Fig. 34 —
Thru-Base Connection Fittings
(07 units built on or after 4/15/2019)
The thru-base gas connector has male and female threads. The
male threads protrude above the basepan of the unit; the female
threads protrude below the basepan.
Check tightness of connector lock nuts before connecting gas pip
-
ing.
Install a
1
/
2
-in. NPT street elbow on the thru-base gas fitting. At
-
tach a
1
/
2
-in. pipe nipple with minimum length of 16-in. (406 mm)
(field-supplied) to the street elbow and extend it through the ac
-
cess panel at the gas support bracket. See Fig. 35 and Fig. 36.
Fig. 35 —
Gas Line Piping (Sizes 07-14)
Fig. 36 —
Thru-Base Gas Line Piping for 48TC**07
Units Built On or After 4/15/19
FACTORY-OPTION THRU-BASE GAS CONNECTIONS
(SIZE 16)
This service connection kit consists of a
3
/
4
-in. NPT gas adapter
fitting (stainless steel), a
1
/
2
-in. electrical bulkhead connector and a
1
1
/
2
-in. electrical bulkhead connector, connected to an “L” bracket
covering the embossed (raised) section of the unit basepan in the
condenser section. See Fig. 37.
1. Remove the “L” bracket assembly from the unit (see
Fig. 37).
2. Cut and discard the wire tie on the gas fitting. Hand-
tighten the fitting if it has loosened in transit.
3. Remove connector plate assembly from the “L” bracket
and discard the “L” bracket, but retain the washer head
screws and the gasket (located between the “L” bracket
and the connector plate assembly
NOTE: Take care not to damage the gasket, as it is reused in the
following step.
4. Place the gasket over the embossed area in the basepan,
aligning the holes in the gasket to the holes in the basepan.
See Fig. 38.
5. Install the connector plate assembly to the basepan using 8
of the washer head screws.
Fig. 37 —
Thru-Base Connection Fittings
(Size 16 Shown)
Fig. 38 —
Completing Installation of Thru-the-Base
Option (Size 16 Shown)
NOTE: If gas and/or electrical connections are not going to occur
at this time, tape or otherwise cover the fittings so that moisture
does not get into the building or conduit in the interim.
LOW VOLTAGE
CONDUIT
CONNECTOR
HIGH VOLTAGE
CONDUIT
CONNECTOR
BRASS FITTING FOR
3 TO 6 TON UNITS
AUXILIARY
POWER
SUPPLY
(OPTIONAL)
EMBOSSMENT
BRASS FITTING
FOR 3-6 TON UNITS
SUPPORT
BRACKET
EMBOSSMENT
BRASS FITTING
FOR GAS PIPING
SUPPORT
BRACKET
1
1
/
2
” ELECTRICAL
BULKHEAD
CONNECTOR
1
/
2
” ELECTRICAL
BULKHEAD
CONNECTOR
3
/
4
” NPT GAS
ADAPTER
FITTING
“L” BRACKET
GASKET
CONNECTOR
PLATE
ASSEMBLY
Содержание WeatherMaker 48TC A/B07 Series
Страница 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Страница 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Страница 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Страница 8: ...8 Fig 5 Base Rail Details Size 07 ...
Страница 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Страница 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Страница 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Страница 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Страница 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Страница 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Страница 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Страница 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Страница 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...