49
* For single enthalpy control, the module compares outdoor enthalpy to
the ABCD set point.
† Power at N terminal determines Occupied/Unoccupied setting: 24 vac
(Occupied), no power (Unoccupied).
** Modulation is based on the supply-air sensor signal.
†† Modulation is based on the DCV signal.
*** Modulation is based on the greater of DCV and supply-air sensor
signals, between minimum position and either maximum position
(DCV) or fully open (supply-air signal).
††† Modulation is based on the greater of DCV and supply-air sensor
signals, between closed and either maximum position (DCV) or
fully open (supply-air signal).
Fig. 61 — EconoMi$er IV Functional View
EconoMi$er IV Standard Sensors
Table 20 provides a summary of EconoMi$er IV. Trouble-
shooting instructions are enclosed. A functional view of the
EconoMi$er is shown in Fig. 61. Typical settings, sensor rang-
es, and jumper positions are also shown. An EconoMi$er IV
simulator program is available from Carrier to help with
EconoMi$er IV training and troubleshooting.
OUTDOOR AIR TEMPERATURE (OAT) SENSOR
The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoor-air temperature.
The outdoor-air temperature is used to determine when the
EconoMi$er IV can be used for free cooling. The sensor is fac-
tory-installed on the EconoMi$er IV in the outdoor airstream.
(See Fig. 62.) The operating range of temperature measure-
ment is 40°F to 100°F (4°C to 38°C). See Fig. 63.
SUPPLY AIR TEMPERATURE (SAT) SENSOR
The supply air temperature sensor is a 3 K thermistor located at
the inlet of the indoor fan. (See Fig. 62.) This sensor is factory
installed. The operating range of temperature measurement is
0°F to 158°F (–18°C to 70°C).
The temperature sensor looks like an eyelet terminal with wires
running to it. The sensor is located in the “crimp end” and is
sealed from moisture.
Table 20 — EconoMi$er IV Input/Output Logic
INPUTS
OUTPUTS
Demand
Controlled
Ventilation (DCV)
Enthalpy*
Y1 Y2
Compressor
N Terminal†
Outdoor
Return
Stage 1 Stage 2
Occupied
Unoccupied
Damper
Below set
(DCV LED off)
High (Free
Cooling LED off)
Low
On On
On
On
Minimum position
Closed
On Off
On
Off
Off Off
Off
Off
Low (Free
Cooling LED on)
High
On On
On
Off
Modulating** (between min.
position and full-open)
Modulating** (between closed
and full-open)
On Off
Off
Off
Off Off
Off
Off
Minimum position
Closed
Above set
(DCV LED on)
High (Free
Cooling LED off)
Low
On On
On
On
Modulating†† (between min.
position and DCV maximum)
Modulating†† (between closed
and DCV maximum)
On Off
On
Off
Off Off
Off
Off
Low (Free
Cooling LED on)
High
On On
On
Off
Modulating***
Modulating†††
On Off
Off
Off
Off Off
Off
Off
Содержание WeatherMaster Puron 48HC D17
Страница 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Страница 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Страница 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Страница 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Страница 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Страница 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Страница 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Страница 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Страница 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Страница 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Страница 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Страница 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Страница 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Страница 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Страница 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Страница 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Страница 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Страница 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Страница 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Страница 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Страница 97: ......