![Carrier WeatherExpert 48LC B14 Series Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/carrier/weatherexpert-48lc-b14-series/weatherexpert-48lc-b14-series_installation-instructions-manual_2561501028.webp)
28
Install a gas supply line that runs to the unit heating section. Refer
to the NFPA 54/NFGC or equivalent code for gas pipe sizing data.
Do not use a pipe smaller than the size specified. Size the gas sup-
ply line to allow for a maximum pressure drop of 0.5 in. wg
(124 Pa) between gas regulator source and unit gas valve connec-
tion when unit is operating at high-fire flow rate.
The gas supply line can approach the unit in two ways: horizontal-
ly from outside the unit (across the roof), or through unit basepan.
Observe clearance to gas line components per Fig. 34.
Fig. 34 — Gas Piping Guide
FACTORY-OPTION THRU-BASE CONNECTIONS
Electrical Connections
Knockouts are located in the control box area. Remove the appro-
priate size knockout for high voltage connection. Use the field
supplied connector depending on wiring or conduit being utilized.
Remove the
7
/
8
-in. (22mm) knockout and appropriate connector
for low voltage wiring. If non-unit powered convenience outlet is
being utilized, remove the
7
/
8
-in. (22mm) knockout and utilize ap-
propriate connector for 115 volt line. See “Step 14 — Making
Electrical Connections” for details.
Gas Connections
Remove the knockout in the base pan and route
3
/
4
-in. gas line up
through the opening. Install an elbow and route gas line through
opening in panel after first removing plastic bushing. Install a gas
shut off followed by a drip leg and ground-joint union. Route gas
line into gas section through the grommet (Part #: KA56SL112) at
the gas inlet and into the gas valve. See Fig. 32 and Table 3. If a
regulator is installed, it must be located 4 feet (1.22 meters) from
the flue outlet.
Some municipal codes require that the manual shutoff valve be lo-
cated upstream of the sediment trap. See Fig. 33 for typical piping
arrangements for gas piping that has been routed through the side-
wall of the base pan.
When installing the gas supply line, observe local codes pertaining
to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1
NFGC latest edition (in Canada, CAN/CSA B149.1). In the ab-
sence of local building codes, adhere to the following pertinent
recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
/
4
-in. in
every 15 ft (7 mm in every 5 m) to prevent traps. Grade all
horizontal runs downward to risers. Use risers to connect to
heating section and to meter.
2. Protect all segments of piping system against physical and
thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a minimum of one hanger every 6 ft
(1.8 m). For pipe sizes larger than
1
/
2
-in., follow recommen-
dations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied petro-
leum gases as specified by local and/or national codes. If
using PTFE (Teflon
1
) tape, ensure the material is Double
Density type and is labeled for use on gas lines. Apply tape
per manufacturer’s instructions.
4. Pressure-test all gas piping in accordance with local and
national plumbing and gas codes before connecting piping to
unit.
NOTE: Pressure test the gas supply system after the gas supply
piping is connected to the gas valve. The supply piping must be
disconnected from the gas valve during the testing of the piping
systems when test pressure is in excess of 0.5 psig (3450 Pa). Pres-
sure test the gas supply piping system at pressures equal to or less
than 0.5 psig (3450 Pa). The unit heating section must be isolated
from the gas piping system by closing the external main manual
shutoff valve and slightly opening the ground-joint union.
Check for gas leaks at the field-installed and factory-installed
gas lines after all piping connections have been completed. Use
soap-and-water solution (or method specified by local codes
and/or regulations).
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of cor-
rect size. Never redrill an orifice. A burr-free and squarely aligned
orifice hole is essential for proper flame characteristics. See
Fig. 35.
Fig. 35 — Orifice Hole
LEGEND
*
Field supplied.
NOTE:
Follow all local codes.
NFGC –
National Fuel Gas Code
STEEL PIPE
NOMINAL DIAMETER
(in.)
SPACING OF SUPPORTS
X DIMENSION
(ft)
1
/
2
3
/
4
or 1
1
1
/
4
or larger
6
8
10
X
BASE UNIT
BASE RAIL
ROOF
CURB
9” MINIMUM CLEARANCE
FOR PANEL REMOVAL
MANUAL GAS
SHUTOFF VALVE
*
GAS
REGULATOR
*
48” MINIMUM
DRIP LEG
PER NFGC
*
FIELD-
FABRICATED
SUPPORT
*
FROM
GAS
METER
1. Teflon is a registered trademark of DuPont.
WARNING
Failure to follow this warning could result in personal injury,
death and/or property damage.
• Connect gas pipe to unit using a backup wrench to
avoid damaging gas controls.
• Never purge a gas line into a combustion chamber.
• Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections.
• Use proper length of pipe to avoid stress on gas control
manifold.
BURNER
ORIFICE
Содержание WeatherExpert 48LC B14 Series
Страница 4: ...4 Fig 2 48LC B14 Vertical Airflow ...
Страница 5: ...5 Fig 3 48LC B14 Horizontal Airflow ...
Страница 6: ...6 Fig 4 48LC B14 Back View and Condensate Drain Location ...
Страница 7: ...7 Fig 5 48LC B14 Corner Weights and Clearances ...
Страница 8: ...8 Fig 6 48LC B14 Bottom View ...
Страница 9: ...9 Fig 7 48LC B17 20 Vertical Airflow ...
Страница 10: ...10 Fig 8 48LC B17 20 Horizontal Airflow ...
Страница 11: ...11 Fig 9 48LC B17 20 Back View and Condensate Drain Location ...
Страница 12: ...12 Fig 10 48LC B17 20 Corner Weights and Clearances ...
Страница 13: ...13 Fig 11 48LC B17 20 Bottom View ...
Страница 14: ...14 Fig 12 48LC B24 26 Vertical Airflow ...
Страница 15: ...15 Fig 13 48LC B24 26 Horizontal Airflow ...
Страница 16: ...16 Fig 14 48LC B24 26 Back View and Condensate Drain Location ...
Страница 17: ...17 Fig 15 48LC B24 26 Corner Weights and Clearances ...
Страница 18: ...18 Fig 16 48LC B24 26 Bottom View ...
Страница 21: ...21 Fig 20 48LC B14 Roof Curb Details ...
Страница 22: ...22 Fig 21 48LC B17 20 Roof Curb Details ...
Страница 23: ...23 Fig 22 48LC B24 26 Roof Curb Details ...
Страница 30: ...30 Fig 40 48LC B14 26 VAV RTU Open Control Wiring Diagram ...
Страница 31: ...31 Fig 41 48LC B14 26 Power Wiring Diagram ...
Страница 53: ......