background image

SM82

A

Switchmode Range of Battery Chargers

Connections & Controls

How to Use

Table (B) -Typical charging characteristics

Ensure correct AC Input Voltage input is selected on the charger (9)
If using the 6/12V switchable model, ensure the 6/12V Voltage Selector (8) is configured correctly, (ON for 12V, OFF for 6V)
Connect AC supply to terminals (2) observing connection details, and plug into the mains, switch the mains on and check the battery charged (float) LED (4) 
illuminates (if connected), then switch off at mains.
Ensure that the battery pack is either Vented or VRLA (sealed) rechargeable lead acid only. Confirm the correct charging stage to be used from Table (A) on 
page 1 and connect mode selector jumper (7) to suit as described above.

Connect the +Ve and -Ve terminals (4) to battery/battery pack

IMPORTANT:  CHECK  POLARITY  OF  BATTERY 
CONNECTIONS  REVERSE  POLARITY  WILL  DAMAGE 
BATTERIES

In Auto-3 Stage Mode of Operation (with LED’s Connected):
Switch  on  at  mains,  ‘Boost’  LED  (4)  should  now  be 
illuminated. When the battery pack is fully charged the ‘Float’ 
LED (4) should be illuminated and the ‘Boost’  LED (4) should 
switch off. Once fully charged the battery packs will receive a 
float charge at specified voltage on Page 1, keeping batteries 
in prime condition ready for use.
Before disconnecting the battery pack from charger, switch of 
at  mains,  disconnect  battery  pack  and  then  disconnect 
charging leads from charger.
In Float Mode of Operation:
As  above,  only  the  Float  LED  (4)  will  be  permanently 
illuminated.

Notes:

  If  no AC  is  present  and  the  unit  is  connected  to  a 

battery, then the C/F LED (2) will be illuminated. The SM82A  
charger draws 20mA from battery(s) when connected with no 
AC present. With AC present and no battery/load connected 
the Float LED (2) will also be illuminated. All the LED outputs 
are  configured  for  2.5VDC  LED’s,  no  voltage  drop  down 
resistor is required.
When  using  the  charger  in  the Auto  3  Stage  mode,  either 
neither of LED’s should be connected or both the Float and 
Boost  LED’s  must  be  connected  for  them  to  function 
correctly, if only 1 of the LED’s are connected they will not 
function correctly.

ENSURE  CONNECTION  OF  LED’S  IS  CORRECT 
BEFORE  SWITCHING  ON  UNIT  -  INCORRECT 
CONNECTION  MAY  DAMAGE  THE  CHARGERS  LED 
OUTPUT CONTROLLER

Charge Fail / Loss of AC 

Supply Relay Output

(1)

Note: 

The  SM82A  may  be  fitted  with  an  on-board  LED 

(marked LED1), this is an internal LED to indicate charger 
control  circuit  is  operational  and  used  for  internal  test 
purposes only. Not all units have this device fitted. 

LED1

(See notes right)

Notes on Charging mode selector and boost operation:

With both the charging stage mode selector jumpers fitted 
uppermost (M) on (7), the unit will function in the float mode, 
providing  a  constant  voltage  output  (at  specified  level  as 
shown  on  page  1),  an  increased  ‘boost’  voltage  can  be 
manually triggered by linking the Boost Terminals (4). Fitting 
both jumpers towards (A) on (7)  will put the charger in Auto-
3 Stage mode.
Note: Care should be taken when using the manual boost 
mode  so  overcharge  does  not  take  place,  the  boost  link 
should be timed or monitored until battery voltage reaches 
required level. 

WARNING! Continuous boost charging will damage the 
batteries

Factory default units are shipped with Jumper (7) fitted 
in M position for Float mode, Jumper (8) fitted for 12V 
setting  (on  6/12V  units)  and  Jumper  (9)  selected  for 
240VAC.

BAT

TER

Y VO

LTA

GE

CHARGING CURRENT

AS CHARGER SWITCHES

FROM BOOST TO FLOAT

THE BATTERY NEEDS A

SMALL PERIOD OF TIME

TO SETTLE. DURING THIS

PHASE NO CURRENT WILL

FLOW FROM CHARGER.

FLOAT CURRENT

AT BATTERIES

KNEE POINT CURRENT

STARTS TO FALL

VOL

TAGE / CURRENT

FLOAT STAGE

BOOST STAGE

Auto 3 Stage Mode

CONSTANT CURRENT

(CURRENT LIMITED)

BA

TTER

VOL

TA

G

E

CONSTANT VOLTAGE

(FLOAT STAGE)

CHARGING CURRENT

FLOAT CURRENT

AT BATTERIES

KNEE POINT CURRENT

STARTS TO FALL

TIME

VOL

TAGE / CURRENT

Float Mode

(80% CHARGED)

Отзывы: