CD Automation srl
REVO S
User’s Manual
CD-Eng-REVO-S-2PH-280-700A-Solid-State-Relay
13
6
Wiring instructions
The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply,
for this reason in accord to the fundamental practices rules is opportune take some precautions:
The coil contactor, the relays and other inductive loads must be equipped with opportune RC filter.
Use shielded bipolar cables for all the input and output signals.
The signal cables must not be near and parallel to the power cables.
Local regulations regarding electrical installation should be rigidly observed.
Use copper cables and wires rated for use at 75°C only.
6.1
Removing the cover
Instructions for open the thyristor unit S10
Instructions for open the thyristor unit size S14
6.2
Power cable torque (suggested)
Current
Connector
Type
Torque
Lb-in (N-m)
Wire
Range
AWG / kcmil
Wire
Terminal
280A (S10)
Bus Bar
with M8 screw
265 (30.0)
2x1/0
300
UL Listed (ZMVV)
Copper Tube Crimp. Lug
400A (S14)
Bus Bar
with M10 screw
505 (57.0)
2x3/0
600
UL Listed (ZMVV)
Copper Tube Crimp. Lug
450A (S14)
Bus Bar
with M10 screw
505 (57.0)
Bus bar
30x6mm
500A (S14)
Bus Bar
with M10 screw
505 (57.0)
Bus bar
60x4mm
600A (S14)
Bus Bar
with M10 screw
505 (57.0)
Bus bar
60x5mm
700A (S14)
Bus Bar
with M10 screw
505 (57.0)
Bus bar
60x6mm
Содержание Revo S
Страница 2: ...CD Automation srl REVO S User s Manual 2 ...
Страница 8: ...CD Automation srl REVO S User s Manual CD Eng REVO S 2PH 280 700A Solid State Relay 8 3 2 Order Code ...
Страница 15: ...CD Automation srl REVO S User s Manual CD Eng REVO S 2PH 280 700A Solid State Relay 15 6 5 Terminals Positions ...
Страница 31: ...CD Automation srl REVO S User s Manual CD Eng REVO S 2PH 280 700A Solid State Relay 31 ...