REVEX
3PH from 120A to 210A
User’s manual
37
9.4.5 Communication Menu
This section describes each item on the communication menu. Use this menu to configure the communication
options.
The password to access this menu is 3.
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Port 1 Baud
Choose the baud rate for the primary serial port
2
30
Read
Write
Option
Value
9600
0
19.2K
1
38.4K
2
115.2K
3
DEFAULT:
38.4K
2
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Port 1 Addr
Set the address for the primary serial
port
1
0 to 255
31
Read
Write
Port 2 Baud
Choose the baud rate for the primary
serial port
2
45
Read
Write
Option
Value
9600
0
19.2K
1
38.4K
2
115.2K
3
DEFAULT:
38.4K
2
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Watchdog
Enable or disable the watchdog on the primary
serial port
0
142
Read
Write
Option
Value
Off
0
On
1
DEFAULT:
Off
0
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
WD Reset
Set the amount of time to wait for a
message before triggering the watch-
dog error.
This function is available only for Modbus
RTU Protocol
5
0 to 255
Sec
143
Read
Write
Содержание REVO REVEX3PH
Страница 2: ......