CDVI CDV4796KP-DX Скачать руководство пользователя страница 5

A

B

*Notes:

  1. Maximum of 4 monitors per call button. 

Daisy Chain Shown 

– 

Use CDV-DBC4A for Star Configuration

NOTE: Max distance from DBC4A to Device is 40m

2.  Cat5E  can  only  be  used  for  a  maximum  of  2 
monitors. 

2 Easy 1 & 2 User (Kit) Cable & Distance Specifications

Cable Type 

A Max 

B Max 

<2

 

Internal 

Monitors

 

B Max 

<8* 

Internal 

monitors

 

Belden 9740 

 1 Twisted Pair 0.79mm

2

 

60m 

100 

40m 

Belden 8471 

 1 Twisted Pair 1.34mm

2

 

80m

 

120m

 

60m

 

CAT5e 

 4 Twisted Pairs 0.2mm

IMPORTANT: ALL STRIPES AND ALL SOLIDS  USED FOR 

EACH BUS-LINE 

40m 

40m 

N/A 

 

Cable Type 

A Max 

B Max 

<2

 

Internal 

Monitors

 

B Max 

<8* 

Internal 

monitors

 

Belden 9740 

 1 Twisted Pair 0.79mm

2

 

60m 

100 

40m 

Belden 8471 

 1 Twisted Pair 1.34mm

2

 

80m

 

120m

 

60m

 

CAT5e 

 4 Twisted Pairs 0.2mm

IMPORTANT: ALL STRIPES AND ALL SOLIDS  USED FOR 

EACH BUS-LINE 

40m 

40m 

N/A 

 

240AC

CDV-PC6

CDV-PC6

CDV47DX

CDV43

CDV43

CDV43

Содержание CDV4796KP-DX

Страница 1: ...door stations with stylish handsets it all adds up to a sophisticated and exible audio entry system Datasheet The 2EASY system from CDVI o er convenient and high quality video entry Connection through...

Страница 2: ...ideo signal 1Vp p 75 CCIR standard Display resolutions 800 3 R G B x 480 pixels Video 2 wires non polarised Wiring Power input 12 24 Vdc Power supply 20 to 28 Vdc for indoor monitor Power consumption...

Страница 3: ...or CMOS 2 0 Mega pixel 1 2 7 sheye camera 1700 wide angle Camera Number of realy circuits 2 the second lock output requires CDV RLC Output Speci cations Power Supply 24Vdc Power Consumption 105mA work...

Страница 4: ...k Datasheet Rated output voltage 28Vdc 2Vdc Rated output current 1 5A Output Speci cations Dimensions 140 x 90 x 60mm Environment 10 C to 50 C Dimensions Input voltage 100 240Vac Input frequency 50 60...

Страница 5: ...nitors Belden 9740 1 Twisted Pair 0 79mm2 60m 100 40m Belden 8471 1 Twisted Pair 1 34mm2 80m 120m 60m CAT5e 4 Twisted Pairs 0 2mm2 IMPORTANT ALL STRIPES AND ALL SOLIDS USED FOR EACH BUS LINE 40m 40m N...

Страница 6: ...01628 531300 www cdvi co uk The installer s choice CDV4796KP DX KIT MANUAL...

Страница 7: ...V47DX Part and Functions 4 1 Terminals Installation 4 2 Mounting 4 3 Main menu 4 4 Installer Setting 4 5 User Code Monitor ID Address setting 4 6 Unlock Time Setting 4 7 Unlock Mode setting 5 Schemati...

Страница 8: ...LED 4 Touch keypad 5 Keypad LED 6 Call button 1 Camera lens 2 Camera LED 3 Speaker 1 2 3 Lock Control Jumper L1 PL S1 GND Main Connect Port L2 S1 GND Lock power connection port Main Connect Port For c...

Страница 9: ...combiner or auxiliary PSU The features are as follows 3 Mounting 3 1 Description Universal AC input full range Multi protection short circuit overload over voltage Integrated with CDV DPS power separa...

Страница 10: ...nected CN Bus control terminal BUS IM Indoor monitor connection terminal BUS DS Door station connection terminal Open the AC cover 1 Push the cover base towards the centre with your fingers 2 Lift up...

Страница 11: ...n port Ring GND Extension buzzer input connection port NC Reserved DIP switchesBit1 Bit5 Reserved Bit6 Video impedance matching switch Set to ON if the monitor is at the The installation height is sug...

Страница 12: ...lls Setting Press to enter setup interface Close Touch to turn off the screen and make the monitor in standby mode Call Scene Touch to activate the functions of No disturb Divert call Touch this icon...

Страница 13: ...Setting Call Tune General Installer Wireless About Current addtess 01 Intercom enable Enable IPC Setting Monitor list manage System settings Touch to set the user code for each monitor 1 Enter the cod...

Страница 14: ...etting the unlock mode Current addtess 01 IPC Setting Monitor list manage System settings FW upgrade Unlock time 03 Unlock mode Open Auto reboot Enable Reboot Installer Installer Call Tune General Ins...

Страница 15: ...L1 L2 PL S1 GND Doorbell Button Switch Code 00 DIP6 on 1 2 3 4 5 6 ON DIP L2 L1 DIP Switches 100 240VAC DBC4A1 A B C D OFF ON Impedance switch BUS IM BUS DS PC6A AC 4 Camera L1 L2 PL S1 GND L1 L2 PL S...

Страница 16: ...DIP6 on Slave 3 BUS IM BUS DS CDV PC6 AC 100 240VAC Code 1 DIP6 off Slave 1 5 3 Basic IN OUT Wiring in Standard Mode The door station is compatible with other monitors within the 2Easy range For the...

Страница 17: ...e 0 Slave 3 DIP6 on Code 0 Master DIP6 on Code 0 Slave 1 DIP6 on 5 4 Star Topology Wiring With CDV DBC4A1 in Standard Mode CDV BDU bus amplifier module CDV RLC staircase light controller module CDV DB...

Страница 18: ...type locks of Power on to unlock fail secure type should be used 4 The Unlock Mode Parameter of the Monitor must be set to 0 default Note 1 This mode only supports strike type locks 1 An external pow...

Страница 19: ...the buzzer beeps and the system exits the setting mode When there isn t any operation in 10s the LED lights off the buzzer beeps and the system exits the setting mode red OFF blue OFF Beep Beep Setti...

Страница 20: ...iring 2 wires non polarity Dimension 132 H 226 W 18 D mm 6 2 CDV PC6 Specifications 6 3 CDV 47DX Specifications Power Supply DC 24V Power Consumption Standby 14mA Working status 122mA Camera Color CMO...

Страница 21: ...fferent cables may also affect the maximum distance which the system can reach Basic IN OUT Wiring Mode Cable Usage A B 2 IM B 16 IM A B CDV PC6 Belden 9470 UTP 2x0 75mm 2 60 100 40 Belden 8471 UTP 2x...

Страница 22: ...s choice B A C 2 2 CDV DBC4A1 CDV PC6 Cable Usage A B C Belden 9740 UTP 2x0 75mm 2 60 60 30 Belden 8471 UTP 2x1mm 2 80 80 40 Cable and distance unit m Star Topology Wiring Mode With CDV DBC4 1 4 5 6 8...