Using the Outputs 

The milliamp output is scaled so that four milliamps corresponds to zero flow and 
20 milliamps corresponds to the range of the meter indicated on the data sheet. 
The meter will display the milliamp full-scale value for a few seconds on startup. 
It will also display it if the button on the main (lower) circuit board is pressed 
twice. 

The pulse output generates a square wave signal, sending one pulse for each 
cubic foot of air that passes through the meter. The LED blinks with the pulse 
output. At zero flow it may be on or off. The pulse output can be configured as a 
threshold output, and the scaling of both the pulse output and the milliamp output 
can be changed, using the optional configuration cable. 

Using the Display 

Pressing a button indicated by a circle on the front of the meter cycles the display 
through four display options: rate, daily usage, cumulative usage and units of 
measure, the last indicated by a digit: (0) for scfm, (1) for m

3

/min and (2) for 

m

3

/hr. The cumulative values are indicated in thousands of cubic feet or cubic 

meters. Holding the button pressed in either of the cumulative modes (daily 
usage or cumulative usage) will reset that value to zero. The display normally 
defaults to the rate display, but this can be changed, as can the units of measure 
and the decimal point location in the cumulative modes. Please refer to 
information on configuring the display. 

Maintenance 

If oil or dirt accumulates on the probes, the meter will read inaccurately. For this 
reason, we recommend cleaning the probes from time to time. To clean the 
probes, wipe them with a cloth dampened with alcohol or a similar degreaser. It 
may be found that the system is clean enough that cleaning is not needed.  

 

 

Warranty 

CDI warrants solely to the buyer that the Model 5250 Flowmeter shall be free from 
defects in materials and workmanship, when given normal, proper and intended 
usage, for three years from the date of purchase. During the warranty period, CDI will 
repair or replace (at its option) any defective product at no cost to the buyer. The 
foregoing warranty is in lieu of any other warranty, express or implied, written or oral 
(including any warranty of merchantability or fitness for a particular purpose). CDI’s 
liability arising out of the manufacture, sale or supplying of the flowmeter, whether 
based on warranty, contract, tort or otherwise, shall not exceed the actual purchase 
price paid by the buyer, and in no event shall CDI be liable to anyone for special, 
incidental or consequential damages. 

Содержание 5250

Страница 1: ...cdimeters CDI Meters Inc support cdimeters com 866 885 2462 www cdimeters com CDI 5250 Hot Tap Flowmeter Installation and Operating Instructions ...

Страница 2: ...trogen They must be installed in a pressurized pipe to ensure all chips are cleared They are not for use in control or safety applications or designed for installation where pressure exceeds 130 psig 9 barg The temperature compensation of the meters is suitable for use from 20 to 120 F 7 to 49 C Locating the Meter For accurate and reliable readings the meters must be installed with adequate straig...

Страница 3: ...match the direction of flow in the pipe If doing so will cause the display to be upside down remove the cover of the meter lift out the display rotate both 180 and re install Apply the Holes in Pipe decal so that it will be hidden when the meter is in place but will be revealed when it is removed Installing the Meter Installation of the CDI 5250 Hot Tap Flowmeter should be done by an experienced m...

Страница 4: ...asionally back the drill bit off of the pipe to help dissipate heat and clear the chips b Once you have broken through the first wall of the pipe and being careful not to drill into the far wall run the drill bit up and down through the hole to ensure clean edges With the drill bit still spinning extract it so one to two inches of it is exposed being careful not to completely remove the bit or exp...

Страница 5: ...nted to the base b With the flow arrow in the correct direction insert the probes into the two holes of the slider plate Expect some resistance as the probes make their way through the O rings Continue to push in until the probes make contact with the closed valves At this point any leakage noted in step 2c should go away Step 4 a With one hand firmly holding the top assembly use the other to rota...

Страница 6: ...er will draw a maximum of 250 mA Unlike earlier 5200 and 5400 meters the Rev 3 meters do not connect the dc terminal to the pipe on which they are mounted Please note that 18 Volt dc supplies furnished with some earlier CDI flowmeters do not provide the voltage required for Rev 3 meters REMOTE DISPLAY If you are using the summing remote display SRD connect the three terminals marked display to the...

Страница 7: ...he receiving device to the negative supply of the meter If an isolated relay contact is required install the CDI 5200 IPO isolated pulse output and wire it to the receiving device SERIAL COMMUNICATION OPTION The RS 485 signal used with the Serial Communication option is wired to the Serial Communication display board The two threaded openings in the meter enclosure permit the signal to be wired fr...

Страница 8: ...umulative usage will reset that value to zero The display normally defaults to the rate display but this can be changed as can the units of measure and the decimal point location in the cumulative modes Please refer to information on configuring the display Maintenance If oil or dirt accumulates on the probes the meter will read inaccurately For this reason we recommend cleaning the probes from ti...

Отзывы: