REVO C
3PH from 60A to 210A
User’s manual
35
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Control Mode
(Feed-back)
Choose the Feed-back type
1
19
Read
Write
Option
Description
Value
Voltage ²
Voltage squared
0
None
No feed-back
1
Current ²
Current squared
2
Voltage
Voltage
32
Current
Current
64
Power
Power
128
External
External signal via analog input 2
256
DEFAULT:
None
1
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Prop band power
Set the gain for the main loop. A
smaller proportional band yields a
larger adjustment for a given deviation
10%
0 to 255
%
26
Read
Write
Integral power
Set how aggressively the integral part
of the control algorithm acts. A smaller
settings yields a larger adjustment for
a given deviation over a given time
50
0 to 255
27
Read
Write
Prop band current
Set the gain for the current loop. A
smaller proportional band yields a
larger adjustment for a given deviation
10%
0 to 255
%
63
Read
Write
Integral current
Set how aggressively the integral acts
in the current loop. A smaller settings
yields a larger adjustment for a given
deviation over a given time
50
0 to 255
64
Read
Write
Htr Break
sensitivity
Set the threshold of resistance that
activates the Heater Break alarm. This
setting is in percentage of the nominal
load resistance
100%
0 to 100.0
%
29
Read
Write
Htr Break delay
Set a delay between when the
resistance drops below the value set
for a heater break sensitivity and when
the heater break alarm is indicated.
This set increments of 50mSec
50 (2,5
sec)
0 to 255
(0 to 12,75
sec)
28
Read
Write
Logging
Enable or disable data logging on the
internal SD card
0
139
Read
Write
Option
Value
Off
0
On
1
DEFAULT:
Off
0