Sequence of Operation
WSHP Open v3
CARRIER CORPORATION ©2021
Integration Guide
All rights reserved
27
During
Heating
, the reversing valve output is held in the heating position (either B or O-type, as configured), even
after the compressor is stopped. The valve does not switch position until the cooling mode is required.
The configuration screens contain the
Max SAT
parameter as well as heating lockout based on outdoor air
temperature (OAT). Both can be adjusted to meet various specifications.
There is a 5-minute off-time for the compressor, as well as a 5-minute time delay, when staging up to allow the
SAT to achieve a stable temperature before energizing a second stage of capacity. Likewise, a 45 second delay is
used when staging down.
After a compressor is staged off, it may be restarted again after a normal time-guard period of 5 minutes and if
the supply air temperature has fallen below the maximum supply air temperature limit.
The WSHP Open provides a status input to monitor the compressor operation. The status is monitored to
determine if the compressor status matches the commanded state. This input is used to determine if a refrigerant
safety switch or other safety device has tripped and caused the compressor to stop operating normally. If this
occurs, an alarm is generated to indicate the faulted compressor condition. Also, if auxiliary heat is available (see
below), the auxiliary heat replaces the reverse cycle heating and maintains the space temperature as required.
Auxiliary heat
The WSHP Open can control a 2-position, or modulating water, or steam valve, connected to a coil on the
discharge side of the unit and supplied by a boiler, or a single stage ducted electric heater, in order to maintain
the desired heating setpoint. If
Aux Heat Control
is configured for
Boilerless
control operation, the aux heat only
operates if a compressor failure occurs or the source water temperature is insufficient for reverse cycle heating. If
Aux Heat Control
is configured for
Auxiliary Heat
, in addition to the above, it also operates to supplement the heat
provided by the compressor, if the space temperature falls more than 1°F below the desired heating setpoint.
(This amount is configurable.) The heat is controlled so the SAT does not exceed the
Maximum Heating SAT
limit.
The same conditions required for
Reverse Cycle Heating
must be true in order for the
Auxiliary Heat
algorithm to
run.
Auxiliary Modulating Hot Water / Steam Heating Reheat -
The control can modulate a hot water or steam valve
connected to a coil on the discharge side of the unit, and supplied by a boiler in order to maintain the desired
heating setpoint, if the compressor capacity is insufficient, or a compressor failure occurs. Unless a compressor
fault condition exists, the valve only operates to supplement the heat provided by the compressor if the space
temperature falls more than 1°F below the desired heating setpoint. The valve is controlled so the SAT does not
exceed the
Maximum Heating SAT
limit.
2- Position Hot Water / Steam Heating Reheat -
The control can operate a 2-position, NO or NC, hot water or
steam valve, connected to a coil on the discharge side of the unit and supplied by a boiler, in order to maintain the
desired heating setpoint, if the compressor capacity is insufficient or a compressor failure occurs. Unless a
compressor fault condition exists, the valve only opens to supplement the heat provided by the compressor, if the
space temperature falls more than 1°F below the desired heating setpoint. The valve is controlled so the SAT
does not exceed the
Maximum Heating SAT
limit and is subject to a 2 minute minimum OFF-time to prevent
excessive valve cycling.
Single Stage Electric Auxiliary Heat
–
The control can operate a field-installed single stage of electric heat that is
installed on the discharge side of the unit, in order to maintain the desired heating setpoint, if the compressor
capacity is insufficient or a compressor failure occurs. Unless a compressor fault condition exists, the heat stage
only operates to supplement the heat provided by the compressor if the space temperature falls more than 1°F
below the desired heating setpoint. The heat stage is controlled so the SAT does not exceed the
Maximum
Heating SAT
limit and is subject to a 2-minute minimum OFF-time to prevent excessive cycling.