SINGLE POINT BOXES AND SUPPLEMENTARY FUSES
When the unit MOCP device value exceeds 60-A, unit-mount-
ed supplementary fuses are required for each heater circuit.
These fuses are included in accessory single point boxes, with
power distribution and fuse blocks. The single point box will
be installed directly under the unit control box, just to the left
of the partition separating the indoor section (with electric
heaters) from the outdoor section. The single point box has a
hinged access cover. See Fig. 45. The single point box also in-
cludes pigtails to complete the wiring between the single point
box and the unit’s main control box terminals. Refer to the ac-
cessory heater and single point box installation instructions for
details on tap connections.
All fuses on 50TCQ units are 60-A. (Note that all heaters are
qualified for use with a 60-A fuse, regardless of actual heater
ampacity, so only 60-A fuses are necessary.)
Fig. 45 — Typical Single Point Installation
SINGLE POINT BOXES WITHOUT FUSES
Refer to accessory heater and single point box installation in-
structions for details on tap connections.
LOW-VOLTAGE CONTROL CONNECTIONS
Run the low-voltage control leads from the heater module(s) -
VIO and BRN (two of each if two modules are installed) - to
the 4-pole terminal board TB4 located on the heater bulkhead
to the left of Heater #1. Except for CRHEATER128B00-
129B00, connect the VIO leads from Heater #1 and Heater #2
to terminal TB4-1. Connect the BRN leads to terminal TB4-3.
For CRHEATER128B00-129B00 only
Connect the ORN lead from HR1 (Heater Relay 1) and the
VIO lead from HR3 (Heater Relay 3) to terminal TB4-1. Con-
nect the BRN lead from HR1 to TB4-3. See Fig. 47.
Fig. 46 — Accessory Electric Heater Control
Connections (Except CRHEATER128B00-129B00)
Fig. 47 — Accessory Electric Heater Control
Connections for CRHEATER128B00-129B00 Only
ALLIED PA
MODEL NO.
ERIAL NO.
CORP.
OD
22.2
3
1
23
ISTED AIR
NDITIONING
UIP ACCESS
346N
.
P / N
2-
5610-4
REV
1
1
1
3
2
1
2
3
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
FOAM
BUSHING
DRIP BOOT
BRACKET
MOUNTING
SCREWS
HEATER
RELAYS
POWER
WIRES
HEATER
MOUNTING
SCREWS
DEFRO
S
T
BOARD
ORN
BRN
Field
Connection
s
E-HEAT
P
3
-
3
3
1
ORN
BRN
VIO
BRN BRN
VIO
TB4
VIO
HR2
HR1
BRN
VIO
BRN
Elec Htr
HR1: On He
a
ter 1 in Po
s
ition #1
HR2: On He
a
ter 2 in Po
s
ition #2 (if in
s
t
a
lled)
DEFRO
S
T
BOARD
ORN
BRN
Field
Connection
s
E-HEAT
P
3
-
3
3
1
ORN
BRN
ORN
BRN
VIO
TB4
VIO
HR
3
HR1
ORN
BRN
Elec Htr
L
S
: Prim
a
ry Limit
S
witch
For
s
implicity, not
a
ll control
wiring intern
a
l to the electric
he
a
ter
s
i
s
s
hown.
Содержание WeatherMaker 50TCQ*08
Страница 4: ...4 Fig 2 Unit Dimensional Drawing 08 and 09 Size Units ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing 08 and 09 Size Units cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing 12 Size Unit ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing 12 Size Unit cont ...
Страница 19: ...19 Fig 25 Typical 50TCQ Control Wiring Diagram Sizes 08 09 ...
Страница 20: ...20 Fig 26 Typical 50TCQ Control Wiring Diagram Size 12 ...
Страница 21: ...21 Fig 27 50TCQ 08 09 Power Wiring Diagram ...
Страница 22: ...22 Fig 28 Typical 50TCQ 12 Power Wiring Diagram 208 230 v 3 Phase 60Hz Unit Shown ...
Страница 45: ......