Installing the UPC Open

 

 

 

UPC Open 

Carrier Proprietary and Confidential 

CARRIER CORPORATION ©2017   

Installation and Integration Guide 

 

All rights reserved 

 

 

Color Code 

Black, white, green, red 

Shielding 

If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire, terminated 

at controller 

UL temperature rating 

32–167°F (0–75°C) 

Voltage 

300 Vac, power limited 

Listing 

UL: NEC CL2P, or better 

 

 

ZS Sensor overview 

ZS Sensors are thermistor-based temperature sensors that may optionally sense humidity, CO

2

, or VOC. ZS 

Sensors are wired to the Rnet port on i-Vu® Open controllers. 

REQUIREMENTS

 

 

A v6.5 or later i-Vu® system 

 

v6.04.xxx or later controller drivers 

 
You can use the following ZS sensors: 

 

ZS Standard 

 

ZS Plus 

 

ZS Pro 

NOTES

 

 

A control program can use no more than 5 ZS Sensors, so you must use 2 control programs if your Rnet 

network has 10 sensors. 

 

The ZS CO2 model uses 190 mA during sample period. Use auxiliary 12 Vdc, unless it is the only device on 

the Rnet port. 

 
For basic user instructions, see the 

ZS Sensor User Guide

. For detailed installation instructions, see the 

ZS 

Sensors Installation Guide

 

 

SPT sensor overview 

The UPC Open is connected to a wall-mounted space temperature sensor to monitor room temperature. Wire SPT 

sensors to the UPC Open's 

Rnet

 port.  

The UPC Open supports the following: 

 

SPT Standard 

 

SPT Plus 

 

SPT Pro 

For basic user instructions, see the 

SPT Sensors Owner Guide

. For more detailed instructions, see the 

Carrier 

Sensors Installation Guide

  

NOTE  

If the Rnet has multiple SPT Standard sensors, you must give each a unique address on the Rnet.  

 

Содержание UPC Open

Страница 1: ...In ns st ta al ll la at ti io on n a an nd d I In nt te eg gr ra at ti io on n G Gu ui id de e CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog...

Страница 2: ...ur local Carrier office Important changes are listed in Document revision history at the end of this document CARRIER CORPORATION 2017 All rights reserved throughout the world i Vu is a registered tra...

Страница 3: ...pecifications 8 ZS Sensor overview 9 SPT sensor overview 9 To wire the ZS or SPT sensor to the UPC Open 10 Wireless sensor overview 10 To install the Wireless Adapter for wireless sensors 11 To wire a...

Страница 4: ......

Страница 5: ...eral purpose protocol converter The UPC Open can convert proprietary equipment data into open protocol data enabling a stand alone single piece of equipment to reside on a BACnet network where it can...

Страница 6: ...CN port Port 2 5 pin port supports EIA 485 3 wire connection to a single Carrier CCN controller LON OC port 14 pin communication port supports the LonWorks Option Card future Rnet port The UPC Open on...

Страница 7: ...0HF Cycoloy plastic Overall dimensions A B 5 3 16 in 13 2 cm 4 1 8 in 10 5 cm Mounting hole dimensions C D E 4 7 8 in 12 4 cm 2 1 20 in 5 2 cm 3 16 in 5 cm Panel depth 2 in 5 1 cm Weight 44 lbs 2 kg B...

Страница 8: ...edges Isolate from high voltage or electrostatic discharge Ensure that you are properly grounded Screw the UPC Open into an enclosed panel using the mounting slots on the coverplate Leave about 2 in...

Страница 9: ...ress that is unique on the MS TP or ARCNET network You can address the UPC Open before or after you wire it for power 1 If the UPC Open has been wired for power pull the screw terminal connector from...

Страница 10: ...NOTE Use the same polarity throughout the network segment 4 Set the communication type and baud rate For Set DIP switches 1 and 2 to DIP switch 3 Set DIP switch 4 to Set DIP switches 5 through 8 to MS...

Страница 11: ...r application which consists of 2 or 3 chillers configured for Lead Lag with a potential third chiller as a standby chiller In this application wire the CCN network between the UPC Open and chillers i...

Страница 12: ...nicating on the CCN Port NOTE If the CCN target address differs from what the UPC Open is configured for default 0 1 then only the transmit LED flashes about 1 time per second Wiring devices to the UP...

Страница 13: ...nsors ZS Standard ZS Plus ZS Pro NOTES A control program can use no more than 5 ZS Sensors so you must use 2 control programs if your Rnet network has 10 sensors The ZS CO2 model uses 190 mA during sa...

Страница 14: ...ommends that you use the following Rnet wiring scheme Connect this wire To this terminal Red Black White Green 12V Rnet Rnet Gnd Wireless sensor overview The Carrier wireless sensors designed for zone...

Страница 15: ...mains voltage to the Wireless Adapter To wire power and mount the Wireless Adapter NOTES The Wireless Adapter requires a 24 Vac or 24 Vdc power supply It is not powered by the Rnet If the Wireless Ad...

Страница 16: ...apter 7 Apply power to the external power supply 8 Verify that the LED on top of the Wireless Adapter is blinking See LED below 9 Turn on the controller s power LED The blue LED on the top of the Wire...

Страница 17: ...4 conductor Rnet cable and follow the instructions below For complete Equipment Touch installation instructions including wiring diagrams see the Equipment Touch Installation and Setup Guide 1 Turn of...

Страница 18: ...er s AC power ground could damage the USB Link and the controller If you are not sure of the wiring polarity use a USB isolator between the computer and the USB Link Purchase a USB isolator online fro...

Страница 19: ...Vu Control System page 15 to load your control program and graphic into the controller To install the UPC Open into an i Vu Control System You must complete the following procedures to successfully i...

Страница 20: ...hysical points by selecting the controller in the navigation tree and going to Properties page I O Points tab Enter your channel numbers under Num using your wire list Enter your expander address unde...

Страница 21: ...pplication the maximum number of UPC Open controllers allowed on the CCN bus is 3 CCN Alarm Acknowledger The UPC Open defaults as the CCN Acknowledger In a Multiple Chiller Application you must config...

Страница 22: ...tches are not replaceable but they will reset themselves if the condition that caused the fault returns to normal Rx Lights when the controller receives data from the network segment there is an Rx LE...

Страница 23: ...alternating with Run LED Ten second recovery period after brownout 14 flashes per second 14 flashes per second alternating with Run LED Brownout On On Failure Try the following solutions Turn the UPC...

Страница 24: ...fault configuration settings 1 Turn off the UPC Open s power switch 2 Put the Factory Defaults jumper on 3 Turn on the UPC Open s power switch 4 Remove the Factory Defaults jumper To replace the UPC O...

Страница 25: ...anual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correc...

Страница 26: ...Field Assistant and the i Vu interface on the Properties page Network Points tab The following example involves outside air temperature System Heat Cool Demand Level behaves similarly except that thei...

Страница 27: ...Device Address Binding allows the UPC Open to receive data from other Open controllers when they are connected by a network You must configure this method Currently the UPC Open allows Device Address...

Страница 28: ...ss Adapter for Wireless sensors To wire an Equipment Touch to the UPC Open New topics C D Wiring devices to the UPC Open s Rnet port Added Wireless Adapter for wireless sensors and Equipment Touch C D...

Страница 29: ......

Страница 30: ...CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 468 01 6 1 2017...

Отзывы: