background image

14

 Hardware 

Installation 

Place the CTs around the line wires as shown in section 

2.2 Measurement Configurations

. Split-core 

(opening) CTs may be placed around the line wires without disconnecting the wire. After a split-core CT 
has been placed around a wire, a nylon cable-tie should be secured around the CT to prevent inadvertent 
opening. Toroidal CTs require that the wire be disconnected before passing it through the opening in the 
CT. Always remove power before disconnecting any live wires. 

Next, connect the CTs to the WattNode. The CT inputs to the WattNode are sensitive to ESD (electrostatic 
discharge), so you should discharge yourself by briefly touching the service panel case or some other 
grounded metal object before connecting the CTs to the WattNode. Route the twisted black and white 
wires from the CT to the WattNode. Any excess length may be trimmed from the wires if desired. Strip or 
trim the wires to expose 1/4" (6 mm) of bare wire. Do not leave more than 5/16" (8 mm) or less than 7/32" 
(5 mm) of bare wire. The current transformers connect to the black screw terminal block. Connect each CT, 
with the white wire aligned with the white dot on the label, and the black wire aligned with the black dot. 
Note the order in which the phases are connected, because the voltage phases must match the current 
phases for accurate power measurement. Any unused CT inputs must be shorted. You may trim short 
sections off the end of the CT wires to use as jumpers. Be careful to leave insulation on the exposed 
portion of the jumper(s) to prevent shock or shorting danger. 

The final installation step for the CTs is part of the network installation. The full-scale current rating of the 
CTs must be programmed into the WattNode so that it can correctly scale the output readings. For detailed 
instructions see section

 

4.2.3 Energy Configuration

. To facilitate this step, the installer should record the 

CT full-scale current as part of the installation record for each WattNode. If the wires being measured are 
passed through the CT(s) more than once, then the recorded full-scale CT current is divided by 

n

 where 

n

 is 

the number of times that the wire passes through the CT. 

2.5  Connecting Voltage Terminals 

Disconnect power—by shutting off circuit breaker(s) or removing fuse(s)—before connecting the voltage 
lines to the WattNode. The WattNode must be connected to voltage lines which are protected by fuses or 
circuit breakers.  Connect each voltage phase input to a circuit breaker on the required phase. If there is 
more than one circuit breaker on a phase, then any one of the circuit breakers may be used. When installing 
multiple WattNodes at the same site, it may be easier to provide separate circuit breaker(s) for the 
WattNodes. 

The detachable screw terminals may be installed or removed while power is applied. CCS recommends the 
use of insulated gloves whenever working with a live circuit. 

When connecting the WattNode, do not place more than one voltage wire in a screw terminal; use separate 
wire nuts or terminal blocks if needed. The screw terminals handle wire up to 12 AWG. Prepare the 
voltage wires by stripping the wires to expose 1/4" (6 mm) of bare wire. Do not leave more than 5/16" (8 
mm) or less than 7/32" (5 mm) of bare wire. Connect each voltage line to the white terminal block as 
described in section 

2.2 Measurement Configurations

. Double check that the voltage line phases match 

the phases to which the CTs are connected. After the voltage lines have been connected, make sure both 
terminal blocks are securely installed on the WattNode. 

The WattNode is powered from the voltage inputs: phase A to neutral, or phase A to phase B for delta 
models. If the WattNode is not receiving at least 80% of the nominal line voltage, it will stop measuring 
power. Since the WattNode consumes some power itself, a decision must be made about whether to place 
the CTs before or after the connection for the WattNode, so as to include or exclude the WattNode’s own 
power consumption (1.5 – 3.0 watts). 

2.6 Network Wiring 

CCS recommends that an experienced LonWorks network installer be consulted for network design, 
including choice of transceivers, wiring, and termination. The WattNode may communicate over a twisted 
pair network or over the power lines. Power line transceivers do not require additional network wiring, but 
twisted pair transceivers require connection to a twisted pair network. 

Содержание WattNode WNA-1P-240-FT10

Страница 1: ...WATTNODE for LONWORKS User s Guide Continental Control Systems http www ccontrolsys com Rev 1 22...

Страница 2: ...ial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio com...

Страница 3: ...als 14 2 6 Network Wiring 14 2 7 Installation Summary 15 3 NETWORK CONFIGURATION 16 3 1 Identifying the WattNode 16 3 2 WattNode Reinitialization 16 3 3 Network Variables 17 3 3 1 Authentication 17 3...

Страница 4: ...34 5 2 2 Test CT Ordering 34 5 2 3 Test CT Output 34 6 SPECIFICATIONS 35 6 1 Models 35 6 2 Current Transformers 35 6 3 Accuracy 36 6 4 Timekeeping 36 6 5 Update Rate 36 6 6 Ratings 36 6 6 1 Electrica...

Страница 5: ...se Phases Wires Neutral Present WNA 1P 240 xxx 120 240 1 2 or 3 Yes WNA 3Y 208 xxx 120 208 240 3 4 Yes WNA 3Y 400 xxx 240 400 3 4 Yes WNA 3Y 480 xxx 277 480 3 4 Yes WNA 3Y 600 xxx 347 600 3 4 Yes WNA...

Страница 6: ...etwork variables of the same type Whenever an output network variable is updated the new value is propagated over the network and all devices which have input network variables bound to the updated ou...

Страница 7: ...nnect the CTs to the WattNode before connecting the line voltages to the WattNode Note in some installations the CT screw terminals will be at line voltage 8 Do not place more than one voltage wire in...

Страница 8: ...inputs must be shorted with an insulated jumper wire Single phase two wire circuits can be measured with models WNA 1P 240 or WNA 3Y 208 Phase A LINE Neutral LOAD Current Transformer WHITE BLACK Sourc...

Страница 9: ...ts in 120 VAC between either line wire and neutral or 240 VAC between the two line wires Single phase three wire circuits can be measured with models WNA 1P 240 or WNA 3Y 208 Note Neutral must be conn...

Страница 10: ...ase three wire delta circuits should be measured with the WNA 3D 208 208 VAC phase to phase or the WNA 3D 480 480 VAC phase to phase Source Faces Phase A LINE Phase B Phase C LOAD Current Transformers...

Страница 11: ...phases It is important however that the neutral line be correctly connected Three phase four wire wye circuits should be measured with the WNA 3Y 208 208 VAC phase to phase and 120 VAC phase to neutra...

Страница 12: ...C Wild Phase 240 VAC 240 VAC Neutral FT10 WNA 4WD 240 FT10 Continental Control Systems WATTNODE C CT B CT A CT Service C 208 VAC B 120 VAC A 120 VAC Figure 2 6 Three Phase Four Wire Delta Connection 2...

Страница 13: ...ors eliminate any shock hazard There are two steps to connecting the current transformers mounting each CT around the wire to be measured and connecting the CTs to the WattNode The WattNode does not m...

Страница 14: ...ided by n where n is the number of times that the wire passes through the CT 2 5 Connecting Voltage Terminals Disconnect power by shutting off circuit breaker s or removing fuse s before connecting th...

Страница 15: ...d have one wire for each direction on the network If this is done then take extra care with the two wires in each terminal slot so that they are both securely tightened Any loose wires could disable a...

Страница 16: ...eed to be identified for the network The network management software must be able to find unconfigured nodes on the network When an unconfigured node is found the network management software will be i...

Страница 17: ...Energy Measurement Object 1 Power Measurement Object 2 and Demand Measurement Object 3 Each object has several associated network variables NVs Each NV has a self documentation string with a LonMark...

Страница 18: ...dy hr mn sec ms nciWMinDelta SNVT_power_f 1 0e38 W Amount by which power must change to force an output transmission nciPowLimHi SNVT_power_f 1 0e38 W Power alarm high limit nciPowLimLo SNVT_power_f 0...

Страница 19: ...ns the number of the object to which the request is directed and the request type In response to each request the object s status is returned in nvoStatus The status variable nvoStatus also indicates...

Страница 20: ...power object will be set to 1 Each field of nvoStatus used by the demand object will be set to 1 OVERRIDE 6 Invalid request Energy totals are set to zero and the in_override field is set in nvoStatus...

Страница 21: ...tNode has both power and demand alarms The power alarm can be configured for an over power alarm and an under power alarm The demand alarm can be configured for two levels of over power alarms Wheneve...

Страница 22: ...y total will always increase as long as the WattNode is online The energy total is reset to zero by an override request or when either nciGain or nciCTAmps is changed For most metering applications th...

Страница 23: ...sembly and should never need adjustment If the WattNode is being used for billing or sub metering see 3 3 1 Authentication on information to prevent unauthorized changes to the configuration The full...

Страница 24: ...hree different units Network Variable Resolution Range nvoPowerW 0 1 watt 0 to 6553 5 watts nvoPowerKW 0 1 kilowatt 0 to 6553 5 kilowatts nvoPower_f 1 2e 7 measurement 0 to 1 0e38 watts Table 4 4 Powe...

Страница 25: ...configured in units of floating point watts over the range 0 to 1 0e38 W The list of alarm configuration variables follows nciPowLimHi The power value above which the high power alarm is set This may...

Страница 26: ...larm if the power falls below 10 kW to indicate that the pump may no longer be performing its cooling duty We set nciPowLimHi to detect the 25 kW 25 000 W level alarm Suppose we don t want the alarm t...

Страница 27: ...im1 SNVT_power_f nciDemHiLim2 SNVT_power_f nc9 nc10 Manufacturer Specific Variables Figure 4 5 Demand Measurement Object Demand is defined as the average power over a specified time interval Typical d...

Страница 28: ...ree Subintervals 4 4 1 Demand Configuration The demand is configured with nciDemPeriod to set the interval over which demand is measured and nciDemSubints to set the number of demand subintervals nciD...

Страница 29: ...onize to the correct time of day allowing multiple WattNodes to stay synchronized even through power failures The WattNode will lose synchronization if nviTimeSet and its internal time differ by the l...

Страница 30: ...there are no timers to delay the alarms and no support for hysteresis in the demand alarms Whenever a demand measurement is made the new value is compared to each of the two alarm levels and if either...

Страница 31: ...erly but has not yet been configured installed by network management software Configured The WattNode is operating properly and has been configured by network management software Internal Error The Wa...

Страница 32: ...screw terminals has not been jumpered with an insulated shorting wire On any unused CT screw terminals connect the white and the black terminals indicated by dots on the label together with a short i...

Страница 33: ...me current rating Ensure that matching CTs are used for all phases The voltage and CT wires may be wired out of phase The best approach is to visually verify that everything is wired correctly but if...

Страница 34: ...the power level of the load being measured is changing significantly then this test may not yield correct results 5 2 3 Test CT Output 1 Since some CTs may produce little or no output below 5 of rated...

Страница 35: ...e of the CT not the rated current Exceeding the maximum allowable current may damage CTs The accuracy of the toroidal CTs is rated as 1 from 10 to 130 of rated current The following toroidal solid cor...

Страница 36: ...of day 6 5 Update Rate The WattNode measures power every 1 678 seconds and energy every 10 066 seconds The demand is measured at the end of each demand interval or subinterval measured to the nearest...

Страница 37: ...uidelines Version 3 0 Echelon Corporation 1996 LONWORKS Custom Node Development LONWORKS Engineering Bulletin Echelon Corporation January 1995 LONWORKS Technology Device Data Q2 95 DL159 D Motorola In...

Страница 38: ...9 status 20 subintervals 28 synchronization 21 29 update rate 36 enabling objects 16 energy measurement 22 configuration 23 disable 20 object 17 22 override 23 status 20 zeroing 16 19 22 23 ESD 14 ext...

Страница 39: ...power outage 17 22 29 rolling demand See demand measurement rolling self documentation 17 service button 16 31 32 service LED 16 31 32 single phase three wire 9 single phase two wire 8 sliding window...

Страница 40: ......

Отзывы: