27
Fig. 36 —
Controller Assembly
Sensor
The sensor (see Fig. 37) includes a plastic housing, a printed cir
-
cuit board, a clear plastic cover, a sampling tube inlet and an ex
-
haust tube. The sampling tube, when used, and exhaust tube are at
-
tached during installation. The sampling tube varies in length de
-
pending on the size of the rooftop unit. The clear plastic cover
permits visual inspections without having to disassemble the sen
-
sor. The cover attaches to the sensor housing using four captive
screws and forms an airtight chamber around the sensing electron
-
ics. Each sensor includes a harness with an RJ45 terminal for con
-
necting to the controller. Each sensor has four LEDs: Power, Trou
-
ble, Alarm, and Dirty. A manual test/reset button is located on the
left side of the housing.
Air is introduced to the duct smoke detector sensor’s sensing
chamber through a sampling tube that extends into the HVAC duct
and is directed back into the ventilation system through a (shorter)
exhaust tube. The difference in air pressure between the two tubes
pulls the sampled air through the sensing chamber. When a suffi
-
cient amount of smoke is detected in the sensing chamber, the sen
-
sor signals an alarm state and the controller automatically takes
the appropriate action to shut down fans and blowers, change over
air handling systems, notify the fire alarm control panel, etc.
The sensor uses a photoelectric (light scattering principle) process
called differential sensing to prevent gradual environmental
changes from triggering false alarms. A rapid change in environ
-
mental conditions, such as smoke from a fire, causes the sensor to
signal an alarm state but dust and debris accumulated over time
does not.
For installations using two sensors, the duct smoke detector
does not differentiate which sensor signals an alarm or trouble
condition.
Fig. 37 —
Smoke Detector Sensor
Smoke Detector Locations
SUPPLY AIR
The supply-air smoke detector sensor is located to the left of the
unit’s indoor (supply) fan. See Fig. 38. Access is through the fan
access panel. There is no sampling tube used at this location. The
sampling tube inlet extends through the side plate of the fan hous
-
ing (into a high pressure area). The controller is located on a
bracket to the right of the return filter, accessed through the lift-off
filter panel.
Fig. 38 —
Typical Supply Air Smoke Detector Sensor
Location
RETURN AIR WITHOUT ECONOMIZER
The sampling tube is located across the return air opening on the
unit basepan. See Fig. 39. The holes in the sampling tube face
downward, into the return air stream. The sampling tube is at
-
tached to the control module bushing that extends from the control
box through the partition into the return air section of the unit. The
sensor tube is shipped mounted to the indoor blower housing and
must be relocated to the return air section of the unit. Installation
requires that this sensing tube be attached to the control module
bushing. See installation steps.
DUCT SMOKE SENSOR
CONTROLLER
CONDUIT NUTS
(SUPPLIED BY INSTALLER)
CONDUIT SUPPORT PLATE
TERMINAL BLOCK COVER
COVER GASKET
(ORDERING OPTION)
CONTROLLER
COVER
FASTENER (2X)
CONDUIT COUPLINGS
(SUPPLIED BY INSTALLER)
CONTROLLER HOUSING
AND ELECTRONICS
ALARM
TROUBLE
POWER
TEST/RESET
SWITCH
SEE DETAIL
A
DETAIL
A
PLUG
SAMPLING TUBE
(ORDERED SEPARATELY)
COUPLING
MAGNETIC
TEST/RESET
SWITCH
ALARM
TROUBLE
POWER
DIRTY
SENSOR
COVER
COVER GASKET
(ORDERING OPTION)
SENSOR HOUSING
AND ELECTRONICS
EXHAUST GASKET
EXHAUST TUBE
DUCT SMOKE SENSOR
INTAKE
GASKET
TSD-CO2
(ORDERING OPTION)
SUPPLY AIR
SMOKE
DETECTOR
SENSOR
Содержание WeatherMaker 50TC 17-30 Series
Страница 34: ...34 Fig 48 RTU Open Overlay for Economizer Wiring ...
Страница 35: ...35 Fig 49 VFD Overlay for W2770 Controller Wiring ...
Страница 80: ...80 Fig C 50TC 17 28 Control Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 81: ...81 Fig D 50TC 30 Control Wiring Diagram 208 230 3 60 Units APPENDIX D WIRING DIAGRAMS ...
Страница 82: ...82 Fig E 50TC 30 Control Wiring Diagram 460 3 60 575 3 60 Units APPENDIX D WIRING DIAGRAMS ...
Страница 83: ...83 Fig F 50TC 17 30 Power Wiring Diagram 208 230 3 60 Units APPENDIX D WIRING DIAGRAMS ...
Страница 84: ...84 Fig G 50TC 17 30 Power Wiring Diagram 460 3 60 575 3 60 Units APPENDIX D WIRING DIAGRAMS ...
Страница 85: ...85 Fig H 50TC 17 30 Control Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 87: ...87 Fig J 50TC 17 30 Power Wiring Diagram 460 3 60 Units with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 88: ...88 Fig K 50TC 17 30 Power Wiring Diagram 575 3 60 Units with Humidi MiZer System APPENDIX D WIRING DIAGRAMS ...
Страница 89: ...89 Fig L 50TC PremierLink System Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 90: ...90 Fig M 50TC RTU Open Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 91: ...91 Fig N 50TC SAV VFD System Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 93: ......