36
REVEX
1PH from 120A to 210A
User’s manual
Parameter Name
Description
Default
Modbus
Address
Par.
Type
DI1 Functn
Choose how the signal detected by digital input 1
is used
2
32
Read
Write
Option
Description
Value
Enable
Enable power output
0
V Feedback
Use voltage feed-back when on
2
Local / Rmt
Local when on / Remote when off
3
Ph Angle
Use phase angle firing when on
4
SP AI1/AI2
Select remote set point source: analog input 1 when off or analog input 2 when on
5
Htr Bake
Enable heater bakeout
7
FastEn
Fast Enable
8
DEFAULT:
Voltage Feed-back
2
SSR Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 3HZ Max on time min. 100 ms
When the Fast Enable input is enabled, Phase Angle firing is automatically selected.
Parameter Name
Description
Default
Modbus
Address
Par.
Type
DI2 Functn
Choose how the signal detected by digital input 2
is used
0
33
Read
Write
Option
Description
Value
Enable
Enable power output
0
V Feedback
Use voltage feed-back when on
2
Local / Rmt
Local when on / Remote when off
3
Ph Angle
Use phase angle firing when on
4
SP AI1/AI2
Select remote set point source: analog input 1 when off or analog input 2 when on
5
Htr Bake
Enable heater bakeout
7
FastEn
Fast Enable
8
DEFAULT:
Enable
0
SSR Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 3HZ Max on time min. 100 ms
When the Fast Enable input is enabled, Phase Angle firing is automatically selected.