For damper minimum position settings and checkout menu
readings, see Table 9.
Table 9 — Damper Minimum Position Settings and Readings on Checkout Menu
SEQUENCE OF OPERATION
See Tables 10-17 for dry bulb and enthalpy sequence of
operation.
Table 10 — Dry Bulb Operation, No Demand Controlled Ventilation (DCV) (CO
2
Sensor) — 1 Speed Fan
*With stage 3 delay (STG3 DLY) in Advanced setup menu, second
stage of mechanical cooling Y2-O can be turned on after the delay if
the calls for Y1-I and Y2-I have not been satisfied.
Table 11 — Dry Bulb Operation, With Demand Controlled Ventilation (DCV) (CO
2
Sensor) — 1 Speed Fan
*With stage 3 delay (STG3 DLY) in Advanced setup menu, second
stage of mechanical cooling Y2-O can be turned on after the delay if
the calls for Y1-I and Y2-I have not been satisfied.
FAN SPEED
DEMAND CONTROLLED VENTILATION
(CO
2
SENSOR)
SETPOINTS
CHECKOUT
1
NO
MIN POS
VMAX – HS
1
NO
N/A
N/A
2
NO
MIN POS H
VMAX – HS
2
NO
MIN POS L
VMAX – LS
1
YES
VENT MIN
VMIN – HS
1
YES
VENT MAX
VMAX – HS
2
YES
VENT MIN H
VMIN – HS
2
YES
VENT MAX H
VMAX – LS
2
YES
VENT MIN L
N/A
2
YES
VENT MAX L
N/A
DCV
OUTSIDE AIR
GOOD TO
ECONOMIZE?
Y1-I
Y2-I
FAN SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
None
No
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
24-v/On
0-v/Off
MIN POS
Closed
On
On
High
24-v/On
24-v/On
MIN POS
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
0-v/Off
0-v/Off
MIN POS to Full-Open
Closed to Full-Open
On
On
High
24-v/On
24-v/Off*
MIN POS to Full-Open
Closed to Full-Open
DCV
OUTSIDE AIR
GOOD TO
ECONOMIZE?
Y1-I
Y2-I
FAN SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
Below
CO
2
Set
No
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN
Closed
On
On
High
24-v/On
24-v/On
VENTMIN
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to Full-Open Closed to Full-Open
On
On
High
24-v/On
0-v/Off*
VENTMIN to Full-Open Closed to Full-Open
Above
CO
2
Set
No
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to VENTMAX Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN to VENTMAX Closed
On
On
High
24-v/On
24-v/On
VENTMIN to VENTMAX Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to VENTMAX Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to Full-Open Closed to Full-Open
On
On
High
24-v/On
0-v/Off*
VENTMIN to Full-Open Closed to Full-Open
Содержание WeatherMaster 50HC*A07 Series
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 07 09 ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Страница 25: ...25 Fig 42 Electro Mechanical Control Wiring Diagram ...
Страница 26: ...26 Fig 43 Electro Mechanical Control Wiring Diagram with Humidi MiZer System ...
Страница 27: ...27 Fig 44 Typical ComfortLink Control Wiring Diagram 50HC 08 09 shown ...
Страница 29: ...29 Fig 46 Typical PremierLink Control Wiring Diagram ...
Страница 30: ...30 Fig 47 Typical PremierLink Control Wiring Diagram with Humidi MiZer System Option ...
Страница 31: ...31 Fig 48 Typical RTU Open Controller Wiring Diagram ...
Страница 32: ...32 Fig 49 Typical RTU Open Controller Wiring Diagram with Humidi MiZer System Option ...