18
REVO C
3PH from 1100A to 2100A
User’s manual
Technical Specifications
6.1 General features
Utilization Category:
AC-51
IP Code:
00 (IP20 on request)
Method of Connecting:
Load in Delta, Load in Star
Auxiliary voltage:
Order code RC3_ _ _ -_1 = line voltage 100/120V transformer range 90:135V (8 VA Max)
Order code RC3_ _ _ -_2 = line voltage 200/208/220/230/240V transformer range 180:265V (8 VA Max)
Relay output for Heater Break Alarm:
0.5A a 125VAC
(only with HB option)
6.2 Input features
Digital Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 0,5Hz max
Volt Analogic input:
0 ÷ 10Vdc impedance 15 kΩ
Current Analogic input:
0 ÷ 20mA impedance 100 Ω
4 ÷ 20mA impedance 100 Ω
Potentiometer:
10 kΩ min.
Logic input SSR (Fast Enable):
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc)
duty cycle min. 100 ms max 3Hz
6.3 Output features 600V
Current
Output
Voltage
range
(Ue)
Repetitive
peak
reverse
voltage
(Uimp)
Latching
current
Max peak
one cycle
Leakage
current
FUSE I
2
T
value
Suggested
A2s (at
660V)
Frequency
range
Power
loss
Thyristor
+ Fuse
FANS
(230Vac Standard)
(115Vac Option)
(A)
(V)
(up to
600V)
(mAeff)
(10msec.)
(A)
(mAeff)
tp=10msec
(Hz)
I=Inom
(W)
N°
W
m3/h
1100A
24÷600
1800
700
22400
300
480.000
47÷70
4047
3
225
(75 x 3 Fan)
2340
(780 x 3 Fan)
1400A
24÷600
1800
700
22400
300
1.750.000
47÷70
5469
6
450
(75 x 6 Fan)
4680
(780 x 6 Fan)
1600A
24÷600
1600
700
26900
300
2.200.000
47÷70
5583
6
450
(75 x 6 Fan)
4680
(780 x 6 Fan)
1800A
24÷600
1800
700
36000
300
2.200.000
47÷70
6243
6
450
(75 x 6 Fan)
4680
(780 x 6 Fan)
2100A
24÷600
1600
700
38000
300
3.700.000
47÷70
7083
6
450
(75 x 6 Fan)
4680
(780 x 6 Fan)
6