Sequence of Operation
WSHP Open v3
CARRIER CORPORATION ©2021
Integration Guide
All rights reserved
23
The multi-protocol WSHP Open controls mechanical cooling, heating, and waterside economizer outputs, based on
its own space temperature input and setpoints. An optional CO
2
IAQ (Indoor Air Quality) sensor that is mounted in
the space maximizes the occupant's comfort. The WSHP Open has its own hardware clock that is automatically set
when you download the heat pump software to the board.
See
Scheduling
(page 23) for occupancy types.
The following sections describe the multi-protocol controller's functions. All point objects mentioned in this
sequence of operation reference the touchscreen interface. Points in Field Assistant and the i-Vu® application are
the same or similar.
Scheduling
Scheduling
- You must configure time periods to schedule the transitions from occupied to unoccupied operation.
The time periods control the space temperature to occupied heating and cooling setpoints. The WSHP Open
operates continuously in the
Occupied
mode until you configure either a time schedule or a third party control
system
Enables/Disables
the
BAS On/Off
point. You must set your local time and date for these functions to
operate properly.
You can change the occupancy source to one of the following:
Occupancy Schedules
- The controller is occupied 24/7 until you configure a time schedule using either the
Equipment Touch, Field Assistant, the i-Vu® application, or a third party
Enables/Disables
the
BAS On/Off
point.
You can disable this by going to
Configuration
>
Unit Configuration
>
Occupancy Schedules
, changing the point
from
Enable
to
Disable
and clicking
OK
.
NOTE
You must
Enable
this point in order for the Equipment Touch, Field Assistant, or the i-Vu® application to
assign a time schedule to the controller.
Schedule_Schedule
- The unit operates according to the schedule configured and stored in the unit. The schedule
is accessible via the Equipment Touch, the i-Vu® application, or Field Assistant. The daily schedule consists of a
start and stop time (standard or 24-hour mode) and 7 days of the week, starting with Monday and ending on
Sunday.
CAUTION
Scheduling can only be controlled from one source.
Occupancy Input Contact (Option)
- If configured for remote occupancy control (default), the WSHP Open can use
an external dry contact closure to determine the occupancy status of the unit. You must disable the
Occupancy
Schedules
in order to use the occupancy contact input. The unit enters an occupied mode when it senses the
abnormal input. After the input returns to its normal state, the unit stays in the occupied mode for the configured
Occ Override Delay
period (15 minutes default).
BAS (Building Automation System) On/Off
- For use with a Building Automation System that supports network
scheduling, you must disable the
Occupancy Schedules
so the BAS system can control the unit through a network
communication and the BAS scheduling function.
Global Occupancy Scheduling
- The WSHP Open can read the occupancy status from another unit so that a group
of WSHP's can be controlled from a single occupancy schedule. The local
Occupancy Schedules
must be disabled
in order to use the global occupancy input.
BACnet Network Occupancy Input
- The WSHP Open can accept an external BACnet Binary Network Input for
occupancy control. This function is only compatible with units used in BACnet systems. You need to configure the
System Occupancy BACnet network input point to locate the device and point name where the external occupancy
point information resides. You must also disable
Occupancy Schedules
in order to use this input.
Sequence of Operation
Содержание WSHP Open v3
Страница 6: ...Introduction WSHP Open v3 CARRIER CORPORATION 2021 Integration Guide All rights reserved 2 ...
Страница 56: ......
Страница 57: ......
Страница 58: ...CARRIER CORPORATION 2021 Catalog No 11 808 539 01 6 15 2021 ...