117
Slow Change Cap Override (SLOW)
With a rooftop unit, the design rise at 100% total unit capacity is
generally around 30
F. For a unit with 4 stages, each stage rep-
resents about 7.5
F of change to EDT. If stages could reliably be
cycled at very fast rates, the set point could be maintained very
precisely. Since it is not desirable to cycle compressors more
than 6 cycles per hour, slow change override takes care of keep-
ing the PID under control when “relatively” close to set point.
VFD INFORMATION DISPLAY TABLE
The VFD information display table provides information on
the supply fan VFD and exhaust fan VFD. See Table 98.
MODE TRIP HELPER
The Mode Trip Helper table provides information on the unit
modes and when the modes start and stop. See Table 99. This
information can be used to help determine why the unit is in
the current mode.
CCN/LINKAGE DISPLAY TABLE
The CCN/Linkage display table provides information on unit
linkage. See Table 100.
COMPRESSOR RUN HOURS DISPLAY TABLE
The Compressor Run Hours Display Table displays the number
of run time hours for each compressor. See Table 101.
COMPRESSOR STARTS DISPLAY TABLE
The Compressor Starts Display Table displays the number of
starts for each compressor. See Table 102.
SOFTWARE VERSION NUMBERS DISPLAY TABLE
The Software Version Numbers Display Table displays the
software version numbers of the unit boards and devices. See
Table 103.
Table 98 — VFD Information Display Table
Table 99 — Mode Trip Helper Display Table
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
VFDS
VFD INFORMATION
S.VFD
SUPPLY FAN VFD (VFD 1)
SPD
VFD1 Actual Speed %
VFD1_SPD
RPM
VFD1 Actual Motor RPM
VFD1RPM
FREQ
VFD1 Actual Motor Freq
VFD1FREQ
AMPS
VFD1 Actual Motor Amps
VFD1AMPS
TORQ
VFD1 Actual Motor Torque
VFD1TORQ
PWR
VFD1 Actual Motor Power
VFD1PWR
VDC
VFD1 DC Bus Voltage
VFD1VDC
V.OUT
VFD1 Output Voltage
VFD1VOUT
TEMP
VFD1 Transistor Temp (C)
VFD1TEMP
RUN.T
VFD1 Cumulative Run Time
VFD1RUNT
KWH
VFD1 Cumulative kWh
VFD1KWH
LFC
VFD1 Last Fault Code
VFD1LFC
E.VFD
EXHAUST FAN VFD (VFD 2)
SPD
VFD2 Actual Speed %
VFD2_SPD
RPM
VFD2 Actual Motor RPM
VFD2RPM
FREQ
VFD2 Actual Motor Freq
VFD2FREQ
AMPS
VFD2 Actual Motor Amps
VFD2AMPS
TORQ
VFD2 Actual Motor Torque
VFD2TORQ
PWR
VFD2 Actual Motor Power
VFD2PWR
VDC
VFD2 DC Bus Voltage
VFD2VDC
V.OUT
VFD2 Output Voltage
VFD2VOUT
TEMP
VFD2 Transistor Temp (C)
VFD2TEMP
RUN.T
VFD2 Cumulative Run Time
VFD2RUNT
KWH
VFD2 Cumulative kWh
VFD2KWH
LFC
VFD2 Last Fault Code
VFD2LFC
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
TRIP
MODE TRIP HELPER
UN.C.S
Unoccup. Cool Mode Start
UCCLSTRT
UN.C.E
Unoccup. Cool Mode End
UCCL_END
OC.C.S
Occupied Cool Mode Start
OCCLSTRT
OC.C.E
Occupied Cool Mode End
OCCL_END
TEMP
Ctl.Temp RAT,SPT or Zone
CTRLTEMP
OC.H.E
Occupied Heat Mode End
OCHT_END
OC.H.S
Occupied Heat Mode Start
OCHTSTRT
UN.H.E
Unoccup. Heat Mode End
UCHT_END
UN.H.S
Unoccup. Heat Mode Start
UCHTSTRT
HVAC
ascii string spelling out the hvac modes
string
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...