187
APPENDIX A
—
LOCAL DISPLAY TABLES
MODE — RUN STATUS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
PAGE NO.
VIEW
AUTO VIEW OF RUN STATUS
HVAC
ascii string spelling out the hvac modes
string
OCC
Occupied?
No/Yes
OCCUPIED
forcible
MAT
Mixed Air Temperature
-40 to 240
dF
MAT
EDT
Evaporator Discharge Tmp
-40 to 240
dF
EDT
LAT
Leaving Air Temperature
-40 to 240
dF
LAT
EC.C.P
Economizer Control Point
0 to 180
dF
ECONCPNT
EC1.P
Econ 1 Out Act.Curr.Pos.
0 to 100
%
ECONOPOS
EC2.P
Econ 2 Ret Act.Curr.Pos.
0 to 100
%
ECON2POS
EC3.P
Econ 3 Out Act.Curr.Pos.
0 to 100
%
ECON3POS
CL.C.P
Cooling Control Point
-20 to 140
dF
COOLCPNT
C.CAP
Current Running Capacity
0 to 100
%
CAPTOTAL
CL.ST
Requested Cool Stage
0 to 20
CL_STAGE
HT.C.P
Heating Control Point
-20 to 140
dF
HEATCPNT
HT.ST
Requested Heat Stage
0 to 20
HT_STAGE
H.MAX
Maximum Heat Stages
0 to 20
HTMAXSTG
ECON
ECONOMIZER RUN STATUS
EC1.P
Econ 1 Out Act.Curr.Pos.
0 to 100
%
ECONOPOS
EC2.P
Econ 2 Ret Act.Curr.Pos.
0 to 100
%
ECON2POS
EC3.P
Econ 3 Out Act.Curr.Pos.
0 to 100
%
ECON3POS
ECN.C
Econ 1 Out Act.Cmd.Pos.
0 to 100
%
ECONOCMD
forcible
ACTV
Economizer Active ?
No/Yes
ECACTIVE
SACA
Single Act CFM Ctl Activ
No/Yes
SACFMCTL
forcible
DISA
ECON DISABLING CONDITIONS
UNV.1
Econ1 Out Act Unvailable ?
No/Yes
ECONUNAV
UNV.2
Econ2 Ret Act Unvailable ?
No/Yes
ECN2UNAV
UNV.3
Econ3 Out Act Unvailable ?
No/Yes
ECN3UNAV
ENTH
Enth. Switch Read High ?
No/Yes
ENTH
DBC
DBC - OAT Lockout ?
No/Yes
DBC_STAT
DEW
DEW - OA Dewpt.Lockout ?
No/Yes
DEW_STAT
DDBC
DDBD- OAT > RAT Lockout ?
No/Yes
DDBCSTAT
OAEC
OAEC- OA Enth Lockout ?
No/Yes
OAECSTAT
DEC
DEC - Diff.Enth.Lockout ?
No/Yes
DEC_STAT
EDT
EDT Sensor Bad ?
No/Yes
EDT_STAT
OAT
OAT Sensor Bad ?
No/Yes
OAT_STAT
FORC
Economizer Forced ?
No/Yes
ECONFORC
SFON
Supply Fan Not On 30s ?
No/Yes
SFONSTAT
CLOF
Cool Mode Not In Effect ?
No/Yes
COOL_OFF
OAQL
OAQ Lockout in Effect ?
No/Yes
OAQLOCKD
HELD
Econ Recovery Hold Off ?
No/Yes
ECONHELD
DH.DS
Dehumid. Disabled Econ.?
No/Yes
DHDISABL
O.AIR
OUTSIDE AIR INFORMATION
OAT
Outside Air Temperature
-40 to 240
dF
OAT
forcible
OA.RH
Outside Air Rel. Humidity
0 to 100
%
OARH
forcible
OA.E
Outside Air Enthalpy
-20 to 10000
OAE
OA.D.T
OutsideAir Dewpoint Temp
-40 to 240
dF
OADEWTMP
COOL
COOLING INFORMATION
C.CAP
Current Running Capacity
0 to 100
%
CAPTOTAL
CUR.S
Current Cool Stage
0 to 20
COOL_STG
REQ.S
Requested Cool Stage
0 to 20
CL_STAGE
MAX.S
Maximum Cool Stages
0 to 20
CLMAXSTG
DEM.L
Active Demand Limit
0 to 100
%
DEM_LIM
forcible
SUMZ
COOL CAP. STAGE CONTROL
SMZ
Capacity Load Factor
-400 to 400
SMZ
ADD.R
Next Stage EDT Decrease
0 to 30
^F
ADDRISE
SUB.R
Next Stage EDT Increase
0 to 30
^F
SUBRISE
R.PCT
Rise Per Percent Capacity
0 to 10
RISE_PCT
Y.MIN
Cap Deadband Subtracting
-40 to 0
Y_MINUS
Y.PLU
Cap Deadband Adding
0 to 40
Y_PLUS
Z.MIN
Cap Threshold Subtracting
-99 to 0
Z_MINUS
Z.PLU
Cap Threshold Adding
0 to 99
Z_PLUS
H.TMP
High Temp Cap Override
No/Yes
HI_TEMP
L.TMP
Low Temp Cap Override
No/Yes
LOW_TEMP
PULL
Pull Down Cap Override
No/Yes
PULLDOWN
SLOW
Slow Change Cap Override
No/Yes
SLO_CHNG
Содержание WeatherExpert 48N2
Страница 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Страница 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Страница 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Страница 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Страница 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Страница 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Страница 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Страница 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Страница 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Страница 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Страница 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Страница 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Страница 168: ...168 Fig 47 Sensor and Ignition Position Fig 48 Combustion Blower Details SENSOR DETAILS IGNITION DETAILS ...
Страница 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...