ECONOMI$ER
®
X (FACTORY-INSTALLED OPTION)
Product Description — The EconoMi$er X system is an ex-
pandable economizer control system, which includes a W7220
economizer module (controller) with an LCD and keypad (see
Fig. 37). The W7220 can be configured with optional sensors.
Fig. 37 — W7220 Economizer Module
The W7220 economizer module can be used as a stand-
alone economizer module wired directly to a commercial set-
back space thermostat and sensors to provide outside air dry-
bulb economizer control.
The W7220 economizer module can be connected to op-
tional sensors for single or differential enthalpy control. The
W7220 economizer module provides power and communica-
tions for the sensors.
The W7220 economizer module automatically detects sen-
sors by polling to determine which sensors are present. If a sen-
sor loses communications after it has been detected, the W7220
economizer controller indicates a device fail error on its LCD.
System Components — The EconoMi$er X system includes
an economizer module, 20k mixed air sensor, damper actuator,
and either a 20k outdoor air temperature sensor or S-Bus en-
thalpy sensors.
Economizer Module
— The economizer module is the core of
the EconoMi$er X system. The module is mounted in the unit’s
control box, and includes the user interface for the system. The
W7220 economizer module provides the basic inputs and out-
puts to provide simple economizer control. When used with the
optional sensors, the economizer module provides more ad-
vanced economizer functionality.
S-Bus Enthalpy Control Sensors
— This sensor is a combina-
tion temperature and humidity sensor which is powered by and
communicates on the S-Bus. Up to three sensors may be con-
figured with the W7220 economizer module. See page 24 for
details.
CO
2
Sensor (optional)
— A CO
2
sensor can be added for
Demand Controlled Ventilation (DCV).
Specifications
W7220 Economizer Module
— The module is designed for
use with 2 to 10 Vdc or bus communicating actuator. The mod-
ule includes terminals for CO2 sensor, mixed air sensor, and an
outdoor dry bulb sensor. Enthalpy and other options are avail-
able with bus sensors.
User Interface
— Provides status for normal operation, setup
parameters, checkout tests, and alarm and error conditions with
a 2-line 16 character LCD display and four button keypad.
Electrical
Rated Voltage —
20 to 30 Vac RMS, 50/60 Hz
Transformer — 100 va maximum system input
Nominal Power Consumption (at 24 Vac, 60 Hz) — 11.5
VA without sensors or actuators
Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only) — 1.5A run:
3.5A inrush at 0.45PF (200,000 cycles) or
7.5A inrush at 0.45PF (100,000 cycles)
External Sensors Power Output — 21 Vdc ± 5% at 48mA
Inputs
Sensors
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor for dry bulb
change over or an OA bus sensor for outdoor enthalpy change
over is required in addition to the MA sensor. An additional
Return Air (RA) bus sensor can be added to the system for dif-
ferential enthalpy or dry bulb changeover. For differential dry
bulb changeover a 20k ohm sensor is required in the OA and a
bus sensor in the RA. DIP switch on RA bus sensor must be
set in the RA position.
Dry Bulb Temperature (optional) and Mixed Air (required),
20k NTC
2-wire (18 to 22 AWG);
Temperature range –40 to 150°F (–40 to 65°C)
Temperature accuracy: 0°F/+2°F
Temperature and Humidity, C7400S1000 (optional)
S-Bus; 2-wire (18 to 22 AWG)
Temperature: range –40 to 150°F (–40 to 65°C)
Temperature accuracy: 0°F/+2°F
Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) S-Bus sensors may be connected to the
W7220 economizer module. For outdoor air (OA), return air
(RA) and discharge (supply) air (DA).
4 Binary Inputs
1-wire 24 Vac + common GND (see page 25 for wiring
details).
24 Vac Power Supply
20 to 30 Vac 50/60Hz;
100 VA Class 2 transformer.
Outputs
Actuator Signal
2-10 Vdc; minimum actuator impedance is 2k ohm; bus
two-wire output for bus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
Environmental
Operating Temperature
–40 to 150°F (–40 to 65°C).
Exception of display operation down to –4°F with full
recovery at –4°F from exposure to –40°F
Storage Temperature
–40 to 150°F (–40 to 65°C)
Shipping Temperature
–40 to 150°F (–40 to 65°C)
Relative Humidity
5% to 95% RH non-condensing
IMPORTANT: All inputs and outputs must be Class 2
wiring.
Содержание WeatherMaker 48TC 04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 48TC B07 Unit with Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 39: ...39 Fig 45 PremierLink Wiring Schematic ...
Страница 40: ...40 Fig 46 PremierLink Wiring Schematic with Humidi MiZer System ...
Страница 48: ...48 Fig 65 Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 66 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System ...