Operating Instructions

Power and Energy Computation

Every pulse from the meter corresponds to a fixed amount of energy. Power (watts) is energy 
divided by time, which can be measured as pulses per second (or pulses per hour). The following 
scale factor tables and equations convert from pulses to energy (watt-hours or kilowatt-hours) for 
different models. 

If you have ordered a custom full-scale pulse output frequency, then see the 

Power and Energy Equations

 section below. For 

Option PV (Photovoltaic)

, see 

Manual Supplement MS-10: Option PV

 for scale factors.

Scale Factors - Standard Bidirectional Outputs (and Option DPO)

The following table provides scale factors for standard bidirectional output models with a full-
scale pulse output frequency of 4.00 Hz. This table also works for 4.00 Hz models with 

Option 

DPO

. Equations to compute power and energy follow the scale factor tables.

CT Size 

(amps)

Watt-hours per pulse (

WHpP

)

Pulses Per kilowatt-hour (

PpKWH

)

3Y-208 

3D-240

3Y-400 

3D-400

3Y-480 

3D-480

3Y-600

3Y-208 

3D-240

3Y-400 

3D-400

3Y-480 

3D-480

3Y-600

5

0.125

0.2396

0.2885

0.3615

8000.00

4173.91

3465.70

2766.57

15

0.375

0.7188

0.8656

1.0844

2666.67

1391.30

1155.24

922.190

20

0.500

0.9583

1.1542

1.4458

2000.00

1043.48

866.426

691.643

30

0.750

1.4375

1.7313

2.1688

1333.33

695.652

577.617

461.095

50

1.250

2.3958

2.8854

3.6146

800.000

417.391

346.570

276.657

60

1.500

2.8750

3.4625

4.3375

666.667

347.826

288.809

230.548

70

1.750

3.3542

4.0396

5.0604

571.429

298.137

247.550

197.612

100

2.500

4.7917

5.7708

7.2292

400.000

208.696

173.285

138.329

150

3.750

7.1875

8.6563

10.844

266.667

139.130

115.523

92.219

200

5.000

9.5833

11.542

14.458

200.000

104.348

86.643

69.164

250

6.250

11.979

14.427

18.073

160.000

83.478

69.314

55.331

300

7.500

14.375

17.313

21.688

133.333

69.565

57.762

46.110

400

10.000

19.167

23.083

28.917

100.000

52.174

43.321

34.582

600

15.000

28.750

34.625

43.375

66.667

34.783

28.881

23.055

800

20.000

38.333

46.167

57.833

50.000

26.087

21.661

17.291

1000

25.000

47.917

57.708

72.292

40.000

20.870

17.329

13.833

1200

30.000

57.500

69.250

86.750

33.333

17.391

14.440

11.527

1500

37.500

71.875

86.563

108.44

26.667

13.913

11.552

9.2219

2000

50.000

95.833

115.42

144.58

20.000

10.435

8.6643

6.9164

3000

75.000

143.75

173.13

216.88

13.333

6.9565

5.7762

4.6110

any

CtAmps

 

40

CtAmps

 

20.87

CtAmps

 

17.329

CtAmps

 

13.833

40,000 

CtAmps

20,870 

CtAmps

17,329 

CtAmps

13,833 

CtAmps

Table 5: Scale Factors - Bidirectional Outputs

Contact CCS for scale factors for models with full-scale pulse output frequencies other than 4.00 
Hz.

Содержание WattNode Pulse WNB-3D-240-P

Страница 1: ...ce Manual WattNode Pulse Models WNB 3Y 208 P WNB 3Y 400 P WNB 3Y 480 P WNB 3Y 600 P WNB 3D 240 P WNB 3D 400 P WNB 3D 480 P WattNode Revenue Pulse Models RWNB 3Y 208 P RWNB 3Y 400 P RWNB 3Y 480 P RWNB...

Страница 2: ...designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used...

Страница 3: ...unting 14 Selecting Current Transformers 15 Connecting Current Transformers 16 Circuit Protection 17 Connecting Voltage Terminals 18 Connecting Pulse Outputs 18 Output Assignments 19 Pull Up Resistor...

Страница 4: ...y and the PV or wind generated energy See Manual Supplement MS 10 Option PV Photovoltaic for details Options DPO The dual positive outputs option behaves exactly like the standard bidirec tional model...

Страница 5: ...t is not required for safety grounding but ensures maximum meter accuracy C Neutral This terminal N should be connected to neutral when available D E F Line voltage inputs These terminals connect to t...

Страница 6: ...A terminals For delta models this voltage should appear between the A and B terminals V Mains frequencies This indicates the rated mains frequencies for the meter W Maximum rated power This is the ma...

Страница 7: ...36 for CT maximum ratings 6 Ensure that the line voltage input leads to the meter are protected by fuses or circuit breakers not needed for the neutral wire See Circuit Protection p 17 for details 7...

Страница 8: ...B 1 Phase 3 Wire 120V 240V with neutral 96 138 166 276 3Y 208 N and A 3D 240 A and B 3 Phase 3 Wire Delta 208V no neutral n a 166 276 3D 240 A and B 3 Phase 3 Wire Delta 400V no neutral non U S n a 32...

Страница 9: ...E BLACK B CT C CT A CT B C N A Common Input or Positive Monitoring Equip ment or Display P1 P2 P3 COM Output Status Status Status WATTNODE PULSE WNB WNB P P Line Neutral SOURCE LOAD Shorting Jumpers S...

Страница 10: ...t or Positive Monitoring Equip ment or Display P1 P2 P3 COM Output Status Status Status WATTNODE PULSE WNB WNB P P Phase A Neutral Phase B WHITE BLACK 120 Vac 240 Vac 120 Vac SOURCE LOAD Shorting Jump...

Страница 11: ...Monitoring Equip ment or Display P1 P2 P3 COM Output Status Status Status WATTNODE PULSE WNB WNB P P Phase A Phase B WHITE BLACK 208 240 Vac SOURCE LOAD Shorting Jumper Source Faces Current Transform...

Страница 12: ...es Current Transformers 3Y xxx 3D xxx Figure 5 Three Phase Four Wire Wye Connection Recommended WattNode Models The following table shows the WattNode models that should be used depending on the line...

Страница 13: ...1 P2 P3 COM Output Status Status Status WATTNODE PULSE WNB WNB P P Phase A Phase B Phase C WHITE BLACK WHITE BLACK SOURCE LOAD Source Faces Current Transformers 3D xxx Figure 6 Three Phase Three Wire...

Страница 14: ...ter in the mounting position because the drill may damage the connectors and leave drill shavings in the connectors You may mount the meter with the supplied 8 self tapping sheet metal screws using 1...

Страница 15: ...is the value reported by multimeters and the WattNode meter Resistive loads like heaters and incandescent lights have nearly sinusoidal current waveforms with a crest factor near 1 4 Power factor cor...

Страница 16: ...current transformers to the voltage phases being measured Make sure the A CT is installed on the same conductor phase that is connected to A voltage input and the same for phases B and C Use the suppl...

Страница 17: ...nnected equipment because it does not use a conventional power cord that can be easily unplugged Permanently connected equip ment must have overcurrent protection and be installed with a means to disc...

Страница 18: ...e A to N neutral for wye 3Y models or A to B for delta 3D models If the meter is not receiving at least 80 of the nominal line voltage it may stop operating Since the meter consumes a small amount of...

Страница 19: ...el has its own positive output connec tion labeled P1 P2 and P3 tied to the transistor collectors Output Assignments The following table shows the pulse output channel assignments for the standard bid...

Страница 20: ...7k 600 470k 47k 1 0k 620k 47k 2 4k 910k 100k 4 7k 1 3M 50 Hz 10k 600 91k 10k 1 0k 130k 20k 2 4k 200k 47k 4 7k 270k 100 Hz 4 7k 600 47k 4 7k 1 0k 62k 10k 2 4k 100k 20k 4 7k 130k 200 Hz 2 0k 600 24k 2 0...

Страница 21: ...esent but the measured power is below the minimum that the meter will measure see Specifications Measurement Creep Limit the meter will display solid green for that phase Inactive Phase If the meter d...

Страница 22: ...ce of noise Also try to keep the CT wires as short as possible and cut off excess wire Meter Not Operating It should not be possible for all three LEDs to stay off when the meter is powered because th...

Страница 23: ...ould output pulses on P1 so there may be something wrong with the pulse output connection or you may need a pull up resistor see Connecting Pulse Outputs p 18 If the LEDs on one or more phases are fla...

Страница 24: ...mall Most current transformers are only specified to meet their accuracy from 10 to 100 of rated current In practice most CTs work reasonably well down to 1 of rated current Very low currents may not...

Страница 25: ...se frequency is constant and the output is an exact square wave If the power is increasing or decreasing the output waveform will not be a perfect square wave as the on and off periods are getting lon...

Страница 26: ...90 20 0 500 0 9583 1 1542 1 4458 2000 00 1043 48 866 426 691 643 30 0 750 1 4375 1 7313 2 1688 1333 33 695 652 577 617 461 095 50 1 250 2 3958 2 8854 3 6146 800 000 417 391 346 570 276 657 60 1 500 2...

Страница 27: ...285 138 329 400 3 3333 6 3889 7 6944 9 6389 300 000 156 522 129 964 103 746 600 5 0000 9 5833 11 542 14 458 200 000 104 348 86 643 69 164 800 6 6667 12 778 15 389 19 278 150 000 78 261 64 982 51 873...

Страница 28: ...is the current transformer CT rated amps Note If the conductors being measured are passed through the CTs more than once then CtAmps is the rated CT current divided by the number of times that the co...

Страница 29: ...0 02500 0 008333 WNB 3D 400 P 0 04792 0 01597 WNB 3D 480 P 0 05771 0 01924 Table 8 Watt Hours per Pulse per CT Rated Amp For example a WNB 3Y 208 P with a full scale pulse frequency of 4 00 Hz has a W...

Страница 30: ...averaged over different time periods to compute the average power also called demand Note use NVac value from Table 7 above FSHz NVac PpPO CtAmps PulseFreq Power W Maintenance and Repair The WattNode...

Страница 31: ...P1 P2 and P3 Each generates pulses in proportion to the real positive energy measured on one phase phases A B and C respectively Option DPO Dual Positive Outputs This option is like the standard mode...

Страница 32: ...racy The following accuracy specifications do not include errors caused by the current transformer accuracy or phase angle errors Rated current is the current that generates a CT output voltage of 0 3...

Страница 33: ...nce as measured by a DMM 100 to 2000 Approximate OFF Resistance as measured by a DMM 50 M Measurement Creep Limit 0 10 1 1000th of full scale Whenever the real power for a phase drops below the creep...

Страница 34: ...ut Fall Time approximately 2 3 microseconds with a 5 Vdc pull up voltage Option SSR Outputs Isolation 5000 Vac RMS Breakdown Voltage 60 Vdc or 40 Vac can switch positive negative or AC voltages Maximu...

Страница 35: ...66 Vac to 15 of 240 Vac 276 Vac Operating Frequencies 50 60 Hz Measurement Category CAT III Measurement category III is for measurements performed in the building installation Examples are measurement...

Страница 36: ...oor Use Suitable for outdoor use when mounted inside an electrical enclosure Hammond Mfg Type EJ Series that is rated NEMA 3R or 4 IP 66 Mechanical Enclosure High impact ABS and or ABS PC plastic Flam...

Страница 37: ...0 xxx CTS 2000 xxx and CTL 1250 xxx where xxx indicates the full scale current rating CTB wwwXhhh xxx and CTBL wwwXhhh xxx where www and hhh indicate the width and height in inches and xxx indicates t...

Страница 38: ...disclaims and negates all other warranties including without limitation implied warranties of merchantability and fitness for a particular purpose Limitation of Liability In no event shall CCS be liab...

Отзывы: