.

Figure 11: Connecting Locking Devices

LOCKING DEVICES

 

Each controller has two lock outputs and each of these outputs is associated to a reader input. Using the lock output 

 

jumpers you can set each lock output to provide 12VDC or 24VDC (see “Jumper Settings” on page 8). A lock output 

 

voltage of 24VDC is recommended for most locking devices. Lock outputs are protected by fuseless technology and 

 

will shutdown if the current exceeds 800mA @ 12/24VDC.

 

• If you have one door with a reader on each side of the door, you can use either lock output.

 

• You can program the lock outputs to function in “fail-safe” (remove power to unlock a door) or “fail-secure” mode

 

  (power required to unlock a door).

 

• When using Electronic Mag Clamps or similar devices ensure that the current specifications are not exceeded.

 

•  When  interconnection  to  a  fire  alarm  system  is  required,  we  recommend  the  CA-A110  Lock  Control  Module. 

 

 

  This module can be used to cut power to the locks during a fire alarm. Refer to the module’s installation instructions

 

 

  for connection of the CA-A110 device.

 

Always consult the regulatory agency in your area for existing regulations regarding doors designated as

 

emergency exits.

Figure 12: Connecting Locking Devices using CA-A110 Lock Control Module

www.cdvgroup.com

Содержание CT-V900

Страница 1: ...CT V900 Controller Installation Manual...

Страница 2: ......

Страница 3: ...kup 7 LED Indicators 7 Upon Power Up 7 Battery Indications 7 Jumper Settings 8 BATT ON OFF 8 EOL Controller Network 8 12V 24V Lock 1 8 12V 24V Lock 2 9 High Low Network Impedance 9 EOL E Bus Network 9...

Страница 4: ...our web site at www postech ca ACCESSORY MODULES POSIPROX CARD READER CR R880 Proximity technology will never be the same again PosiProx sets exacting new standards in design reliability and affordabi...

Страница 5: ...allowing the card holder to selectthedesiredfloor TheDestinationControlledModeoffersafarsuperioreventtrailanduseraccountability by permitting the card holder to make only one floor selection upon pre...

Страница 6: ...m 2 5 wide 10cm 4 deep Multiple Conduit Knock outs Two 25mm 1 or 31mm 1 25 and one 12mm 0 5 or 19mm 0 75 on each side Minimum Clearance For Cabinet 25cm 10 clear space around all sides 38cm 15 clear s...

Страница 7: ...strobe during this one minute period LED INDICATORS For location of LEDs refer to Figure 2 on page 8 UPON POWER UP The AC PRESENT LED should be on The READER 5 VOLT LED should be on The 12 VOLT SUPPL...

Страница 8: ...er to off until the the battery is replaced Note however if a complete power loss occurs the time and date as well as all controller programming will be lost EOL CONTROLLER NETWORK Places the EOL term...

Страница 9: ...ntrollers each Using Table 1 on page 10 set the dip switches to the desired controller address Each of these loops is assigned to a specific COM port Controllers connected to the selected COM port wil...

Страница 10: ...F OFF OFF ON OFF OFF 31 OFF ON ON ON ON OFF 53 OFF OFF ON OFF ON ON 10 ON OFF OFF ON OFF OFF 32 ON ON ON ON ON OFF 54 ON OFF ON OFF ON ON 11 OFF ON OFF ON OFF OFF 33 OFF OFF OFF OFF OFF ON 55 OFF ON O...

Страница 11: ...CA 360 converter as shown in Figure 5 If the access control server is located less than 25 feet from the first controller you can connect the access control server directly to the controller s RS 232...

Страница 12: ...assigned by the dip switches on each controller see page 9 do not have to correspond to the actual order of controller placement along the RS 485 network However we recommend that this is done to faci...

Страница 13: ...CT V900 CONTROLLER 13 Figure 9 Overview of Access Control System Using Centaur 3 0 www cdvgroup com...

Страница 14: ...free exit Controlled entry and exit by using 2 readers per door no entry or exit registration Controlled entry and exit by using 2 readers and 2 keypads per door no entry or exit registration Reader...

Страница 15: ...ts are protected by fuseless technology and will shutdown if the current exceeds 800mA 12 24VDC If you have one door with a reader on each side of the door you can use either lock output You can progr...

Страница 16: ...nd wire fault short circuit recognition but will generate an alarm condition when the state of the input is breached Only odd numbered inputs 1 3 5 need to be programmed ATZ 2R CONNECTION 16 INPUTS Th...

Страница 17: ...ators 2 Floors per Elevator 64 Schedules per Floor per Elevator Yes Floor Groups 128 Inputs Readers 2 Wiegand or Track 2 Magnetic Swipe Card Readers Keypads 2 Wiegand and or BCD Keypads Multi Purpose...

Страница 18: ...nk Distributed Architecture 100 off line operation Local Anti passback Dynamic Memory Adjustment Operates with all Centaur Software Applications E Bus for Plug and Play expansion modules Ethernet or N...

Страница 19: ...CT V900 CONTROLLER 19 DIAGRAMS SYSTEM DIAGRAM Figure 14 Overview of Controller Connections www cdvgroup com...

Страница 20: ...the door is monitored by installing a magnetic door contact reed switch Separate wire runs must be installed for each card reader door contact and door locking device With this configuration a card a...

Страница 21: ...used so that the system can differentiate between a door forced open and an authorized exit The REX can be programmed for free exit according to a specific schedule otherwise a door forced open event...

Страница 22: ...wise including without limitation any implied warranty of merchantability and fitness for a particular purpose are expressly excluded Because Seller does not install or connect the products and becaus...

Страница 23: ...31 avenue du G n ral Leclerc 93500 PANTIN T l 33 0 1 48 91 01 02 Fax 33 0 1 48 91 21 21 www cdvgroup com...

Отзывы: