background image

10

 

Overview

 

 

There are two steps to connecting the current transformers: pass the wire to be measured through the CT 
and connect the CT to the WattNode. Note: always remove power before disconnecting any live wires. 
Split-core CTs may be mounted around a wire by opening one side of the CT, sliding the CT around the 
wire, and then closing the open side of the CT. A split-core CT is opened by pulling the removable section 
straight away from the rest of the CT; this may require a strong pull. To reinstall the removable portion of 
the CT, check that the ends mate correctly by looking at the exposed laminated steel core on the CT body 
and the removable section. When pressing the CT back together, if it seems to jam and will not close, the 
steel core pieces are probably not aligned correctly. Do not force the CT, instead, reposition or rock the 
removable portion until the CT closes without excessive force. After a split-core CT has been placed 
around a wire, a nylon cable tie should be secured around the CT to prevent inadvertent opening. 

The WattNode does not measure negative power and will instead indicate zero power. CTs are directional 
and if mounted backwards or with their wires reversed the power will be negative. In an installation with 
just one CT, the WattNode would output zero power. In a multiple CT installation, if one CT were 
backwards and others were mounted correctly, then the reversed CT would cause the power on that phase 
to be subtracted from the power measured on the other phases, resulting in a plausible, but incorrect 
reading. 

CTs are labeled with either a label which says “THIS SIDE TOWARD SOURCE”, or with an arrow. 
Mount the CT so the label faces or the arrow points towards the current source—typically the circuit 
breaker for the circuit being measured or the utility’s meter box. It is also possible to measure generated 
power by treating the generator as the source. 

Start by removing power from wires being measured. Toroidal CTs require that the wire be disconnected 
before passing it through the opening in the CT. Put the line wires through the CTs as shown in the section 

Measurement Configurations

Next, connect the CTs to the WattNode. The CT inputs to the WattNode are sensitive to ESD (electrostatic 
discharge), so you should ground yourself by touching the service panel case or some other grounded metal 
object before connecting the CTs to the WattNode. Route the twisted black and white wires from the CT to 
the WattNode. Any excess length may be trimmed from the wires if desired. Strip or trim the wires to 
expose 1/4" (6 mm) of bare wire. Do not leave more than 5/16" (8 mm) or less than 3/16" (5 mm) of bare 
wire. The current transformers connect to the black screw terminal block, and it may be easier to install the 
terminal block on the WattNode before connecting the wires from the CTs. Connect each CT, with the 
white wire aligned with the white dot on the label, and the black wire aligned with the black dot. Note the 
order in which the phases are connected, as the voltage phases 

must

 match the current phases for accurate 

power measurement. Any unused CT inputs must be shorted. You may trim short sections off the end of 
the CT wires to use as jumpers. Be careful to leave insulation on the exposed portion of the jumper(s) to 
prevent shock or shorting danger. 

Finally record the CT full-scale current as part of the installation record for each WattNode. If the wires 
being measured are passed through the CT(s) more than once, then the recorded full-scale CT current is 
divided by the number of times that the wire passes through the CT. 

Connecting Voltage Terminals 

Always disconnect power

—by shutting off circuit breaker(s) or removing fuse(s)—before connecting the 

voltage lines to the WattNode.

 The WattNode must be connected to voltage lines which are protected 

by fuses or circuit breakers.

  Connect each voltage phase input to a circuit breaker on the required phase. 

If there is more than one circuit breaker on a phase, then any one of the circuit breakers may be used. 
When installing multiple WattNodes at the same site, it may be easier to provide separate circuit breaker(s) 
for the WattNodes. 

Содержание WattNode Pulse Output

Страница 1: ...WATTNODE Pulse Output Installation and Operation Manual Continental Control Systems http www ccontrolsys com Rev 1 20eUL...

Страница 2: ...w ccontrolsys com WattNode is a registered trademark of Continental Control Systems LLC FCC INFORMATION This equipment has been tested and found to comply with the limits for a Class A digital device...

Страница 3: ...Phase Three Wire Delta 7 Mounting 8 Current Transformers 9 Approved Current Transformers 9 Connecting Current Transformers 9 Connecting Voltage Terminals 10 Connecting Output 11 Installation Summary 1...

Страница 4: ...mum current and greatest accuracy is desired at the normal operating power levels then a CT rated somewhat above the normal operating current may be a better choice Take care that the maximum allowabl...

Страница 5: ...figurations the CT screw terminals will be at line voltage when the WattNode is powered 7 Do not place more than one voltage wire in a screw terminal 8 Remember that the screw terminals are not insula...

Страница 6: ...should be measured with models WNA 1P 240 P or WNA 3Y 208 P If you wish to measure a single phase two wire 220 to 240 VAC circuit use the WNA 3Y 400 P and connect the two wires to the neutral and pha...

Страница 7: ...and neutral and 240 VAC or sometimes 208 VAC between the two line wires Any unused CT inputs must be shorted with an insulated jumper wire Single phase three wire circuits should be measured with mode...

Страница 8: ...ectly Three phase four wire wye circuits should be measured with the WNA 3Y 208 P 208 VAC phase to phase and 120 VAC phase to neutral the WNA 3Y 400 P 400 VAC phase to phase and 230 VAC phase to neutr...

Страница 9: ...wire delta circuits should be measured with the WNA 3D 240 P or the WNA 3D 480 P Phase B LINE Phase C Phase A LOAD Current Transformers WHITE BLACK Source Faces WHITE BLACK Output WNA 3D xxx P Contin...

Страница 10: ...Remove the screw terminals by pulling outward while rocking from end to end The WattNode or Figure 5 may be used as a template to mark mounting hole positions but do not drill the holes with the WattN...

Страница 11: ...060 2749 003 60 0 50 12 70mm CTT 0750 030 3829 003 30 0 75 19 05mm CTT 0750 050 3830 003 50 0 75 19 05mm CTT 0750 070 3831 003 70 0 75 19 05mm CTT 0750 100 2685 003 100 0 75 19 05mm CTT 1000 050 3832...

Страница 12: ...that the wire be disconnected before passing it through the opening in the CT Put the line wires through the CTs as shown in the section Measurement Configurations Next connect the CTs to the WattNod...

Страница 13: ...he WattNode is not receiving at least 80 of the nominal line voltage it may stop measuring power Since the WattNode consumes some power itself a decision must be made about whether to place the CTs be...

Страница 14: ...attNode 2 Turn off power before installing toroidal CTs or making voltage connections 3 Mount the CTs around the line wires being measured Take care to orient the CTs correctly 4 Connect the twisted w...

Страница 15: ...on or the load being measured may not be active If possible verify that at least 5 of the CT s rated current is flowing through the CT Follow PROCEDURE C below to check the CTs The WattNode is not fun...

Страница 16: ...power If the reported power on a pair of screw terminals is zero then also try reversing the CT wires Throughout this test unused CT inputs must be jumpered with a shorting wire between the white and...

Страница 17: ...20 WNA 3Y 400 P 4 000 290 0 or 1160 Hz 3 240 WNA 3Y 480 P 4 000 290 0 or 1160 Hz 3 277 WNA 3Y 600 P 4 000 290 0 or 1160 Hz 3 347 WNA 3D 240 P 2 667 193 3 or 773 3 Hz 2 240 WNA 3D 480 P 2 667 193 3 or...

Страница 18: ...2 500 17 291 20 000 40 000 46 167 80 000 57 833 1000 40 000 20 000 17 329 10 000 13 833 25 000 50 000 57 708 100 00 72 292 1200 33 333 16 667 14 440 8 333 11 527 30 000 60 000 69 250 120 00 86 750 150...

Страница 19: ...0 of full scale power at reduced accuracy which provides extra range for occasional high loads Due to their nonlinearity however the CTs may not produce accurate readings at very low power levels and...

Страница 20: ...m misuse neglect improper application improper installation acts of nature or repairs by anyone other than CCS Except as set forth herein CCS makes no warranties expressed or implied and CCS disclaims...

Отзывы: