51
Table 14 — VFD Unit Parameters – 48LC*B Size 26
REGIONAL
SETTINGS
GRID
TYPE
MOTOR
POWER
MOTOR
VOLTAGE
MOTOR
FREQUENCY
(Hz)
MOTOR
CURRENT
(MUST-HOLD
AMPS)
MOTOR
NOMINAL
SPEED (RPM)
Motor
Option Voltage
Motor
P/N
VFD
Carrier P/N
VFD
Mfr P/N
0–03
0–06
1–20
1–22
1–23
1–24
1–25
STD
208/230 HD60FK657 HK30WA373 131L9798
[1]
[102]
[14]
230
60
21.2
1760
460
HD60FK657 HK30WA380 131L9867
[1]
[122]
[14]
460
60
9.7
1760
575
HD60FL576 HK30WA384 131N0229
[1]
[132]
[14]
575
60
7.2
1745
MID
208/230 HD62FK654 HK30WA374 131L9799
[1]
[102]
[15]
230
60
28.0
1760
460
HD62FK654 HK30WA381 131L9868
[1]
[122]
[15]
460
60
13.7
1760
575
HD62FL576 HK30WA384 131N0229
[1]
[132]
[15]
575
60
8.9
1750
HIGH
208/230 HD64FK654 HK30WA375 131L9800
[1]
[102]
[16]
230
60
37.3
1755
460
HD64FK654 HK30WA386 131L9869
[1]
[122]
[16]
460
60
16.9
1755
575
HD64FL576 HK30WA388 131N0233
[1]
[132]
[16]
575
60
12.6
1755
START
DELAY
(sec)
FLYING
START
MIN SPEED FOR
FUNCTION (Hz)
MOTOR
THERMAL
PROTECTION
PRESET REFERENCE
Motor
Option Voltage
1–71
1–73
1–82
1–90
3–10 [0] 3–10 [1] 3–10 [2] 3–10 [3] 3–10 [4] 3–10 [5] 3–10 [6] 3–10 [7]
STD
208/230
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
460
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
575
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
MID
208/230
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
460
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
575
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
HIGH
208/230
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
460
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
575
2.0
[1]
1.0
[4]
0%
60.00% 72.00%
100%
100%
0%
0%
0%
RAMP UP
TIME (sec)
RAMP DOWN
TIME (sec)
CURRENT
LIMIT
TERMINAL 18
DIGITAL INPUT
TERMINAL 19
DIGITAL INPUT
TERMINAL 27
DIGITAL INPUT
TERMINAL 29
DIGITAL INPUT
Motor
Option
Voltage
3–41
3–42
4–18
5–10
5–11
5–12
5–13
STD
208/230
10.00
10.00
100%
[8]
[16]
[17]
[18]
460
10.00
10.00
100%
[8]
[16]
[17]
[18]
575
10.00
10.00
100%
[8]
[16]
[17]
[18]
MID
208/230
10.00
10.00
100%
[8]
[16]
[17]
[18]
460
10.00
10.00
100%
[8]
[16]
[17]
[18]
575
10.00
10.00
100%
[8]
[16]
[17]
[18]
HIGH
208/230
10.00
10.00
100%
[8]
[16]
[17]
[18]
460
10.00
10.00
100%
[8]
[16]
[17]
[18]
575
10.00
10.00
100%
[8]
[16]
[17]
[18]
TERMINAL 53
LOW VOLTAGE
TERMINAL 53
HIGH VOLTAGE
TERMINAL 53
LOW REFERENCE
TERMINAL 53
HIGH REFERENCE
RESET
MODE
AUTO. RESTART
TIME (s)
RFI
FILTER
Motor
Option Voltage
6–10
6–11
6–14
6–15
14–20
14–21
14–50
STD
208/230
2
[10]
0
[60]
[3]
600
[0]
460
2
[10]
0
[60]
[3]
600
[0]
575
2
[10]
0
[60]
[3]
600
[0]
MID
208/230
2
[10]
0
[60]
[3]
600
[0]
460
2
[10]
0
[60]
[3]
600
[0]
575
2
[10]
0
[60]
[3]
600
[0]
HIGH
208/230
2
[10]
0
[60]
[3]
600
[0]
460
2
[10]
0
[60]
[3]
600
[0]
575
2
[10]
0
[60]
[3]
600
[0]
Содержание WeatherExpert 48LC B14 Series
Страница 4: ...4 Fig 2 48LC B14 Vertical Airflow ...
Страница 5: ...5 Fig 3 48LC B14 Horizontal Airflow ...
Страница 6: ...6 Fig 4 48LC B14 Back View and Condensate Drain Location ...
Страница 7: ...7 Fig 5 48LC B14 Corner Weights and Clearances ...
Страница 8: ...8 Fig 6 48LC B14 Bottom View ...
Страница 9: ...9 Fig 7 48LC B17 20 Vertical Airflow ...
Страница 10: ...10 Fig 8 48LC B17 20 Horizontal Airflow ...
Страница 11: ...11 Fig 9 48LC B17 20 Back View and Condensate Drain Location ...
Страница 12: ...12 Fig 10 48LC B17 20 Corner Weights and Clearances ...
Страница 13: ...13 Fig 11 48LC B17 20 Bottom View ...
Страница 14: ...14 Fig 12 48LC B24 26 Vertical Airflow ...
Страница 15: ...15 Fig 13 48LC B24 26 Horizontal Airflow ...
Страница 16: ...16 Fig 14 48LC B24 26 Back View and Condensate Drain Location ...
Страница 17: ...17 Fig 15 48LC B24 26 Corner Weights and Clearances ...
Страница 18: ...18 Fig 16 48LC B24 26 Bottom View ...
Страница 21: ...21 Fig 20 48LC B14 Roof Curb Details ...
Страница 22: ...22 Fig 21 48LC B17 20 Roof Curb Details ...
Страница 23: ...23 Fig 22 48LC B24 26 Roof Curb Details ...
Страница 30: ...30 Fig 40 48LC B14 26 VAV RTU Open Control Wiring Diagram ...
Страница 31: ...31 Fig 41 48LC B14 26 Power Wiring Diagram ...
Страница 53: ......