CCM12 CANbus
User Manual
17
9M02-7717-A001-EN
Version 3.0
Table 8: CANopen Node ID selection table
SW3
POSITION
SW2
POSITION
NODE ID,
CROSS-MONITORED
OPERATION
NODE ID,
PARALLEL OPERATION
MASTER
CONTROLLER
SLAVE CONTROLLER
0
0
Invalid
– Do not use
Invalid
– Do not use
0
1
01h
01h
02h
0
2
02h
02h
03h
…
…
…
…
..
7
D
7Dh
7Dh
7Eh
7
E
7Eh
7Eh
7Fh
7
F
7Fh
Invalid
– Do not use
8-F
X
Invalid
– Do not use
Invalid
– Do not use
If SW1, SW2 or SW3 are set to an invalid position, the CCM12 goes to Error mode at start-up (with the 14 flashes
code).
3.3.4 LEDs
The MCU CAN1 and CAN2 LEDs are bicolor (Green and Red), operating according
to CiA DR303-3
, “CANopen
Indicator S
pecification”. CAN1 is associated with the master controller and CAN2 with the slave controller.
The behavior of the Green and Red components is independent. Green behavior indicates the RUN state, and
Red behavior the ERROR state. In the case of conflict between turning the LED Green or Red, Red has priority.
Table 9: CAN LED Green component behavior (CANopen operation)
GREEN (RUN) BEHAVIOR
MEANING
Blinking
(200 ms ON, 200 ms OFF)
The MCU is in PRE-OPERATION state
Single flash
(200 ms ON, 1 s OFF)
The MCU is in STOPPED state
On
The MCU is in OPERATIONAL state
Table 10: CAN LED Red component behavior (CANopen operation)
RED (ERROR) BEHAVIOR
MEANING
OFF
No error
Single flash
(200 ms ON, 1 s OFF)
A warning limit has been reached (too many error frames)
ON
Bus off condition