Fig. 65 −
PC Running Field Assistant
Table 14 – LEDs
The LEDs on the RTU Open Controller show the status of certain functions
If this LED is on...
Status is...
Power
The RTU Open controller has power
Rx
The RTU Open controller is receiving data from the network segment
Tx
The RTU Open controller is transmitting data over the network segment
BO#
The binary output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
Off
Normal
2 flashes per second
2 flashes, alternating with
Run
LED
Five minute auto-restart delay after system error
2 flashes per second
3 flashes, then off
Control module has just been formatted
2 flashes per second
4 flashes, then pause
Two or more devices on this network have the
same MSTP network address
2 flashes per second
On
Exec halted after frequent system errors or
control programs halted
5 flashes per second
On
Exec start-up aborted, Boot is running
5 flashes per second
Off
Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second, alternating
with
Run
LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second,
alternating with
Run
LED
Brownout
On
On
Failure. Try the following solutions:
S
Turn the RTU Open controller off, then on.
S
Format the RTU Open controller.
S
Download memory to the RTU Open controller.
S
Replace the RTU Open controller.
NOTE: Refer to the RTU Open Multi−Protocol Controller
Controls, Start−Up, Operation and Troubleshooting manual
for complete configuration of the RTU Open controller
operating sequences and troubleshooting information. Refer
to the RTU Open v3 Integration Guide for details on
configuration and troubleshooting of connected networks.
Have a copy of these manuals available at unit start−up.
50HCQ
Содержание WeatherMaster 50HCQ
Страница 4: ...4 C160133 Fig 2 Unit Dimensional Drawing 07 08 Size Units 50HCQ...
Страница 5: ...5 C160134 Fig 2 Unit Dimensional Drawing 07 08 Size Unit cont 50HCQ...
Страница 6: ...6 C10588 Fig 3 Unit Dimensional Drawing 09 Size Units 50HCQ...
Страница 7: ...7 C10589 Fig 3 Unit Dimensional Drawing 09 Size Unit cont 50HCQ...
Страница 26: ...26 C160124 Fig 39 Typical PremierLinkt Control Wiring Diagram 50HCQ...
Страница 35: ...35 C160125 Fig 56 Typical RTU Open Controller Wiring Diagram 50HCQ...
Страница 53: ...53 50HCQ...