38 Specifications
Specifications
Models
Model
Nominal Vac
Line-to-Neutral
Nominal Vac
Line-to-Line
Phases
Wires
WNC-3Y-208-FT10
120
208–240
3
4
WNC-3Y-400-FT10
230
400
3
4
WNC-3Y-480-FT10
277
480
3
4
WNC-3Y-600-FT10
347
600
3
4
WNC-3D-240-FT10
120*
208–240
3
3–4
WNC-3D-400-FT10
230*
400
3
3–4
WNC-3D-480-FT10
277*
480
3
3–4
*Note: the delta models have an optional neutral connection that may be used for measuring
wye circuits. In the absence of neutral, voltages are measured with respect to ground. Delta
WattNode models use the phase A and phase B connections for power.
Table 6: WattNode Models
Model Options
WattNode for LonWorks models are available with the following options. See the CCS website
WattNode Plus for Lonworks - Options
page for details.
Option CT=xxx
:
Pre-assign
xxx
as the global
CtAmps
value of the attached current
transformers.
Option PT or Option PT=xxx
:
Improves support for potential transformers (PTs), by adding a
configuration property
UCPTptRatio
which configures the ratio of the external PT. Optionally
pre-assign
xxx
as the PT ratio.
Option B
:
Emulates the WNB series WattNode Plus for LonWorks models.
Note:
this option is
not available on WattNode Logger models.
Option BI
:
Emulates the WNB series WattNode Plus for LonWorks models with integer outputs.
Note:
this option is not available on WattNode Logger models.
Firmware
Firmware Version:
3.37
XIF file:
WNC-FT-Plus-337.XIF
L
on
W
orks
Program ID:
8:00022:1500:0A:04:07
L
on
M
ark
Certification Version:
3.4
With Option PT
Firmware Version:
3.40
XIF file:
WNC-FT-Plus-PT-340.XIF
L
on
W
orks
Program ID:
9:00022:1500:0A:04:0C
L
on
M
ark
Certification Version:
not certified
Accuracy
The following accuracy specifications do not include errors caused by the current transformer
accuracy or phase angle errors. “Rated current” is the current that generates a CT output voltage
of 0.33333 Vac.