CD Automation srl
pag. 47 di 121
INTEGRAL TIME
(available only with PID o PI - CntF <> onoF (group miSC of configuration))
Upper display
ti1
Lower display
Actual Value
Range
00.01
↔
20.00 mm.ss
Beyond the maximum value, the display of the integral action is excluded.
With selftune activated, the lower limit is given by Lti
DERIVATIVE TIME
(available only with PI - CntF = Pi (group miSC of configuration))
Upper display
td
Lower display
Actual Value
Range
00.01
↔
10.00 mm.ss
With selftune activated, the derivative time is equal to tI / 4
INTEGRAL PRELOAD
(available only with PID or PI - CntF <> onoF (group miSC of configuration))
Upper display
iP1
Lower display
Actual Value
Range
With O2Fn
≠
Cool
0
↔
100
With O2Fn = Cool
-100
↔
100