116
Run Status Menu
The Run Status menu provides the user important information
about the unit. The Run Status table can be used to trouble
-
shoot problems and to help determine how and why the unit is
operating.
AUTO VIEW OF RUN STATUS
The Auto View of Run Status display table provides the most
important unit information. The HVAC Mode (
Run Sta
-
tus
VIEW
HVAC
) informs the user what HVAC mode the
unit is currently in. Refer to the Modes section on page 39 for
information on HVAC modes. The occupied status, unit tem
-
peratures, unit set points, and stage information can also be
shown. See Table 83.
Run Status
VIEW
HVAC
Displays the current HVAC Mode(s) by name. HVAC Modes
include:
Run Status
VIEW
OCC
Displays the current occupancy status of the control.
Run Status
VIEW
MAT
Displays the current value for mixed-air temperature. This val
-
ue is calculated based on return-air and outside-air tempera
-
tures and economizer damper position.
Run Status
VIEW
EDT
Displays the current evaporator discharge air temperature
during Cooling modes. This value is read at the supply air
thermistor location (or at cooling coil thermistor array if unit is
equipped with hydronic heating coil).
Run Status
VIEW
LAT
Displays the current leaving-air temperature during Vent and
Hydronic Heating modes. This value is read at the supply air
thermistor location.
Run Status
VIEW
EC.C.P
Displays the current economizer control point value (a target
value for air temperature leaving the evaporator coil location).
Run Status
VIEW
EC1.P
Displays the current actual economizer no. 1 (out) position (in
percentage open).
Run Status
VIEW
EC2.P
Displays the current position of actuator no. 2 (ret.) (in percent
-
age open).
Run Status
VIEW
EC3.P
Displays the current position of actuator no. 3 (out) (in percent
-
age open).
Run Status
VIEW
CL.C.P
Displays the current cooling control point (a target value for air
temperature leaving the evaporator coil location).
Run Status
VIEW
C.CAP
Displays the current amount of unit cooling capacity (in per
-
cent of maximum). Compare to staging tables in Appendix C.
Run Status
VIEW
CL.ST
Displays the current number of requested cooling stages. Com
-
pare to staging tables in Appendix C and to
C.CAP
above.
Run Status
VIEW
HT.C.P
Displays the current heating control point; for use with staged
gas or modulating gas control option only (a target value for air
temperature leaving the supply duct).
Run Status
VIEW
HT.ST
Displays the current number of heating stages active (for
staged gas control option only). Compare to following point.
Run Status
VIEW
H.MAX
Displays the maximum number of heat stages available for this
model.
ECONOMIZER RUN STATUS
The Economizer Run Status display table provides information
about the economizer and can be used to troubleshoot econo
-
mizer problems. See Table 84. The current position, command
-
ed position, and whether the economizer is active can be dis
-
played. All the disabling conditions for the economizer and
outside air information is also displayed.
Table 83 —
Auto View of Run Status Display Table
OFF
VENT
HIGH HEAT
STARTING UO
HIGH COOL
FIRE SHUT DOWN
SHUTTING DOWN
LOW COOL
PRESSURIZATION
DISABLED
UNOCC FREE COOL
EVACUATION
SOFTSTOP REQUEST TEMPERING HI COOL
SMOKE PURGE
REM SW DISABLE
TEMPERING LO COOL DEHUMIDIFICATION
COMP STUCK ON
TEMPERING VENT
RE-HEAT
TEST
LOW HEAT
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
VIEW
AUTO VIEW OF RUN STATUS
HVAC
ascii string spelling out the hvac modes
string
OCC
Occupied?
No/Yes
OCCUPIED
forcible
MAT
Mixed Air Temperature
dF
MAT
EDT
Evaporator Discharge Tmp
dF
EDT
LAT
Leaving Air Temperature
dF
LAT
EC.C.P
Economizer Control Point
dF
ECONCPNT
EC1.P
Economizer Out Act.Curr.Pos.
0-100
%
ECONOPOS
EC2.P
Economzr2 Ret. Act.Curr.Pos.
0-100
%
ECON2POS
EC3.P
Economzr3 Out Act.Curr.Pos.
0-100
%
ECON3POS
CL.C.P
Cooling Control Point
dF
COOLCPNT
C.CAP
Current Running Capacity
CAPTOTAL
CL.ST
Requested Cool Stage
CL_STAGE
HT.C.P
Heating Control Point
dF
HEATCPNT
HT.ST
Requested Heat Stage
HT_STAGE
H.MAX
Maximum Heat Stages
HTMAXSTG
Содержание WeatherExpert 48N2
Страница 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Страница 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Страница 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Страница 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Страница 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Страница 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Страница 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Страница 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Страница 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Страница 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Страница 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Страница 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Страница 168: ...168 Fig 47 Sensor and Ignition Position Fig 48 Combustion Blower Details SENSOR DETAILS IGNITION DETAILS ...
Страница 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...