![Carrier WeatherMaker 48TC*A04 Скачать руководство пользователя страница 97](http://html.mh-extra.com/html/carrier/weathermaker-48tc-a04/weathermaker-48tc-a04_service-and-maintenance-instructions_2560316097.webp)
97
FAN PERFORMANCE (cont.)
48TC**12
3 PHASE
10 TON HORIZONTAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Field---Supplied Drive
1
Standard Static Option
Medium Static Option
3000
579
0.70
660
0.89
732
1.09
799
1.29
860
1.50
3250
613
0.85
690
1.06
760
1.27
823
1.49
883
1.71
3500
648
1.03
721
1.25
788
1.48
850
1.71
907
1.95
3750
683
1.23
753
1.47
817
1.71
877
1.96
933
2.21
4000
719
1.45
786
1.71
848
1.97
905
2.23
959
2.50
4250
756
1.71
819
1.98
879
2.26
934
2.53
987
2.81
4500
792
1.99
853
2.28
910
2.57
964
2.87
1015
3.16
4750
830
2.31
888
2.62
943
2.92
995
3.23
1044
3.54
5000
867
2.66
923
2.98
976
3.30
1026
3.63
1074
3.95
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
3000
917
1.70
970
1.91
1021
2.13
1070
2.34
1117
2.56
3250
938
1.93
991
2.16
1041
2.38
1089
2.61
1134
2.85
3500
961
2.18
1013
2.42
1062
2.66
1108
2.91
1153
3.15
3750
985
2.46
1035
2.71
1083
2.97
1129
3.23
1173
3.49
4000
1011
2.76
1059
3.03
1106
3.30
1151
3.58
1194
3.85
4250
1037
3.09
1084
3.38
1130
3.66
1174
3.95
1216
4.24
4500
1064
3.46
1110
3.76
1155
4.06
1198
4.36
1239
4.66
4750
1091
3.85
1137
4.16
1180
4.48
1222
4.80
1263
5.12
5000
1120
4.28
1164
4.61
1207
4.94
---
---
---
---
NOTE
: For more information, see General Fan Performance Notes on page 87.
Boldface
indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part no. KR11AD912) and belt (part no. KR29AF051).
2. Recommend using field---supplied motor pulley (part no. KR11HY410).
48TC**12
3 PHASE
10 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
3000
616
0.79
689
0.97
757
1.16
821
1.36
882
1.57
3250
655
0.96
724
1.16
788
1.37
849
1.58
907
1.80
3500
695
1.17
760
1.38
821
1.60
879
1.83
934
2.06
3750
736
1.41
797
1.63
855
1.86
910
2.10
963
2.35
4000
777
1.68
834
1.91
889
2.16
942
2.41
993
2.67
4250
818
1.98
873
2.23
925
2.49
976
2.75
1025
3.02
4500
860
2.32
912
2.58
962
2.85
1010
3.13
1057
3.41
4750
902
2.69
951
2.97
999
3.26
1046
3.55
1091
3.84
5000
944
3.11
991
3.40
1037
3.70
1082
4.00
1125
4.31
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
3000
939
1.79
994
2.01
1047
2.24
1098
2.47
1147
2.71
3250
962
2.03
1015
2.26
1066
2.50
1115
2.75
1163
3.00
3500
987
2.30
1038
2.54
1088
2.80
1135
3.05
1181
3.32
3750
1014
2.60
1063
2.86
1111
3.12
1157
3.39
1202
3.66
4000
1042
2.93
1090
3.20
1136
3.48
1180
3.76
1224
4.04
4250
1072
3.30
1118
3.58
1162
3.87
1205
4.16
1247
4.46
4500
1103
3.70
1147
4.00
1190
4.29
1232
4.60
1273
4.91
4750
1135
4.14
1177
4.45
1219
4.76
1259
5.08
---
---
5000
1167
4.63
1209
4.95
---
---
---
---
---
---
NOTE
: For more information, see General Fan Performance Notes on page 87.
Boldface
indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part no. KR11HY410).
48TC
Содержание WeatherMaker 48TC*A04
Страница 10: ...10 COOLING CHARGING CHARTS cont C08204 C08228 Fig 12 cont Cooling Charging Charts 48TC ...
Страница 11: ...11 COOLING CHARGING CHARTS cont C08229 C08437 Fig 12 cont Cooling Charging Charts 48TC ...
Страница 12: ...12 COOLING CHARGING CHARTS cont C08438 C08439 Fig 12 cont Cooling Charging Charts 48TC ...
Страница 35: ...35 C08248 Fig 42 PremierLink Wiring Schematic 48TC ...
Страница 43: ...43 C07129 Fig 59 RTU MP Multi Protocol Control Board 48TC ...
Страница 44: ...44 44 C08458 Fig 60 RTU MP System Control Wiring Diagram 48TC ...
Страница 64: ...64 C08308 Fig 83 48TC Typical Unit Wiring Diagram Power A06 208 230 3 60 48TC ...