The Delay parameter present in the paragraph
SERIAL COMMUNICATION
SETTING
allows for a further delay in the instrument response, and this directly influences
the number of possible queries in the unit of time.
For additional information on this protocol, refer to the general technical specification
PI_MBUS_300.
In
general
, the query and response to and from a slave instrument are organised as follows:
FUNCTION 3: Read holding registers
(PROGRAMMABLE REGISTER READING)
QUERY
Address
Funcion
Add. Register1
No. register
2 bytes
A 0x03
0x0000
0x0002
CRC
Tot. bytes = 8
RESPONSE
Address
Funcion
No.bytes
Register1
Register2
2 bytes
A 0x03
0x04
0x0064
0x00C8
CRC
Tot. bytes = 3 + 2*No. r2
where: No. registers= number of Modbus register to be read, starting from the Address
1° register;
No. bytes = number of data bytes to follow;
FUNCTION 16: Preset multiple registers (MULTIPLE REGISTER WRITING)
QUERY
Addr
Func
Add.
Reg.1
No.reg.
No.
bytes
Val.
Reg. 1
Val.
Reg. 2
2 bytes
A 0x10
0x0000
0x0002
0x4 0x0000
0x0000
CRC
Tot. bytes = 7 + 2*No. r2
RESPONSE
Address
Funcion
Add.Reg.1
No.reg.
2 bytes
A 0x10
0x0000
0x0002
CRC
Tot. bytes = 8
81
Содержание CI-600D Series
Страница 1: ...2 ...
Страница 11: ...2 Specifications in Appearance 2 1 External Dimension CI 601D CI 605D 2 2 Front Panel Descriptions 12 ...
Страница 36: ...5 2 How to Seal the Indicator Sealing 37 ...
Страница 50: ...51 ...
Страница 51: ...52 ...
Страница 86: ...MEMO 87 ...
Страница 87: ...MEMO 88 ...
Страница 88: ...MEMO 89 ...
Страница 89: ...MEMO 90 ...
Страница 90: ...91 ...