Installing the VVT Zone II
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
37
Wiring field-supplied actuators to the analog output
You can wire a high-torque actuator or parallel actuators to the controller's 0–10 Vdc analog output.
High-torque actuator
You can wire one of the following Belimo actuators to the VVT Zone II's analog output instead of using the
controller's built-in, 45 in.-lb (4 Nm) actuator.
NMX24-MFT P-10028
90 in.-lb (10 Nm) actuator with 0–10 Vdc control and 0–10 Vdc feedback
AMX24-MFT P-10028
180 in.-lb (20 Nm) actuator with 0–10 Vdc control and 0–10 Vdc feedback
1
Install the actuator according to the manufacturer's instructions.
2
Wire the actuator to the controller using the diagram below.
NOTE
For proper operation and to prevent damage to the devices, use the same polarity for the actuator's power
and the VVT Zone II's power.