12
REVO SSR
User’s manual
Installation
Before to install, make sure that the Thyristor unit have not
damages. If the product has a fault, please contact the dealer
from which you purchased the product. Verify that the product
is the same thing as ordered.
The Thyristor unit must be always mounted in vertical position to
improve air cooling on heat-sink.
Maintain the minimum distances in vertical and in horizontal as
represented. When more unit has mounted inside the cabinet
maintain the air circulation like represented in figure.
Sometimes is necessary installing a fan to have better air
circulation.
The Thyristor unit must be used in conjunction with an
appropriate heat-sink (Optional).
The heat-sink must be sized in relation to environment
temperature and the load current (see the Dissipation Curves).
The assembly (module-heatsink) must happen on a flat surface
with low roughness. The fixing holes on the heat-sink must be
threaded and countersunk. Spread a layer of thermo-conductive
silicon putty between the two surfaces (the surfaces must be
clean and the thermo-conductive silicon putty must be free of impurities).
Tighten the two fixing screws M4 alternately until reaching a torque of 1 Nm.
Attention: make sure that there are no air bubbles under the copper plate.
3
≥5 cm
≥15 cm
≥2 cm
AIR
AIR
97
m
m
36 m
m
33
mm
9,2 mm
6 mm
47,5 mm
M4
Weight
0,12Kg
3.1 Dimensions and Fixing holes
Size: SR0
Содержание REVO SSR
Страница 2: ......