RSA-80A Installation and Operation 

 

Page | 3

  

 

Step 3

: Install the RSA-80A on the breaker by resting the black delrin portion of the handle 

adapter on the CLOSE/TRIP handle of the breaker and position the RSA so that the magnets are 

sitting flush against the surface of the door.  See image below for details. 

 

 

 
Step 4

: Next, secure the RSA-80A into place by rotating the handles of each of the two twist-

lock magnets 180° clockwise. 

 
Step 5

: When installed, make sure that both magnets are sitting flush with the door and that 

the RSA-80A is sitting level with respect to the horizontal plane.  A small bubble level on the 
backside of the RSA device will show whether or not the RSA is level.  If it is not, release both 
magnets, adjust the position of the RSA as necessary, and then re-engage both magnets to lock 
the RSA into its current position. 
 

Step 6

: The RSA-80A is now properly installed and ready for operation; see Section 2 for 

operation instructions.  The following section will address any adjustments that may be 
necessary for users in the field. 

 

 

Содержание RSA-80A

Страница 1: ...CBS ArcSafe RSA 80A For Westinghouse DB 25 CBS ArcSafe Inc 2616 Sirius Road Denton TX 76208 940 382 4411 www cbsarcsafe com Installation and Operation...

Страница 2: ...uctions around the switch that will interfere with RSA installation as shown below ATTENTION The location of certain items such as mimic bus stickers and or placards may interfere with the installatio...

Страница 3: ...ise Step 5 When installed make sure that both magnets are sitting flush with the door and that the RSA 80A is sitting level with respect to the horizontal plane A small bubble level on the backside of...

Страница 4: ...lowing image which shows travel stop adjustments Step 2 Another adjustment which may need to be made is the location of the RSA 80A motor assembly Adjusting the motor assembly may be necessary in the...

Страница 5: ...ep 3 The height of the RSA 80A motor assembly may also be adjusted to account for varying depths of doors or breaker CLOSE TRIP switches See the following image for details This procedure will have to...

Страница 6: ...be performed Either Close or Trip Step 5 Turn the power switch on the RSO IIID to the ON position and input the settings based on the placard on the RSA 80A based on the corresponding operation to be...

Страница 7: ...RSA 80A Installation and Operation Page 7...

Страница 8: ...they are correctly stationed outside the arc flash boundary and that they comply with all applicable Federal State Local and In house safety regulations and procedures Attention should be given to dis...

Отзывы: