CBS ArcSafe RSK-AK11 Скачать руководство пользователя страница 3

877-4-SAFETY

 | 

Fax: 940-382-9435

CBS

Safe

®

A Group CBS Company

Arc

2.0 Safety Information 

ALWAYS connect the control cable to the actuator 
BEFORE installing the Chicken Switch®. 

2.1 Finger pinch points

Keep fingers clear of the bottom of the actuator 
when the actuator is near a ferrous surface. 

2.2 Strong magnets

The holding magnets are very strong.  Keep magnetically-
sensitive objects such as watches or computer 
disks away from the bottom of the actuator.

3.0 Battery Requirements

•  Eight (8) AA alkaline cells are required. Carefully observe 

polarity when installing cells.

•  Rechargeable batteries are not recommended.

3.1 Battery Life

•  A set of fresh alkaline cells should give hundreds of 

operations.

•  The Chicken Switch® is designed as a portable device.  

It is not designed to remain with the control unit 
connected to the actuator for extended periods of 
time.  To do so will deplete a fresh set of batteries in 
approximately four to five days.

3.2 Battery Replacement

•  ALWAYS disconnect the control cable before replacing 

batteries to avoid possible static damage of the 
electronics!

•  Turn the control station upside down, remove the 

endplate retaining knob.  Remove the endplate and 
slide the cover out as shown below.

3.3 To connect/disconnect batteries: 

3.4 CAUTION: Static Discharge Potential

•  To avoid possible damage to electronic components 

disconnect the control cable before replacing batteries.

4.0 Operation 

ALWAYS connect the control cable to the actuator 
BEFORE installing the Chicken Switch®.

4.1 Connecting the control cable

1. Align the arrow on the cable end with the top of the  

receptacle.

2. Push in and engage the threads on the coupling nut and  

turn clockwise.

3. After one or two turns of the coupling nut, push in on the 

cable end. Repeat this until the connector is fully seated.

4. Use a similar technique of turn-stop-and-pull to 

disengage the cable ends.

TO AVOID POSSIBLE 

DAMAGE TO ELECTRONIC 

COMPONENTS DISCONNECT 

CONTROL CABLE BEFORE 

REPLACING BATTERIES.

WARNING

Содержание RSK-AK11

Страница 1: ...FLASH DANGER CBS Safe A Group CBS Company Arc CBSArcSafe com Email info CBSArcSafe com 877 4 SAFETY Fax 940 382 9435 WE DO RSK AK11 A Portable Actuator for Remotely Operating Selected GE AK Breakers...

Страница 2: ...are well documented Studies conducted by numerous industries and professional organizations have sought to quantify the intensity of arc blast the risks to personnel and various methodologies for miti...

Страница 3: ...set of batteries in approximately four to five days 3 2 Battery Replacement ALWAYS disconnect the control cable before replacing batteries to avoid possible static damage of the electronics Turn the...

Страница 4: ...d the button 7 Release the ENABLE and TRIP or CLOSE buttons and the actuator will retract 4 3 Attaching and Removing the Actuator Step 1 Before installing the actuator verify that the plungers are ful...

Страница 5: ...o operate the breaker with the RSK AK11 Step 6 Actuator is installed and ready to use STEPS TO REMOVE THE ACTUATOR To remove the actuator perform the above steps in the reverse order Step1 Rotate the...

Страница 6: ...OFF buttons both actuators will move to the retracted position NOTE If either of the actuators are held in the extended position for longer than approximately 2 seconds the actuator will de energize a...

Страница 7: ...airs and incompetent supervision This warranty also does not cover repairs or replacements made by unauthorized individuals except when agreed to in writing CBS ArcSafe reserves the right to disallow...